This Part is intended to reduce the likelihood of illness or loss of amenity as result of undue noise transmission between different parts of a building or adjoining buildings. This Part contains minimum requirements for sound insulation for walls, floors and penetrations through walls and floors for services such as pipework.
Objectives
F7O1
Objective
FO5
The Objective of this Part is to safeguard occupants from illness or loss of amenity as a result of undue sound being transmitted—
A floor separating sole-occupancy units or a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, must minimise the transmission of airborne and impact generated sound such that the separating floor, including the effect of services and their penetrations, has—
a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 for airborne sound; and
a weighted standardised impact sound pressure level (LnT,w) not more than 62 for impact generated sound.
A wall, including services and their penetrations, must minimise the transmission of sound such that—
for airborne sound—
a wall separating sole-occupancy units has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45; and
a wall separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, has a weighted standardised level difference (DnT,w) not less than 45; and
any door assembly located in a wall that separates a sole-occupancy unit from a stairway, public corridor, public lobby, or the like, has a weighted standardised level difference (DnT,w) not less than 25; and
for impact generated sound, a wall must have sufficient sound insulation to prevent illness or loss of amenity to the occupants if the wall separates—
Sound transmission through floors in a residential care building
2019: FP5.4
A floor separating sole-occupancy units must minimise the transmission of airborne and impact generated sound such that the separating floor, including the effect of services and their penetrations, has—
a weighted standardised level difference (DnT,w) not less than 40 for airborne sound; and
a weighted standardised impact sound pressure level (LnT,w) not more than 62 for impact generated sound.
Sound transmission through walls in a residential care building
2019: FP5.5
(1) A wall separating sole-occupancy units, or a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room, including the effect of services and their penetrations, must minimise the transmission of—
airborne sound such that the wall has a weighted standardised level difference (DnT,w) not less than 40; and
impact generated sound, if the wall separates a sole-occupancy unit from a kitchen or laundry.
(2) Sound insulation required by (1) must be sufficient to prevent illness or loss of amenity to the occupants.
Compliance with F7P1 to avoid the transmission of airborne and impact generated sound through floors is verified when it is measured in-situ that the separating floor has—
airborne: a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 when determined under AS/NZS ISO 717.1; and
impact: a weighted standardised impact sound pressure level (LnT,w) not more than 62 when determined under AS ISO 717.2.
Compliance with F7P2(a) to avoid the transmission of airborne sound through walls is verified when it is measured in-situ that—
a wall separating sole-occupancy units has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 when determined under AS/NZS ISO 717.1; or
a wall separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, has a weighted standardised level difference (DnT,w) not less than 45 when determined under AS/NZS ISO 717.1; or
any door assembly located in a wall that separates a sole-occupancy unit from a stairway, public corridor, public lobby, or the like, has a weighted standardised level difference (DnT,w) not less than 25 when determined under AS/NZS ISO 717.1.
Compliance with F7P3 to avoid the transmission of airborne and impact generated sound through floors is verified when it is measured in-situ that the separating floor has—
airborne: a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1; and
impact: a weighted standardised impact sound pressure level (LnT,w) not more than 62 when determined under AS ISO 717.2.
Sound transmission through walls [F7P4(1)(a) and (2)]
2019: FV5.4
Compliance with F7P4(1)(a) and (2) to avoid the transmission of airborne sound through walls is verified when it is measured in-situ that—
a wall separating sole-occupancy units has a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1; or
a wall separating a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room has a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1.
Determination of airborne sound insulation ratings
2019: F5.2
A form of construction required to have an airborne sound insulation rating must—
have the required value for weighted sound reduction index (Rw) or weighted sound reduction index with spectrum adaptation term (Rw + Ctr) determined in accordance with AS/NZS ISO 717.1 using results from laboratory measurements; or
(1) A floor in a building required to have an impact sound insulation rating must—
have the required value for weighted normalised impact sound pressure level (Ln,w) determined in accordance with AS ISO 717.2 using results from laboratory measurements; or
(2) A wall in a building required to have an impact sound insulation rating must—
for a Class 2 or 3 building be of discontinuous construction and
for a Class 9c building, must—
for other than masonry, be two or more separate leaves without rigid mechanical connection except at the periphery; or
be identical with a prototype that is no less resistant to the transmission of impact sound when tested in accordance with Specification 29 than a wall listed in S28C4 to S28C7.
(3) For the purposes of this Part, discontinuous construction means a wall having a minimum 20 mm cavity between 2 separate leaves, and—
for masonry, where wall ties are required to connect leaves, the ties are of the resilient type; and
for other than masonry, there is no mechanical linkage between leaves except at the periphery.
have an Rw + Ctr (airborne) not less than 50, if it separates sole-occupancy units; and
have an Rw (airborne) not less than 50, if it separates a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification; and
(2) A door may be incorporated in a wall in a Class 2 or 3 building that separates a sole-occupancy unit from a stairway, public corridor, public lobby or the like, provided the door assembly has an Rw not less than 30.
(3) A wall in a Class 9c building must have an Rw not less than 45 if it separates—
(1) If a duct or soil, waste or water supply pipe, including a duct or pipe that is located in a wall or floor cavity, serves or passes through more than one sole-occupancy unit, the duct or pipe must be separated from the rooms of any sole-occupancy unit by construction with an Rw + Ctr (airborne) not less than—
40 if the adjacent room is a habitable room (other than a kitchen); or
25 if the adjacent room is a kitchen or non-habitable room.
(2) If a stormwater pipe passes through a sole-occupancy unit, it must be separated in accordance with (1)(a) and (b).