(1) A part of a building element is exposed to a fire-source feature if any of the horizontal straight lines between that part and the fire-source feature, or vertical projection of the feature, is not obstructed by another part of the building that—
an external wall of another building that stands on the allotment and the part concerned is more than 15 m above the highest part of that external wall; or
a side or rear boundary of the allotment and the part concerned is below the level of the finished ground at every relevant part of the boundary concerned.
(3) If various distances apply for different parts of a building element—
the entire element must have the FRL applicable to that part having the least distance between itself and the relevant fire-source feature; or
each part of the element must have the FRL applicable according to its individual distance from the relevant fire-source feature.
(4) The requirements of (3) do not override or permit any exemption from S5C3.
(1) Where a part of a building required to have an FRL depends upon direct vertical or lateral support from another part to maintain its FRL, that supporting part, subject to (2), must—
have an FRL not less than that required by other provisions of this Specification; and
of Type A construction if it complies with S5C15(a), (b) or (d); and
of Type B and C construction.
A column providing lateral support to a wall where the column complies with S5C6(1) and (2).
An element providing lateral support to a fire wall or fire-resisting wall, provided the wall is supported on both sides and failure of the element on one side does not affect the fire performance of the wall.
Method of attachment not to reduce the fire-resistance of building elements
2019: Spec C1.1: 2.4
The method of attaching or installing a finish, lining, ancillary element or service installation to the building element must not reduce the fire-resistance of that element to below that required.
2 storeys in some of its parts and 1 storey only in its remaining parts if the sum of the floor areas of the upper storeys of its 2 storey parts does not exceed the lesser of—
(3) Structures on roofs — A non-combustible structure situated on a roof need not comply with the other provisions of this Specification if it only contains—
lift motor equipment; or
one or more of the following:
Hot water or other water tanks.
Ventilating ductwork, ventilating fans and their motors.
Other service units that are non-combustible and do not contain flammable or combustible liquids or gases.
(4) Curtain walls and panel walls — A requirement for an external wall to have an FRL does not apply to a curtain wall or panel wall which is of non-combustible construction and fully protected by automatic external wall-wetting sprinklers.
(5) Balconies and verandahs — A balcony, verandah or the like and any incorporated supporting part, which is attached to or forms part of a building, need not comply with Table S5C11c, S5C11g, S5C21c, S5C21g, S5C24b or S5C24e if—
it does not form part of the only path of travel to a requiredexit from the building; and
in Type A construction—
it is situated not more than 2 storeys above the lowest storey providing direct egress to a road or open space; and
(1) This Clause does not apply to a Class 9b building that is a spectator stand or audience viewing area accommodating more than 100 persons as calculated according to D2D18.
the total floor area of all the mezzanines in the same room does not exceed 1/3 of the floor area of the room or 200 m2, whichever is the lesser; and
the FRL of each wall and column that supports any other part of the building within 6 m of the mezzanine is increased by the amount listed in Table S5C7.
Table S5C7 Increased FRLs — Construction surrounding mezzanines
Level otherwise required for any FRL criterion (mins)
(1) Shaftsrequired to have an FRL must be enclosed at the top and bottom by construction having an FRL not less than that required for the walls of a non-loadbearingshaft in the same building.
for any floor and any loadbearing wall, may be reduced to 60, except any FRL criterion of 90 for an external wall must be maintained when tested from the outside; and
it is lined on each side with standard grade plasterboard not less than 13 mm thick or similar non-combustible material; and
it extends—
to the underside of the floor next above; or
to the underside of a ceiling lined with standard grade plasterboard not less than 13 mm thick or a material with at least an equivalent level of fire protection; or
any insulation installed in the cavity of the wall is non-combustible; and
any construction joint, space or the like between the top of the wall and the floor, ceiling or roof is smoke sealed with intumescent putty or other suitable material.
(2) The concession described at (1) does not apply to fire-protected timber building elements.
Type A fire-resisting construction — fire-resistance of building elements
2019: Spec C1.1: 3.1 and Table 3
(1) In a building required to be of Type A construction—
each building element listed in Tables S5C11a, S5C11b, S5C11c, S5C11d, S5C11e, S5C11f and S5C11g, and any beam or column incorporated in it, must have an FRL not less than that listed in those Tables for the particular class of building concerned; and
the underside of a roof complying with Table S5C11g; or
if under S5C15 the roof is not required to comply with Table S5C11g, the underside of the non-combustible roof covering and, except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
a ceiling that is immediately below the roof and has a resistance to the incipient spread of fire to the roof space between the ceiling and the roof of not less than 60 minutes; and
the FRLs specified in Table S5C11c for an external column apply also to those parts of an internal column that face and are within 1.5 m of a window and are exposed through that window to a fire-source feature.
(2) For the purposes of (1)(c)(iii), fire-protected timber may be used, provided that—
the building is—
a separate building; or
a part of a building—
which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and
the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and
any insulation installed in the cavity of the timber building element required to have an FRL is non-combustible; and
cavity barriers are provided in accordance with Specification 9.
(3) For the purposes of Table S5C11a and Table S5C11b, external wall includes any column and other building element incorporated within it or other external building element.
Table S5C11a Type A construction: FRL of loadbearing parts of external walls
in a Class 2, 3, 5 or 9 building, the space below is not a storey, does not accommodate motor vehicles, is not a storage or work area, and is not used for any other ancillary purpose; or
it is a timber stage floor in a Class 9b building laid over a floor having the required FRL and the space below the stage is not used as a dressing room, store room, or the like; or
it is within a sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building; or
it is an open-access floor (for the accommodation of electrical and electronic services and the like) above a floor with the required FRL.
If a roof is required to have an FRL or its covering is required to be non-combustible, roof lights or the like installed in that roof must—
have an aggregate area of not more than 20% of the roof surface; and
be not less than 3 m from—
any boundary of the allotment other than the boundary with a road or public place; and
any part of the building which projects above the roof unless that part has the FRL required of a fire wall and any openings in that part of the wall for 6 m vertically above the roof light or the like are protected in accordance with C4D5; and
any roof light or the like in an adjoining sole-occupancy unit if the walls bounding the unit are required to have an FRL; and
any roof light or the like in an adjoining fire-separated section of the building; and
Type A fire-resisting construction — internal columns and walls: Concession
2019: Spec C1.1:3.7
For a building with an effective height of not more than 25 m and having a roof without an FRL in accordance with S5C15, in the storey immediately below that roof, internal columns other than those referred to in S5C11(1)(d) and internal walls other than fire walls and shaft walls may have—
(1) Notwithstanding S5C11, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—
a separate building; or
a part of a building—
which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
which is located above or below another classification, and the floor separating the classifications complies with C3D10; or
which is located above another Class 7 part of the building not used for carparking, and the floor separating the parts complies with Table S5C11g for a Class 7 part other than a carpark; or
which is located below another Class 7 part of the building not used for carparking, and the floor separating the parts complies with this clause.
an administration area associated with the functioning of the carpark; and
where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units, each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
excludes—
except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.
(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable:
Supporting only the roof (not used for carparking) and 3 m or more from a fire-source feature to which it is exposed: –/–/–.
Steel column, other than one covered by (i) and one that does not support a part of a building that is not used as a carpark—
60/–/–; or
an ESA/M of not greater than 26m2/tonne.
Any other column not covered by (i) or (ii): 60/–/–.
Beams:
Steel floor beam in continuous contact with a concrete floor slab—
60/–/–; or
an ESA/M of not greater than 30m2/tonne.
Any other beam: 60/–/–.
Fire-resisting lift and stair shaft (within the carpark only): 60/60/60.
Floor slab and vehicle ramp: 60/60/60.
Roof (not used for carparking): –/–/–.
(4) For the purposes of sub-clause (3):
ESA/M means the ratio of exposed surface area to mass per unit length.
Refer to Specification 17 for special requirements for a sprinkler system in a carpark complying with (3) and located within a multi-classified building.
notwithstanding S5C3(1)(c), timber framing may be used for a part of a building that provides support to a part of a building constructed of timber framing or non-combustible material in accordance with (a) and (b).
(2) A Class 2 or 3 building having a rise in storeys of not more than 4 may have the top three storeys constructed in accordance with (1) provided—
the lowest storey is used solely for the purpose of parking motor vehicles or for some other ancillary purpose; and
the lowest storey is constructed of concrete or masonry including the floor between it and the Class 2 or 3 part of the building above; and
the lowest storey and the storey above are separated by construction having an FRL of not less than 90/90/90 with no openings or penetrations that would reduce the fire-resisting performance of that construction except that a doorway in that construction may be protected by a –/60/30 self-closing fire door.
(3) In a Class 2 or 3 building complying with (1) or (2) and fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17, any FRL criterion prescribed in Tables S5C11a, S5C11d, S5C11e, S5C11f and S5C11g—
for any floor and any loadbearing wall, may be reduced to 60, except any FRL criterion of 90 for an external wall must be maintained when tested from the outside; and
any insulation installed in the cavity of the wall is non-combustible; and
any construction joint, space or the like between the top of the wall and the floor, ceiling or roof is smoke sealed with intumescent putty or other suitable material; and
any doorway in the wall is protected by a self-closing, tight fitting, solid core door not less than 35 mm thick.
Type B fire-resisting construction — fire-resistance of building elements
2019: Spec C1.1: 4.1 and Table 4
(1) In a building required to be of Type B construction—
each building element listed in Tables S5C21a, S5C21b, S5C21c, S5C21d, S5C21e, S5C21f and S5C21g, and any beam or column incorporated in it, must have an FRL not less than that listed in the Tables for the particular class of building concerned; and
if a stair shaft supports any floor or a structural part of it—
the floor or part must have an FRL of 60/–/– or more; or
the junction of the stair shaft must be constructed so that the floor or part will be free to sag or fall in a fire without causing structural damage to the shaft; and
the underside of the roof covering if it is non-combustible and, except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
450 mm above the roof covering if it is combustible; and
in a Class 2 or 3 building, except where within the one sole-occupancy units, or a Class 9a health-care building or a Class 9b building, a floor separating storeys or above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, must—
be constructed so that it is at least of the standard achieved by a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
have an FRL of at least 30/30/30; or
have a fire-protective covering on the underside of the floor, including beams incorporated in it, if the floor is combustible or of metal; and
in a Class 9c building a floor above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor must—
be constructed so that it is at least of the standard achieved by a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
(2) For the purposes of (1)(d)(iii), fire-protected timber may be used, provided that—
the building is—
a separate building; or
a part of a building—
which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and
cavity barriers are provided in accordance with Specification 9.
(3) For the purposes of Table S5C21a and Table S5C21b, external wall includes any column and other building element incorporated within it or other external building element.
Table S5C21a Type B construction: FRL of loadbearing parts of external walls
(1) Notwithstanding S5C21, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—
a separate building; or
a part of a building, and if occupying only part of a storey, is separated from the remaining part by a fire wall.
an administration area associated with the functioning of the carpark; and
where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
excludes—
except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.
(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable:
notwithstanding S5C3(1)(c), timber framing may be used for a part of a building that provides support to a part of a building constructed of timber framing or non-combustible material in accordance with (a) and (b).
(2) A Class 2 or 3 building having a rise in storeys of not more than 2 may have the top storey constructed in accordance with (1) provided—
the lowest storey is used solely for the purpose of parking motor vehicles or for some other ancillary purpose; and
the lowest storey is constructed of concrete or masonry including the floor between it and the Class 2 or 3 part of the building above; and
the lowest storey and the storey above are separated by construction having an FRL of not less than 90/90/90 with no openings or penetrations that would reduce the fire-resisting performance of that construction except that a doorway in that construction may be protected by a –/60/30 self-closing fire door.
(3) In a Class 2 or 3 building complying with (1) or (2) and fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17, any FRL criterion prescribed in Tables S5C21a, S5C21d, S5C21e, S5C21f and S5C21g; and —
for any loadbearing wall, may be reduced to 60, except any FRL criterion of 90 for an external wall must be maintained when tested from the outside; and
it is lined on both sides with 13 mm standard grade plasterboard or similar non-combustible material; and
it extends—
to the underside of the floor next above if that floor has an FRL of at least 30/30/30 or is lined on the underside with a fire-protective covering; or
any insulation installed in the cavity of the wall is non-combustible; and
any construction joints, spaces and the like between the top of the wall and the floor, ceiling or roof is smoke sealed with intumescent putty or other suitable material.
Type C fire-resisting construction — fire-resistance of building elements
2019: Spec C1.1: 5.1 and Table 5
(1) In a building required to be of Type C construction—
a building element listed in Tables S5C24a, S5C24b, S5C24c, S5C24d and S5C24e and any beam or column incorporated in it, must have an FRL not less than that listed in those Tables for the particular Class of building concerned; and
an external wall that is required by Table S5C24a to have an FRL need only be tested from the outside to satisfy the requirement; and
to the underside of the roof covering if it is non-combustible, and except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
450 mm above the roof covering if it is combustible; and
in a Class 2 or 3 building, except where within the one sole-occupancy unit, or a Class 9a health-care building, or a Class 9b building, a floor separating storeys, or above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor, must—
have an FRL of at least 30/30/30; or
have a fire-protective covering on the underside of the floor including beams incorporated in it and around the column, if the floor or column is combustible or of metal; and
in a Class 9c building a floor above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor, must—
have an FRL of at least 30/30/30; or
have a fire-protective covering on the underside of the floor including beams incorporated in it and around the column, if the floor or column is combustible or of metal.
(2) For the purposes of Table S5C24a and Table S5C24b, external wall includes any column and other building element incorporated within it or other external building element.
Table S5C24a Type C construction: FRL of parts of external walls
(1) Notwithstanding S5C24, a carpark may comply with this clause if it is an open-deck carpark or is protected with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and is—
a separate building; or
a part of a building, and if occupying only part of a storey, is separated from the remaining part by a fire wall.
an administration area associated with the functioning of the carpark; and
where the carpark is sprinklered, is associated with a Class 2 or 3 building and provides carparking for separate sole-occupancy units, each carparking area with an area not greater than 10% of its floor area for purposes ancillary to the sole-occupancy units; but
excludes—
except for (a), any area of another classification, or other part of a Class 7 building not used for carparking; and
a building or part of a building specifically intended for the parking of trucks, buses, vans and the like.
(3) For building elements in a carpark as described in (1) and (2), the following minimum FRLs are applicable: