NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

45

Specification 45 Modelling profiles for J1V5

Specification 45 Modelling profiles for J1V5

This Specification contains the required modelling parameters for J1V5.

The heating loads and cooling loads must be calculated for the reference building sole-occupancy unit in accordance with the following:

  1. J3D7, for roofs.
  2. J3D9, for wall-glazing construction.
  3. J3D10, for floors.
  4. J4D5, for roof lights.
  5. Solar absorptance of 0.6 for external walls and roofs.
  6. Open area of 3.8 x 10-4 m2 per m2 of zone façade area for façade air infiltration, separate to designed natural ventilation openings.

(1) The heating load, cooling load and energy value for J1V5(1) and (2) must be calculated for both the proposed building and the reference building sole-occupancy unit using the same—

  1. heating load or cooling load limits, calculated using heating degree hours, cooling degree hours and dehumidification gram hours from Table S45C3a; and
  2. energy value factors from Tables S45C3b and S45C3c; and
  3. location, in accordance with S34C3(3); and
  4. climatic data, using the Typical Meteorological Year weather files drawn from the years 1990 to 2015 published by CSIRO; and
  5. adjacent structures and features; and
  6. orientation; and
  7. building form, including—
    1. roof geometry; and
    2. floor plan; and
    3. number of storeys; and
    4. location, extent and configuration of ground floors and basements; and
    5. the size and location of glazing; and
    6. external doors; and
    7. walls between or bounding sole-occupancy units; and
    8. balconies; and
  8. testing standards, including for insulation, glazing, water heater and unitary air-conditioning equipment; and
  9. fabric and glazing, including—
    1. thermal resistance of air films including any adjustment factors, moisture content of materials and the like; and
    2. internal shading devices, including their colour and criteria for operation; and
  10. system configuration and control of air-conditioning services and energy sources other than renewable energy generated on-site where present; and
  11. capacity and water usage, for on-site domestic heated water systems, assuming—
    1. a consumption rate in accordance with Table A.6.2 of AS/NZS 4234 of 10 L plus 1.25 L per m2 of floor area per sole-occupancy unit per day; and
    2. a seasonal load profile in accordance with Table A.6.3 of AS/NZS 4234; and
    3. a water inlet temperature of the monthly ground temperature in accordance with Table A.8 of AS/NZS 4234; and
    4. a water outlet temperature of 60°C; and
    5. the same calculation method for standing losses; and
  12. internal heating loads, in accordance with Table S45C3d; and
  13. occupancy profiles, in accordance with Tables S45C3e, S45C3f, S45C3g, S45C3h, S45C3i, S45C3j, S45C3k and S45C3l; and
  14. internal zoning, assuming—
    1. daytime air-conditioned zones include at least one living space and one dining space; and
    2. kitchen zones are a separate zone using virtual wall partitions at all times, and are only air-conditioned if adjacent to an external façade; and
    3. each bedroom is a night-time air-conditioned zone; and
    4. all other zones, including pantries, corridors, en-suites, walk-in robes, bathrooms, toilets, laundries and adjacent roof space or basement are unconditioned; and
  15. the same assumptions and means of calculating the temperature difference across air-conditioning zone boundaries; and
  16. the same floor coverings, furniture and fittings density; and
  17. the same internal artificial lighting illumination levels.

(2) Where present, the air-conditioning services, including all centralised domestic services infrastructure, of each sole-occupancy unit of both the proposed building and the reference building must be modelled with—

  1. in climate zone 2 to 8, a heating thermostat setting of—
    1. 20°C for all conditioned zones from 6:00 am to 12:00 am; and
    2. 18°C at all other times; and
  2. a cooling thermostat setting of—
    1. in climate zones 1, 2 and 3, 27°C for all daytime conditioned zones from 6:00 am to 11:00 pm; and
    2. in climate zone 4, 26°C for all daytime conditioned zones from 6:00 am to 11:00 pm; and
    3. in climate zone 5, 25°C for all daytime conditioned zones from 6:00 am to 11:00 pm; and
    4. in climate zones 6 and 7, 24°C for all daytime conditioned from 6:00 am to 11:00pm; and
    5. in climate zone 8, 23°C for all daytime conditioned zones from 6:00 am to 11:00 pm; and
    6. in all climate zones, a constant cooling thermostat setting of 24°C for all night-time conditioned zones.

(3) Natural ventilation of each sole-occupancy unit of the proposed building and the reference building must be modelled with the same—

  1. frequency of data output, being at least hourly; and
  2. opening flow properties in accordance with Table S45C3m; and
  3. wind pressure coefficients in accordance with Tables S45C3n and S45C3o; and
  4. infiltration values, unless building sealing is verified using J1V4, in which case infiltration values equal to the intended building air change rate at 50 Pa divided by 20 may be used for the proposed building only; and
  5. operation settings as follows:
    1. openings must shut when the external dry bulb temperature is less than or equal to a temperature 1°C higher than the air-conditioning service cooling set point; and
    2. openings must shut when the external dry bulb temperature is greater than or equal to a temperature 1°C lower than the air-conditioning service heating set point; and
    3. openings must remain open for all hours of the year that do not meet the above closing conditions.
Table S45C3a Annual heating degree hours, cooling degree hours and dehumidification gram hours for various locations
Climate zone Location Annual heating degree hours Annual cooling degree hours Annual dehumidification gram hours
1 Darwin 0 15770 15364
1 Port Hedland 859 16540 8011
1 Townsville 595 6392 5843
1 Weipa 4 12144 12565
1 Wyndham 126 26975 9184
1 Willis Island N/A N/A N/A
1 Cairns 268 6411 6030
1 Broome 624 14749 14083
2 Rockhampton 3283 6717 1701
2 Amberley 10958 4483 290
2 Brisbane 4744 2228 1415
2 Coffs Harbour 7137 1309 231
2 Mackay 976 3183 5214
2 Gladstone 568 4307 3543
2 Oakey 15392 3979 40
3 Longreach 6002 14634 505
3 Carnarvon 2260 4810 1023
3 Alice Springs 11767 13149 125
3 Charleville 11284 9580 230
3 Halls Creek 611 19571 2109
3 Tennant Creek 1171 18644 1747
3 Mount Isa 3060 15813 1797
3 Newman 6286 15240 645
4 Moree 13986 7291 151
4 Wagga 24833 4678 0
4 Mildura 19003 6300 11
4 Meekatharra 6883 12766 67
4 Oodnadatta 8352 13845 18
4 Kalgoorlie 13048 7763 31
4 Woomera 11754 8434 3
4 Cobar 13663 7616 101
4 Dubbo 20431 5332 36
4 Giles 6259 13082 81
5 Geraldton 6846 6365 10
5 Perth 11024 6084 0
5 Williamtown 11713 2802 276
5 Adelaide 13066 5132 0
5 Sydney RO (Observatory Hill) 7079 1466 129
5 Bickley 15664 4015 34
5 Swanbourne 6322 3332 63
5 Ceduna 14061 5212 53
5 Mandurah 6081 3131 2
5 Esperance 11009 1884 0
5 Manjimup 20910 2531 0
5 Mascot (Sydney Airport) 6357 1596 110
6 Nowra 14813 2801 56
6 Melbourne RO 14494 2416 0
6 East Sale 27229 1259 0
6 Katanning 21496 3566 14
6 Forrest 15294 8410 14
6 Albany 16131 932 0
6 Mount Lofty 41095 1626 0
6 Tullamarine (Melbourne Airport) 23496 2764 0
6 Mount Gambier 28496 2764 0
6 Moorabbin 20249 2291 0
6 Warnambool 27285 1406 1
6 Cape Otway 19279 960 3
6 Richmond 15607 3917 60
7 Armidale 33374 1039 9
7 Launceston (Ti Tree Bend) 30952 833 0
7 Canberra 35153 2863 0
7 Cabramurra 65831 79 0
7 Hobart 28542 451 0
7 Orange 40325 1192 2
7 Ballarat 37873 2585 2
7 Low Head 26047 80 0
7 Launceston Airport 39444 456 0
7 Learmonth 1646 14048 958
8 Thredbo (Village) 61209 147 0
Table Notes

If location is not listed, use the nearest appropriate.

Table S45C3b Energy factors based on fuel type
Fuel type ACT NSW NT Qld SA Tas Vic WA
Electricity: peak (kWh) 1.55 1.53 1.54 1.53 1.54 1.55 1.53 1.54
Electricity: shoulder (kWh) 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Electricity: off-peak (kWh) 0.78 0.79 0.79 0.79 0.78 0.78 0.79 0.79
Electricity: cont. load (kWh) 0.68 0.54 1.11 0.76 0.62 0.70 0.82 0.47
Natural gas (MJ) 0.18 0.14 0.16 0.24 0.13 0.21 0.10 0.16
Electricity: PV export (kWh) 0.42 0.39 1.10 0.51 0.35 0.50 0.53 0.29
Table S45C3c Electricity usage — timing for categories of usage
Hour Hour span Weekday
1 24-1 Off-peak
2 1-2 Off-peak
3 2-3 Off-peak
4 3-4 Off-peak
5 4-5 Off-peak
6 5-6 Off-peak
7 6-7 Off-peak
8 7-8 Peak
9 8-9 Peak
10 9-10 Shoulder
11 10-11 Shoulder
12 11-12 Shoulder
13 12-13 Shoulder
14 13-14 Shoulder
15 14-15 Shoulder
16 15-16 Shoulder
17 16-17 Peak
18 17-18 Peak
19 18-19 Peak
20 19-20 Peak
21 20-21 Shoulder
22 21-22 Shoulder
23 22-23 Off-peak
24 23-24 Off-peak
Table S45C3d Internal heat loads for lighting, cooking and appliances
Sole-occupancy unit area (excluding garage) (m2) Occupancy (m2/person) Day time lighting power density (6:00 am to 6:00 pm) (W/m2) Night-time lighting power density (6:00 pm to 6:00 am) (W/m2) Cooking in kitchen zone only (W/m2 kitchen area) Appliances (except oven) in whole sole-occupancy unit (W/m2)
≤ 100 41.2 4.0 4.0 36.2 4.38
> 100 to ≤ 125 44.3 4.0 4.0 34.7 3.52
> 125 to ≤ 150 47.8 4.0 4.0 28.9 2.99
> 150 to ≤ 175 51.7 4.0 4.0 24.8 2.60
> 175 to ≤ 200 55.8 4.0 4.0 25.3 2.26
> 200 to ≤ 225 60.0 4.0 4.0 22.5 2.02
> 225 to ≤ 250 64.4 4.0 4.0 20.2 1.84
> 250 to ≤ 275 68.9 4.0 4.0 18.4 1.68
> 275 to ≤ 300 73.3 4.0 4.0 16.9 1.55
> 300 to ≤ 325 77.5 4.0 4.0 15.6 1.44
> 325 to ≤ 350 81.6 4.0 4.0 14.5 1.34
> 350 to ≤ 375 85.4 4.0 4.0 13.5 1.26
> 375 89.0 4.0 4.0 12.7 1.19
Table S45C3e Lighting schedules for daytime zones
Time period (local standard time) December to February June to August March to May, September to November
12:00 am to 1:00 am 0% 0% 0%
1:00 am to 2:00 am 0% 0% 0%
2:00 am to 3:00 am 0% 0% 0%
3:00 am to 4:00 am 0% 0% 0%
4:00 am to 5:00 am 0% 0% 0%
5:00 am to 6:00 am 0% 0% 0%
6:00 am to 7:00 am 5% 10% 5%
7:00 am to 8:00 am 5% 10% 5%
8:00 am to 9:00 am 0% 0% 0%
9:00 am to 10:00 am 0% 0% 0%
10:00 am to 11:00 am 0% 0% 0%
11:00 am to 12:00 pm 0% 0% 0%
12:00 pm to 1:00 pm 0% 0% 0%
1:00 pm to 2:00 pm 0% 0% 0%
2:00 pm to 3:00 pm 0% 0% 0%
3:00 pm to 4:00 pm 0% 0% 0%
4:00 pm to 5:00 pm 5% 5% 5%
5:00 pm to 6:00 pm 15% 20% 20%
6:00 pm to 7:00 pm 25% 30% 25%
7:00 pm to 8:00 pm 30% 35% 30%
8:00 pm to 9:00 pm 25% 30% 30%
9:00 pm to 10:00 pm 20% 25% 25%
10:00 pm to 11:00 pm 10% 15% 15%
11:00 pm to 12:00 am 0% 0% 0%
Table S45C3f Lighting schedules for night-time zones
Time period (local standard time) December to February June to August March to May, September to November
12:00 am to 1:00 am 0% 0% 0%
1:00 am to 2:00 am 0% 0% 0%
2:00 am to 3:00 am 0% 0% 0%
3:00 am to 4:00 am 0% 0% 0%
4:00 am to 5:00 am 0% 0% 0%
5:00 am to 6:00 am 0% 0% 0%
6:00 am to 7:00 am 5% 10% 5%
7:00 am to 8:00 am 5% 10% 5%
8:00 am to 9:00 am 0% 0% 0%
9:00 am to 10:00 am 0% 0% 0%
10:00 am to 11:00 am 0% 0% 0%
11:00 am to 12:00 pm 0% 0% 0%
12:00 pm to 1:00 pm 0% 0% 0%
1:00 pm to 2:00 pm 0% 0% 0%
2:00 pm to 3:00 pm 0% 0% 0%
3:00 pm to 4:00 pm 0% 0% 0%
4:00 pm to 5:00 pm 0% 0% 0%
5:00 pm to 6:00 pm 15% 20% 20%
6:00 pm to 7:00 pm 25% 30% 25%
7:00 pm to 8:00 pm 30% 35% 30%
8:00 pm to 9:00 pm 25% 30% 30%
9:00 pm to 10:00 pm 20% 25% 25%
10:00 pm to 11:00 pm 10% 15% 10%
11:00 pm to 12:00 am 0% 0% 0%
Table S45C3g Cooking schedules
Time period (local standard time) December to February June to August March to May, September to November
12:00 am to 1:00 am 0% 0% 0%
1:00 am to 2:00 am 0% 0% 0%
2:00 am to 3:00 am 0% 0% 0%
3:00 am to 4:00 am 0% 0% 0%
4:00 am to 5:00 am 0% 0% 0%
5:00 am to 6:00 am 0% 0% 0%
6:00 am to 7:00 am 0% 0% 0%
7:00 am to 8:00 am 5% 5% 5%
8:00 am to 9:00 am 10% 10% 10%
9:00 am to 10:00 am 15% 15% 15%
10:00 am to 11:00 am 10% 15% 10%
11:00 am to 12:00 pm 15% 15% 15%
12:00 pm to 1:00 pm 15% 20% 20%
1:00 pm to 2:00 pm 15% 25% 20%
2:00 pm to 3:00 pm 15% 20% 20%
3:00 pm to 4:00 pm 15% 15% 15%
4:00 pm to 5:00 pm 20% 25% 20%
5:00 pm to 6:00 pm 30% 50% 40%
6:00 pm to 7:00 pm 60% 100% 80%
7:00 pm to 8:00 pm 70% 90% 80%
8:00 pm to 9:00 pm 40% 40% 40%
9:00 pm to 10:00 pm 20% 20% 20%
10:00 pm to 11:00 pm 10% 10% 10%
11:00 pm to 12:00 am 5% 5% 5%
Table S45C3h Appliance schedule for all zones
Time period (local standard time) December to February June to August March to May, September to November
12:00 am to 1:00 am 45% 45% 45%
1:00 am to 2:00 am 40% 40% 40%
2:00 am to 3:00 am 35% 40% 35%
3:00 am to 4:00 am 35% 40% 35%
4:00 am to 5:00 am 35% 40% 35%
5:00 am to 6:00 am 40% 40% 40%
6:00 am to 7:00 am 50% 55% 50%
7:00 am to 8:00 am 60% 75% 65%
8:00 am to 9:00 am 50% 55% 50%
9:00 am to 10:00 am 45% 50% 50%
10:00am to 11:00 am 45% 55% 50%
11:00 am to 12:00 pm 45% 50% 45%
12:00 pm to 1:00 pm 45% 50% 45%
1:00 pm to 2:00 pm 45% 50% 45%
2:00 pm to 3:00 pm 45% 50% 45%
3:00 pm to 4:00 pm 45% 50% 45%
4:00 pm to 5:00 pm 70% 85% 75%
5:00 pm to 6:00 pm 85% 100% 90%
6:00 pm to 7:00 pm 75% 85% 80%
7:00 pm to 8:00 pm 60% 70% 65%
8:00 pm to 9:00 pm 65% 75% 70%
9:00 pm to 10:00 pm 60% 70% 65%
10:00 pm to 11:00 pm 55% 60% 55%
11:00 pm to 12:00 am 50% 55% 50%
Table S45C3i Occupancy schedules
Time period (local standard time) Weekdays Weekends
12:00 am to 1:00 am 0% 0%
1:00 am to 2:00 am 0% 0%
2:00 am to 3:00 am 0% 0%
3:00 am to 4:00 am 0% 0%
4:00 am to 5:00 am 0% 0%
5:00 am to 6:00 am 0% 0%
6:00 am to 7:00 am 30% 30%
7:00 am to 8:00 am 30% 30%
8:00 am to 9:00 am 100% 30%
9:00 am to 10:00 am 100% 100%
10:00 am to 11:00 am 50% 100%
11:00 am to 12:00 pm 50% 100%
12:00 pm to 1:00 pm 50% 100%
1:00 pm to 2:00 pm 50% 50%
2:00 pm to 3:00 pm 50% 50%
3:00 pm to 4:00 pm 50% 50%
4:00 pm to 5:00 pm 100% 50%
5:00 pm to 6:00 pm 100% 50%
6:00 pm to 7:00 pm 100% 100%
7:00 pm to 8:00 pm 100% 100%
8:00 pm to 9:00 pm 100% 100%
9:00 pm to 10:00 pm 30% 100%
10:00 pm to 11:00 pm 30% 30%
11:00 pm to 12:00 am 0% 0%
Table S45C3j Heating, ventilation and air-conditioning schedules for daytime zones
Time period (local standard time) Heating, ventilation and air-conditioning on/off
12:00 am to 1:00 am Off
1:00 am to 2:00 am Off
2:00 am to 3:00 am Off
3:00 am to 4:00 am Off
4:00 am to 5:00 am Off
5:00 am to 6:00 am Off
6:00 am to 7:00 am On
7:00 am to 8:00 am On
8:00 am to 9:00 am On
9:00 am to 10:00 am On
10:00 am to 11:00 am On
11:00 am to 12:00 pm On
12:00 pm to 1:00 pm On
1:00 pm to 2:00 pm On
2:00 pm to 3:00 pm On
3:00 pm to 4:00 pm On
4:00 pm to 5:00 pm On
5:00 pm to 6:00 pm On
6:00 pm to 7:00 pm On
7:00 pm to 8:00 pm On
8:00 pm to 9:00 pm On
9:00 pm to 10:00 pm On
10:00 pm to 11:00 pm On
11:00 pm to 12:00 am Off
Table Notes

If windows are open in accordance with S45C3(3)(e), the heating, ventilation and air-conditioning schedule must be Off.

Table S45C3k Occupancy schedules for night-time zones
Time period (local standard time) Weekdays Weekends
12:00 am to 1:00 am 100% 100%
1:00 am to 2:00 am 100% 100%
2:00 am to 3:00 am 100% 100%
3:00 am to 4:00 am 100% 100%
4:00 am to 5:00 am 100% 100%
5:00 am to 6:00 am 100% 100%
6:00 am to 7:00 am 50% 50%
7:00 am to 8:00 am 50% 50%
8:00 am to 9:00 am 50% 50%
9:00 am to 10:00 am 0% 0%
10:00 am to 11:00 am 0% 0%
11:00 am to 12:00 pm 0% 0%
12:00 pm to 1:00 pm 0% 0%
1:00 pm to 2:00 pm 0% 0%
2:00 pm to 3:00 pm 0% 0%
3:00 pm to 4:00 pm 0% 0%
4:00 pm to 5:00 pm 0% 0%
5:00 pm to 6:00 pm 0% 0%
6:00 pm to 7:00 pm 50% 50%
7:00 pm to 8:00 pm 50% 50%
8:00 pm to 9:00 pm 50% 50%
9:00 pm to 10:00 pm 100% 100%
10:00 pm to 11:00 pm 100% 100%
11:00 pm to 12:00 am 100% 100%
Table S45C3l Heating, ventilation and air-conditioning schedules for night-time zones
Time period (local standard time) All days, heating, ventilation and air-conditioning on/off
12:00 am to 1:00 am On
1:00 am to 2:00 am On
2:00 am to 3:00 am On
3:00 am to 4:00 am On
4:00 am to 5:00 am On
5:00 am to 6:00 am On
6:00 am to 7:00 am On
7:00 am to 8:00 am On
8:00 am to 9:00 am On
9:00 am to 10:00 am Off
10:00 am to 11:00 am Off
11:00 am to 12:00 pm Off
12:00 pm to 1:00 pm Off
1:00 pm to 2:00 pm Off
2:00 pm to 3:00 pm Off
3:00 pm to 4:00 pm Off
4:00 pm to 5:00 pm Off
5:00 pm to 6:00 pm Off
6:00 pm to 7:00 pm On
7:00 pm to 8:00 pm On
8:00 pm to 9:00 pm On
9:00 pm to 10:00 pm On
10:00 pm to 11:00 pm On
11:00 pm to 12:00 am On
Table Notes

If windows are open in accordance with S45C3(3)(e), the Heating, ventilation and air-conditioning schedule must be Off.

Table S45C3m Window opening area percentage
Window type Opening area
Any window with restricted opening due to safety requirements 10%
Sliding and double hung 45%
Casement, awning, louvre, bi-fold, pivot, tilt and turn and French 90%
Table S45C3n Wind pressure coefficients for natural ventilation of low-rise buildings (total height less than 12 m)
Exposure type Façade component Wind direction (0° perpendicular to face)
0 45 90 135 180
Exposed Wall 0.70 035 -0.50 -0.40 -0.20
Roof pitch < 10 degrees -0.80 -0.70 -0.60 -0.50 -0.40
Roof pitch 10 to 30 degrees -0.40 -0.50 -0.60 -0.50 -0.40
Roof pitch > 30 degrees 0.30 -0.40 -0.60 -0.40 -0.50
Semi-exposed Wall 0.40 0.10 -0.30 -0.35 -0.20
Roof pitch < 10 degrees -0.60 -0.50 -0.40 -0.50 -0.60
Roof pitch 10 to 30 degrees -0.35 -0.45 -0.55 -0.45 -0.35
Roof pitch > 30 degrees 0.30 -0.50 -0.60 -0.50 -0.50
Sheltered Wall 0.20 0.05 -0.25 -0.30 -0.25
Roof pitch < 10 degrees -0.50 -0.50 -0.40 -0.50 -0.50
Roof pitch 10 to 30 degrees -0.30 -0.40 -0.50 -0.40 -0.30
Roof pitch > 30 degrees 0.25 -0.30 -0.50 -0.30 -0.40
Table Notes

Pressure coefficient exposure categories are defined as follows:

  1. Exposed – no obstructions surrounding the building (e.g. open fields or bodies of water).
  2. Semi-exposed – some obstructions comparable to the height of the building on some but not all sides.
  3. Sheltered – obstructions comparable to the height of the building on all sides.
Table S45C3o Wind pressure coefficients for natural ventilation of high-rise building (total height more than 12 m)
Exposure type Façade component Wind direction (0° perpendicular to face)
0 45 90 135 180
Exposed Wall h/H = 0.0 0.30 0.22 -0.23 -0.43 -0.24
Wall h/H = 0.2 0.32 0.22 -0.43 -0.44 -0.25
Wall h/H = 0.4 0.39 0.16 -0.56 -0.43 -0.27
Wall h/H = 0.6 0.55 0.24 -0.62 -0.41 -0.29
Wall h/H = 0.8 0.65 0.32 -0.65 -0.39 -0.28
Wall h/H = 1.0 0.40 0.15 -0.65 -0.38 -0.26
Flat roof h/H = 0.0 -0.23 -0.23 -0.23 -0.23 -0.23
Flat roof h/H = 0.2 -0.43 -0.43 -0.43 -0.43 -0.43
Flat roof h/H = 0.4 -0.56 -0.56 -0.56 -0.56 -0.56
Flat roof h/H = 0.6 -0.62 -0.62 -0.62 -0.62 -0.62
Flat roof h/H = 0.8 -0.65 -0.65 -0.65 -0.65 -0.65
Flat roof h/H = 1.0 -0.65 -0.65 -0.65 -0.65 -0.65
Semi-exposed Wall h/H = 0.0 0.19 0.08 -0.15 -0.28 -0.15
Wall h/H = 0.2 0.20 0.08 -0.28 -0.29 -0.16
Wall h/H = 0.4 0.25 0.10 -0.36 -0.28 -0.18
Wall h/H = 0.6 0.36 0.16 -0.40 -0.27 -0.19
Wall h/H = 0.8 0.42 0.20 -0.42 -0.25 -0.18
Wall h/H = 1.0 0.26 0.10 -0.42 -0.25 -0.17
Flat roof h/H = 0.0 -0.15 -0.15 -0.15 -0.15 -0.15
Flat roof h/H = 0.2 -0.28 -0.28 -0.28 -0.28 -0.28
Flat roof h/H = 0.4 -0.36 -0.36 -0.36 -0.36 -0.36
Flat roof h/H = 0.6 -0.40 -0.40 -0.40 -0.40 -0.40
Flat roof h/H = 0.8 -0.42 -0.42 -0.42 -0.42 -0.42
Flat roof h/H = 1.0 -0.42 -0.42 -0.42 -0.42 -0.42
Sheltered Wall h/H = 0.0 0.10 0.04 -0.08 -0.15 -0.08
Wall h/H = 0.2 0.11 0.04 -0.15 -0.15 -0.08
Wall h/H = 0.4 0.13 0.05 -0.19 -0.15 -0.09
Wall h/H = 0.6 0.19 0.08 -0.21 -0.14 -0.10
Wall h/H = 0.8 0.22 0.11 -0.22 -0.13 -0.09
Wall h/H = 1.0 0.32 0.05 -0.22 -0.13 -0.09
Flat roof h/H = 0.0 -0.08 -0.08 -0.08 -0.08 -0.08
Flat roof h/H = 0.2 -0.15 -0.15 -0.15 -0.15 -0.15
Flat roof h/H = 0.4 -0.19 -0.19 -0.19 -0.19 -0.19
Flat roof h/H = 0.6 -0.21 -0.21 -0.21 -0.21 -0.21
Flat roof h/H = 0.8 -0.22 -0.22 -0.22 -0.22 -0.22
Flat roof h/H = 1.0 -0.22 -0.22 -0.22 -0.22 -0.22
Table Notes
  1. Pressure coefficient exposure categories are defined as follows:
    1. Exposed – no obstructions surrounding the building (e.g. open fields or bodies of water).
    2. Semi-exposed – some obstructions comparable to the height of the building on some but not all sides.
    3. Sheltered – obstructions comparable to the building height on all sides.
  2. h = height of natural ventilation opening above ground.
  3. H = height of roof of building above ground.