NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
E1
Part E1 Fire fighting equipmentPart E1 Fire fighting equipment
This Part focuses on provision of fire-fighting equipment which can enable occupants to fight the fire in its early stages and/or evacuate the building safely, facilitate fire brigade intervention and minimise the risk of fire spread between buildings.
Objectives
E1O1
Objective
2019: EO1
The Objective of this Part is to—
Functional Statements
E1F1
Fire-fighting equipment
2019: EF1.1
A building is to be provided with fire-fighting equipment to safeguard against fire spread—
Performance Requirements
E1P1
Fire hose reels
2019: EP1.1
A fire hose reel system must be installed to the degree necessary to allow occupants to safely undertake initial attack on a fire appropriate to—
E1P2
Fire extinguishers
2019: EP1.2
Fire extinguishers must be installed to the degree necessary to allow occupants to undertake initial attack on a fire appropriate to—
E1P3
Fire hydrants
2019: EP1.3
A fire hydrant system must be provided to the degree necessary to facilitate the needs of the fire brigade appropriate to—
E1P3 only applies to a building where a fire brigade is available to attend.
E1P4
Automatic fire suppression systems
2019: EP1.4
An automatic fire suppression system must be installed to the degree necessary to control the development and spread of fire appropriate to—
E1P5
Fire-fighting services in buildings under construction
2019: EP1.5
Suitable means of fire-fighting must be installed to the degree necessary in a building under construction to allow initial fire attack by construction workers and for the fire brigade to undertake attack on the fire appropriate to—
E1P6
Fire control centres
2019: EP1.6
Suitable facilities must be provided to the degree necessary in a building to co-ordinate fire brigade intervention during an emergency appropriate to—
An automatic fire detection system must be installed to the degree necessary to alert the fire brigade of fire so that fire fighting operations may be undertaken at the earliest possible time to limit property and environmental damage appropriate to—
Tas E1P7 only applies to—
Automatic fire detection system
Verification Methods
E1V1
Fire Safety Verification Method
2019: EV1.1
Deemed-to-Satisfy Provisions
E1D1
Deemed-to-Satisfy Provisions
2019: E1.0
Performance RequirementsE1P1 to E1P6 and TAS E1P7 are satisfied by complying with E1D2 to E1D16, TAS E1D17, and for farm buildings and farm sheds, Part I3.
Deemed-to-Satisfy Provisions
E1D2
Fire hydrants
2019: E1.3
Building Group | Floor area (m2) | Minimum water supply quantity (L) |
---|---|---|
Group A | 500 to 1,000 | 36,000 |
1,001 to 2,000 | 72,000 | |
2,001 to 5,000 | 144,000 | |
Group B | 500 to 1,000 | 72,000 |
1,001 to 2,000 | 144,000 | |
Group C | 5 L/m2 or 36,000 L at each location, whichever is greater |
A single water supply with the minimum water quantity outlined in Table SA E1D2 can serve more than one building.
E1D3
Fire hose reels
2019: E1.4
must be installed to provide the minimum flow and pressures required by clause 6.1 of AS 2441.
E1D4
Sprinklers
2019: E1.5
A sprinkler system must—
E1D5
Where sprinklers are required: all classifications
2019: Table E1.5
Sprinklers are required throughout the whole building if any part of the building has an effective height of more than 25 m—
E1D6
Where sprinklers are required: Class 2 and 3 buildings other than residential care buildings
2019: Table E1.5
E1D7
Where sprinklers are required: Class 3 building used as a residential care building
2019: Table E1.5
Sprinklers are required throughout—
Where sprinklers are required: Class 3 building
Sprinklers are required throughout a building containing—
E1D8
Where sprinklers are required: Class 6 building
2019: Table E1.5
In a Class 6 building, sprinklers are required in fire compartments where either of the following apply:
E1D9
Where sprinklers are required: Class 7a building, other than an open-deck carpark
2019: Table E1.5
In a Class 7a building, other than an open-deck carpark, sprinklers are required in fire compartments where more than 40 vehicles are accommodated.
E1D10
Where sprinklers are required: Class 9a health-care building used as a residential care building and Class 9c buildings
2019: Table E1.5
Where sprinklers are required: Class 9a and 9c buildings
E1D11
Where sprinklers are required: Class 9b buildings
2019: Table E1.5
E1D11(2) does not apply to a Class 9b early childhood centre—
E1D12
Where sprinklers are required: additional requirements
2019: Table E1.5
E1D13
Where sprinklers are required: occupancies of excessive hazard
2019: Table E1.5 (Note 4)
E1D14
Portable fire extinguishers
2019: E1.6 and Table E1.6
E1D15
Fire control centres
2019: E1.8
A fire control centre facility in accordance with Specification 19 must be provided for—
E1D16
Fire precautions during construction
2019: E1.9
In a building under construction—
E1D17
Provision for special hazards
2019: E1.10
Suitable additional provision must be made if special problems of fighting fire could arise because of—
Fire detection and alarm system
Part B4 of NCC Volume Three sets out the requirements for access for maintenance of fire-fighting water services.