A wall system need not be tested in accordance with this Specification for static pressure or impact if it is designed and constructed in accordance with the Deemed-to-Satisfy Provisions of Part B1 to resist the appropriate pressures and impacts defined in this Specification.
in spectator stand, sports stadium, cinema or theatre, railway or bus station or airport terminal, must be subjected to the tests and must fulfil the criteria set out in (2).
(2) For the purposes of (1), the following tests and criteria apply:
A static test by the imposition of a uniformly distributed load of 1.0 kPa (or its equivalent) in accordance with S6C10(b) and the damage and deflection criteria of S6C11(b) and (c) respectively.
A dynamic test by the fall of the impact bag through a height of 350 mm in accordance with S6C10(c) and the damage and deflection criteria of S6C11(b) and (d) respectively.
The surface indentation test of S6C10(d) and the surface indentation criterion of S6C11(e).
A static test by the imposition of a uniformly distributed load of 0.35 kPa (or its equivalent) in accordance with S6C10(b) and the damage and deflection criteria of S6C11(b) and (c) respectively.
A dynamic test by the fall of the impact bag through a height of 150 mm in accordance with S6C10(c) and the damage and deflection criteria of S6C11(b) and (d) respectively.
The surface indentation test of S6C10(d) and the surface indentation criterion of S6C11(e).
(1) In addition to the requirements of S6C3 and S6C4, a wall system for use in a lift shaft that is required to be fire-resisting must be subjected to dynamic test by the imposition of—
where the lift car speed is 7 m/s or less — 106 cycles of a uniformly distributed load between 0 and 0.2 kPa (or its equivalent); or
where the lift car speed is greater than 7 m/s — 106 cycles of a uniformly distributed load between 0 and 0.35 kPa (or its equivalent) in accordance with S6C10(e) and must fulfil the damage criteria of S6C11(b).
(2) The wall system must be subjected to the static test in accordance with S6C4(b) after the successful conclusion of the dynamic test specified in (1).
A static test by the imposition of a uniformly distributed load of 0.25 kPa (or its equivalent) in accordance with S6C10(b) and the damage and deflection criteria of S6C11(b) and (c) respectively.
A dynamic test by fall of the impact bag through a height of 100 mm in accordance with S6C10(c) and the damage and deflection criteria of S6C11(b) and (d) respectively.
The surface indentation test of S6C10(d) and the surface indentation criterion of S6C11(e).
If testing is carried out in-situ, it must be done on that part of the construction least likely, because of the particular combination of the height of the walls, the support conditions and other aspects of the construction, to resist the loads.
If a laboratory specimen is tested, the specimen must span only in the direction corresponding to the height of the wall and testing must be done in accordance with either (a) or (b) below:
The test specimen—
height (or length, if the specimen is tested horizontally) must be identical with the height between supports in the actual construction; and
must be supported at the top and bottom (or at each end if tested horizontally) by components identical with, and in a manner identical with, the actual construction.
If the distance between supports of the actual construction is more than 3 m, then a smaller specimen may be tested but—
the distance between supports must be not less than 3 m; and
forces, reactions and support conditions must be modelled so as to reproduce the behaviour of the actual construction if it were tested in-situ.
Tests must be carried out in accordance with the following:
Material tests — The methods specified for the constituent materials of the construction of the standards adopted by reference in the NCC.
For resistance to static pressure — The provisions for testing walls under transverse load in ASTM E72-15, except that—
support conditions must be as specified in S6C9; and
equivalent load shall mean the quarter-point load that produces the same deflection or central moment as appropriate; and
the timber species nominated in that standard may be substituted with a different species.
For resistance to impact — The provisions for testing wall systems in ASTM E695-03, except that—
the point of impact must be set 1.5 m above finished floor level or 1.5 m above the part of the specimen that corresponds to finished floor level; and
the impact bag must be not less than 225 mm in diameter and not more than 260 mm in diameter and have a mass of not less than 27.2 kg or more than 27.3 kg; and
the mass must be achieved by putting loose, dry sand into the bag and must be adjusted before each series of impact tests; and
where the impact bag and suspension cannot be vertical at the instant of impact on a curved surface or an inclined surface, the height of drop is the net height at the point of impact.
For resistance to surface indentation — The test for resistance to surface indentation must be carried out at three points on the surface of an undamaged sample sheet as follows:
A steel ball of 10 mm diameter with a load of 150 N must be placed gently on the surface of the sheet and allowed to remain in position for 5 minutes.
The ball and load must then be removed and the diameter of each impression of the ball on the surface measured.
For resistance of lift shaft construction to repetitive load — As for (b) except that—
it is sufficient to test one specimen with the pressure applied from the side of the construction on which the lift will operate; and
the load must be applied dynamically at a frequency not less than 1 Hz and not more than 3 Hz; and
equivalent load shall mean the quarter-point load that produces the same central moment as the distributed load.
The wall system or the specimen of it must fulfil the following criteria:
Materials — Materials must comply with the applicable standard adopted by reference in the NCC.
Damage — There must be no crack, penetration or permanent surface-deformation to a depth of more than 0.5 mm or any other non-elastic deformation or fastener failure.
Deflection — Static pressure — Under static pressure the deflection must not be more than—
1/240th of the height between supports; or
for construction other than a lift shaft — 30 mm; or