Part E2 Smoke hazard management
Part E2 Smoke hazard management
Introduction to this Part
This Part is intended to reduce the risk of injury or loss of life for occupants due to the effects of smoke, including inhalation, if a fire occurs in a building. It provides for automatic warning of the presence of smoke or fire, and measures to ensure conditions within evacuation routes remain tenable long enough for occupants evacuate safely and to facilitate fire brigade intervention.
Objectives
E2O1
Objective
2019: EO2
The Objective of this Part is to—
safeguard occupants from illness or injury by warning them of a fire so that they may safely evacuate; and
safeguard occupants from illness or injury while evacuating during a fire.
In a building providing sleeping accommodation, occupants must be provided with automatic warning on the detection of smoke so they may evacuate in the event of a fire to a safe place.
Applications
E2P1 only applies to a Class 2, 3, 9a or 9c building or Class 4 part of a building.
(1) In the event of a fire in a building the conditions in any evacuation route must be maintained for the period of time occupants take to evacuate the part of the building so that—
the temperature will not endanger human life; and
the level of visibility will enable the evacuation route to be determined; and
the level of toxicity will not endanger human life.
(2) The period of time occupants take to evacuate referred to in (1) must be appropriate to—
the number, mobility and other characteristics of the occupants; and
the function or use of the building; and
the travel distance and other characteristics of the building; and
(3) The smoke exhaust and smoke-and-heat vent provisions of this Part do not apply to any area not used by occupants for an extended period of time such as a storeroom with a floor area less than 30 m2, sanitary compartment, plant room or the like.
(1) An air-handling system which does not form part of a smoke hazard management system in accordance with E2D4 to E2D20 and which recycles air from one fire compartment to another fire compartment or operates in a manner that may unduly contribute to the spread of smoke from one fire compartment to another fire compartment must, subject to (2), be designed and installed—
to operate as a smoke control system in accordance with AS 1668.1; or
such that it—
incorporates smoke dampers where the air-handling ducts penetrate any elements separating the fire compartments served; and
is arranged such that the air-handling system is shut down and the smoke dampers are activated to close automatically by smoke detectors complying with clause 7.5 of AS 1670.1.
(3) Miscellaneous air-handling systems covered by Sections 5 and 6 of AS 1668.1 serving more than one fire compartment (other than a carpark ventilation system) and not forming part of a smoke hazard management system must comply with these Sections of the Standard.
(4) A smoke detection system must be installed in accordance with S20C6 to operate AS 1668.1 systems that are provided for zone pressurisation and automatic air pressurisation for fire-isolated exits.
Buildings more than 25 m in effective height: Class 5, 6, 7b, 8 and 9b buildings
2019: Table E2.2a
(1) A Class 5, 6, 7b, 8 or 9b building or part of a building must be provided with a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the building is more than 25 m in effective height.
(2) The requirements of (1) do not apply to a building that has a fire compartment containing a Class 5, 6, 7b, 8 or 9b part (or a combination of these classes in the same fire compartment) where there is only one fire compartment containing these classifications in an otherwise Class 2, 3, 9a or 9c building.
Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
a system complying with (b)(i) or (b)(ii) must be installed; or
a smoke alarm or detector system complying with Specification 20 must be provided except that alarms or detectors need only be installed adjacent to each doorway into each fire-isolated stairway (set back horizontally from the doorway by a distance of not more than 1.5 m) to initiate a building occupant warning system for the Class 4 part.
Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the building has more than one fire compartment; or
Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4
2019: Table E2.2a
NCC Blurbs
(1) In a Class 5, 6, 7, 8 or 9 building of not more than 25 m in effective height, and which exceeds 18 000 m2 in floor area or 108 000 m3 in volume, the building must be provided with—
if the ceiling height of the fire compartment is not more than 12 m—
(2) For the purposes of (1), reference to ‘the building’ being provided with specified measures, means to the nominated classes within the building.
Notes
Refer to E2D14 and E2D15 for specific provisions applicable to a Class 6 building or part of a building (in a fire compartment having a floor area of more than 2000 m2).
Refer to NSW E2D16 to NSW E2D19 for specific provisions applicable to a Class 9b building or part of a building.
Refer to E2D5 and E2D8 where a Class 5, 6, 7b, 8 and 9b building contains a Class 2, 3 or 4 part.
NCC Title
Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4
NCC ID
_27a1f5a3-7565-4c04-a2b4-bae19da002e9
(1) In a Class 7 or 8 building of not more than 25 m in effective height, and which does not exceed 18 000 m2 in floor area nor exceed 108 000 m3 in volume, the building must be provided with—
a sprinkler system complying with Specification 17, and provided with perimeter vehicular access complying with C3D5(2); or
an automatic fire detection and alarm system complying with AS 1670.1 and monitored in accordance with S20C8; or
natural smoke venting, with ventilation openings distributed as evenly as practicable and comprising permanent openings at roof level with a free area not less than 1.5% of floor area and low level openings which may be permanent or readily openable with a free area not less than 1.5% of floor area.
(2) In a Class 5, 6, 7, 8 or 9 building of not more than 25 m in effective height, and which exceeds 18 000 m2 in floor area or 108 000 m3 in volume, the building must be provided with—
if the ceiling height of the fire compartment is not more than 12 m—
(3) For the purposes of (1) and (2), reference to ‘the building’ being provided with specified measures, means to the nominated classes within the building.
Notes
Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
Refer to E2D5 and E2D8 where a Class 5, 6, 7b, 8 and 9b building contains a Class 2, 3 or 4 part.
Buildings not more than 25 m in effective height: Class 9a and 9c buildings
2019: Table E2.2a
(1) A Class 9a health-care building or a Class 9c building, or a building containing a part thereof, which is not more than 25 m in effective height, must be provided throughout with—
automatic shutdown of any air-handling system which does not form part of a zone pressurisation system (other than individual room units with a capacity not more than 1000 L/s, systems serving critical treatment areas and miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) on the activation of—
smoke detectors installed in accordance with (a); and
any other installed fire detection and alarm system including a sprinkler system complying with Specification 17; and
in a building having a rise in storeys of more than 2 and not more than 25 m effective height (not being a Class 9c building)—
a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1; or
A Class 7a building, including a basement, provided with a mechanical ventilation system in accordance with AS 1668.2, must comply with clause 5.5 of AS 1668.1.
a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the basement has more than one fire compartment; or
Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
Basements with more than 3 below ground storeys or containing Class 6 or 9b occupancies with a large number of occupants may require special consideration in accordance with E2D21.
Class 6 buildings – in fire compartments more than 2000 m2: Class 6 building (not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit)
2019: Table E2.2b
(1) This clause applies to a Class 6 building not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit, except for—
is single storey with a main public entrance opening to a road or open space; and
is separated from other parts of the fire compartment by construction, including openings, penetrations and junctions with other building elements, that prevents the free passage of smoke; and
parts of any other classification that are smoke separated from a Class 6 part by construction complying with (a)(iii).
Class 6 buildings – in fire compartments more than 2000 m2: Class 6 building (containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit)
2019: Table E2.2b
(1) This clause applies to a Class 6 building containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit, except for—
is single storey with a main entrance opening to a road or open space; and
is separated from other parts of the fire compartment by construction, including openings, penetrations and junctions with other building elements, that prevents the free passage of smoke; and
parts of any other classification that are smoke separated from a Class 6 part by construction complying with (a)(ii)(C).
(2) Where the floor area of a Class 6 part of a fire compartment referred to in (1) is more than 2000 m2, the fire compartment, including the enclosed common walkway or mall, must be provided with—
A building or part of a building used as an assembly building must be provided with automatic shutdown of any air-handling system (other than non-ducted individual room units with a capacity not more than 1000 L/s and miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
smoke detectors installed complying with S20C6; and
any other installed fire detection and alarm system, including a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
an automatic zone pressurisation system in accordance with AS 1668.1 if the basement has more than one fire compartment; or if the basement forms part of a multi fire compartmented building served by the zone pressurisation system; or
a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
For the purposes of this clause, where a stage is separated from the auditorium by a proscenium wall incorporating a proscenium opening, a backstage room or area that is not separated from the stage by construction having an FRL of not less than 60/60/60, is taken to form part of the stage.
A building or part of a building used as an assembly building which has a stage with a floor area of more than 50 m2 and not more than 150 m2 must, over the stage, be provided with—
A building or part of a building used as an assembly building which has a stage with a floor area of more than 150 m2 must, over the stage, be provided with an automatic smoke exhaust system complying with Specification 21 (including Figure S21C2).
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
NCC Title
Class 9b – assembly buildings: all
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Class 9b – assembly buildings: all
NCC ID
_8f7e230e-b4d4-4b3b-a325-123311821d12
A Class 9b assembly building which is a nightclub, discotheque or the like must be provided with—
automatic shutdown of any air-handling system (other than miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
smoke detectors installed complying with S20C6; and
any other installed fire detection and alarm system, including a sprinkler system complying with Specification 17; and
where a building or part of a building has a floor area of more than 2000 m2, smoke hazard management measures as provided for under NSW E2D19.
Notes
Paragraph (a) applies only to an auditorium designed principally to accommodate an audience to an entertainment.
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
NCC Title
Class 9b – assembly buildings: night clubs, discotheques and the like
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Class 9b – assembly buildings: night clubs, discotheques and the like
NCC ID
_17946838-0ca2-4752-b134-b270a8d0faf8
Building Classes
1a,1b,2,3,4,5,6,7a,7b,8,9a,9c,10a,10b,10c
A Class 9b assembly building which is an exhibition hall must be provided with—
automatic shutdown of any air-handling system (other than miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
NCC Title
Class 9b – assembly buildings: exhibition halls, museums and art galleries
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Class 9b – assembly buildings: exhibition halls, museums and art galleries
NCC ID
_9e6990c1-4e7d-476e-a05f-d0d412017021
(1) This clause applies to a Class 9b assembly building where the building or part of the building is used as a theatre or public hall which—
is a school assembly, church or community hall, and has a stage and any backstage area with a total floor area of more than 300 m2; or
is not a school assembly, church or community hall, and has a stage and any backstage area with a total floor area of more than 200 m2; or
Class 9b – assembly buildings: theatres and public halls (not listed in E2D18) including lecture theatres and cinema/auditorium complexes
2019: Table E2.2b
NCC Blurbs
(1) Unless otherwise described in (2), in a building or part of a building used as an assembly building (not being a night club, discotheque or the like; or an exhibition hall, museum or art gallery) where the floor area of a fire compartment is more than 2000 m2, the fire compartment must be provided with—
a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
(2) The following buildings are exempt from the provisions of (1):
Sporting complexes, (including sports halls, gymnasiums, swimming pools, ice and roller rinks, and the like) other than indoor sports stadiums with total spectator seating for more than 1000 persons.
Churches and other places used solely for religious worship.
(3) A building containing a Class 9b early childhood centre must be provided with an automatic smoke detection and alarm system complying with Specification 20 throughout the whole building, including any part of another Class.
Notes
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
NCC Title
Class 9b – assembly buildings: other assembly buildings (not listed in NSW E2D16 to E2D18)
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Class 9b – assembly buildings: other assembly buildings (not listed in NSW E2D16 to E2D18)
NCC ID
_5d43d77a-2d24-46be-b6a3-f65e2e543dae
Building Classes
1a,1b,2,3,4,5,6,7a,7b,8,9a,9c,10a,10b,10c
(1) This clause applies to a Class 9b assembly building where the building or part of the building is used as a theatre or public hall not listed in E2D18 and includes lecture theatres and cinema/auditorium complexes.
(2) A building or part of a building referred to in (1)—
must be provided with automatic shutdown of any air-handling system (other than miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
2019: Table E2.2b
NCC Title
Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
NCC State
NSW
NCC Variation Type
Deletion
NCC SPTC Current
Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
NCC Notice
E2D20 does not apply in NSW. This clause is deleted from the BCA in NSW, as requirements for Class 9b – Assembly buildings in NSW are covered under NSW E2D16 to NSW E2D19.
NCC ID
idm140214735625376
(1) The requirements of (2)—
apply to a Class 9b assembly building where the building or part of the building is used for a purpose other than—
sporting complexes (including sports halls, gymnasiums, swimming pools, ice and roller rinks, and the like) other than an indoor sports stadium with total spectator seating for more than 1000; or
churches and other places used solely for religious worship.
(2) Each fire compartment, other than one in a building referred to in (1)(b), having a floor area of more than 2000 m2 must be provided with—
a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
(3) A building containing a Class 9b early childhood centre must be provided with an automatic smoke detection and alarm system complying with Specification 20 throughout the whole building, including any part of another class.