NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
Filter
43
Specification 43 Bushfire protection for certain Class 9 buildings
Specification 43 Bushfire protection for certain Class 9 buildings
S43C1
Scope
New for 2022
(1) This Specification sets out bushfire protection measures for buildings described in G5D4.
(2) Compliance with this Specification does not guarantee the safety of building occupants or the maintenance of tenable conditions within a building during a bushfire event.
Explanatory information
The measures set out in this Specification are intended to operate in conjunction with other bushfire safety measures that lie outside the scope of the NCC. Information about these measures can be found in the Guide to NCC Volume One for Part G5.
(1) The building must be located not less than 12 m from any other building.
(2) The separation distance required by (1) need not be complied with if the building is constructed—
with external walls that have an FRL of not less than 60/60/60 when tested from the outside, including any openings protected in accordance with AS 3959 for BAL—19 or greater; or
for external walls and roof, using a material or system that satisfies the test criteria of AS 1530.8.1 for a radiant heat flux of 10 kW/m² or greater.
Separation from allotment boundaries and carparking areas
New for 2022
(1) The building must be located not less than 10 m from any allotment boundary or open carparking area/spots.
(2) The separation distance required by (1) need not be complied with if the building is constructed—
with external walls that have an FRL of not less than 60/60/60 when tested from the outside, including any openings protected in accordance with AS 3959 for BAL—19 or greater; or
for external walls and roof, using a material or system that satisfies the test criteria of AS 1530.8.1 for a radiant heat flux of 10 kW/m² or greater.
The external walls and roof of the building must be protected from potential hazards on the site such as liquefied petroleum gas bottles, fuel storage, storage of combustible materials, waste bins, vehicles, machinery, and the like, by—
a separation distance of not less than 10 m; or
where within the 10 m separation distance described in (a), constructed with external walls that have an FRL of not less than 60/60/60 when tested from the outside, including any openings protected in accordance with AS 3959 for BAL—19 or greater; or
for external walls and roof, using a material or system that satisfies the test criteria of AS 1530.8.1 for a radiant heat flux of 10 kW/m² or greater.
(1) Access pathways that lead to a road or open space must—
be readily identifiable; and
have an even surface; and
have a minimum clear width of not less than 1 m.
(2) If the access pathway is an accessway that is required to comply with Part D4, the requirements of Part D4 override (1) to the extent of any inconsistency.
An external area designed to hold people unable to be safely accommodated within the building, that may be exposed to radiant heat flux from a fire front during a bushfire event, must not be exposed to an incident radiant heat flux from the fire front exceeding 1 kW/m2 above background solar radiant heat flux.
To maintain internal tenability throughout the duration of occupancy during a bushfire event, the building must comply with the following:
An air handling system must be provided that is capable of—
being adjusted for full recycling of internal air for a period of not less than 4 hours to avoid the introduction of smoke into the building; and
maintaining an internal air temperature of not more than 25°C.
The building envelope must be designed such that if an air handling system required by (a) fails, then—
internal air temperatures can be maintained below 39°C; and
internal surface temperatures can be maintained below 60°C.
If the building is divided into separate compartments then, for the purposes of (a), each compartment must have a separate air handling system.
Each air handling system required by (a) must be designed to account for the activation of smoke detectors from low concentrations of smoke from external sources, so as to ensure that air-conditioning and other essential systems remain operational.
The building envelope must be constructed in accordance with AS 3959 – BAL 19 or greater, except that where the use of combustible materials is permitted by AS 3959, they are not to be used unless permitted by C2D10(4), (5) or (6).
A static water supply consisting of tanks, swimming pools, dams or the like, or a combination of these, together with suitable pumps, hoses and fittings, determined in consultation with the relevant fire brigade that—
is capable of providing the required flow rate for a period of not less than 4 hours; or
has a volume of 10 000 litres for each occupied building.
NCC Title
Supply of water for fire-fighting purposes
NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Supply of water for fire-fighting purposes
NCC ID
_1d3a91b4-d72b-43f6-8f7f-a23193547abc
Water for fire-fighting purposes must be available and consist of—
a static water supply consisting of tanks, swimming pools, dams or the like, or a combination of these, together with suitable pumps, hoses and fittings, capable of providing the required flow rate for a period of not less than 4 hours, determined in consultation with the relevant fire brigade.
(1) Emergency power must be provided to support, for not less than 4 hours before and 2 hours after the passing of the fire front during a bushfire event, the ongoing operation of—
air handling systems to maintain internal tenability; and