Not incorporate any glazed areas unless the glass is safety glass as defined in AS 1288.
Only have doorways which are fitted with smoke doors complying with Specification 12.
Have all openings around penetrations and the junctions of the smoke-proof wall and the remainder of the building stopped with non-combustible material to prevent the free passage of smoke.
Incorporate smoke dampers where air-handling ducts penetrate the wall unless the duct forms part of a smoke hazard management system required to continue air movement through the duct during a fire.
a flush plasterboard ceiling lined with 13 mm standard grade plasterboard or a fire-protective covering, with all penetrations sealed against the free passage of smoke.
If plasterboard is used in the lining on a wall, it must be a minimum of 13 mm standard grade plasterboard.
Not incorporate any glazed areas unless the glass is safety glass as defined in AS 1288.
Only have doorways which are fitted with smoke doors complying with Specification 12.
Have all openings around penetrations and the junctions of the smoke-proof wall and the remainder of the building stopped with non-combustible material to prevent the free passage of smoke.
Incorporate smoke dampers where air-handling ducts penetrate the wall unless the duct forms part of a smoke hazard management system required to continue air movement through the duct during a fire.
A door required by C3D6 or this Specification to be smoke-proof or have an FRL, other than one that serves a fire compartment provided with a zone pressurisation system in accordance with AS 1668.1, must provide a smoke reservoir by not extending within 400 mm of the underside of—
a roof covering; or
the floor above; or
an imperforate false ceiling that will prevent the free passage of smoke.