Part G4 Construction in alpine areas
Part G4 Construction in alpine areas
Introduction to this Part
This Part contains additional requirements for buildings constructed in an alpine area to address the potential for snow and ice to obstruct or delay evacuation and fire fighting or cause a hazard by falling on people.
Objectives
G4O1
Objective
2019: GO4
The Objective of this Part is to safeguard occupants in alpine areas from illness or injury from an emergency while evacuating a building.
Applications
G4O1 applies to a building constructed in an alpine area.
A building in an alpine area is to be provided with additional measures in view of the increased difficulties in fire-fighting and maintaining access and means of egress in snow conditions.
Applications
G4F1 only applies to a building constructed in an alpine area.
A building in an alpine area containing external trafficable structures forming part of the means of egress must be constructed so that those structures remain, as far as practicable, useable under snow conditions.
A building in an alpine area must be constructed so that snow or ice is not shed from the building onto the allotment, any adjoining allotment, road or public space in a location or manner that will—
obstruct a means of egress from any building to a road or open space; or
External doors which may be subject to the build-up of snow must—
open inwards or slide; and
if inward opening, be marked “OPEN INWARDS” on the inside face of the door in letters not less than 75 mm high in a colour contrasting with that of the background; and
be constructed so that the threshold is not less than 900 mm above the adjoining surface; and
if it serves a corridor or stairway, be positioned in an alcove or recess with—
no horizontal dimensions of the alcove or recess less than twice the width of the door; and
the door positioned to open against a wall such that the distance from any part of its swing to the nearest point of entry of the stairway or corridor is not less than the width of the door.
In a Class 2, 3, 5, 6, 7, 8 or 9 building or Class 4 part of a building, a system of emergency lighting must be installed in accordance with the Deemed-to-Satisfy Provisions of Part E4—
in every stairway (other than those within a sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building); and
if any part of an external wall is more than 3.6 m above the natural ground level — the distance of that part from a boundary other than a road alignment is not less than 2.5 m plus an additional 100 mm for each 300 mm or part thereof by which that part of the wall exceeds a height of 3.6 m; and
if an exit doorway discharges into a court between wings of a building and that area may be used for vehicle access to the building, the distance between wings must be not less than 4 m; and
where an exit doorway discharges opposite a feature that could entrap snow or an embankment that is more than 900 mm above the threshold of the doorway, a distance of not less than 4 m must be provided between the doorway and the feature.
Every Class 2, 3 or 9 building must display a notice clearly marked “FIRE ORDERS” in suitable locations near the main entrance and on each storey, explaining—
the method of operation of the fire alarm system and the location of all call-points; and
the location and methods of operation of all fire-fighting equipment; and