Smoke doors must be constructed so that smoke will not pass from one side of the doorway to the other and, if they are glazed, there is minimal danger of a person being injured by accidentally walking into them.
A smoke door of one or two leaves satisfies S12C3 if it is constructed as follows:
The leaves are side-hung to swing—
in the direction of egress; or
in both directions.
The leaves are solid-core and at least 35 mm thick, or are capable of resisting smoke at 200°C for 30 minutes.
The leaves are fitted with smoke seals.
The leaves—
are normally in the closed position; or
operate such that—
they are closed automatically with the automatic closing operation initiated by smoke detectors, installed in accordance with the relevant provisions of AS 1670.1, located on each side of the doorway not more than 1.5 m horizontal distance from the doorway; and
in the event of power failure to the door, they will fail-safe in the closed position.
The leaves return to the fully closed position after each manual opening.
Any glazing incorporated in the door complies with AS 1288.
If a glazed panel is capable of being mistaken for an unobstructed exit, the presence of the glass must be identified by an opaque mid-height band, mid-rail, crash-bar or other opaque construction.