NCC 2019 Volume Three Amendment 1
Search the National Construction Code editions
This Part sets out the requirements for the design, construction, installation, replacement, repair, alteration and maintenance of any part of a sanitary plumbing system of a property including from sanitary fixtures and appliances to an approved disposal system.
OBJECTIVE
CO1
The Objective of this Part is to—
FUNCTIONAL STATEMENTS
CF1
Sanitary fixtures and sanitary appliances must be provided with an adequate disposal system that does not impact adversely on occupants of the premises, property, the environment or the Network Utility Operator's infrastructure.
A sanitary plumbing system must ensure the following:
Sewage or sullage is transferred to a sanitary drainage system or an approved disposal system.
Access for maintenance of mechanical components, operational controls and for clearing blockages.
Ventilation, to avoid hydraulic load imbalance is provided.
Effective and efficient water use.
A sanitary plumbing system must avoid the following:
Entry of water, sewage, sullage, foul air and gases from the system into buildings.
Damage from superimposed loads, ground movement or root penetration.
Entry of surface water, subsurface water and stormwater into the system.
Where a non-flushing (waterless) urinal is to be installed to a sanitary plumbing system comprising copper, copper alloy or other metallic piping, undiluted discharge transported through such pipework may increase the likelihood of corrosion.
Practitioners should also be aware that undiluted discharge, transported through pipework of any material, can cause a build-up of struvite (ammonium magnesium phosphate) inside the pipework, potentially causing blockage within the sanitary plumbing system.
There are no Verification Methods in this Part.
Performance RequirementCP1.1 is satisfied by complying with C1.2 and C1.3.
The invert level of a trap or gully weir must be a minimum of 10 mm higher than the soffit of the pipe to which it connects.
The design, construction, installation, replacement, repair, alteration and maintenance of a sanitary plumbing system must be in accordance with AS/NZS 3500.2.
Item |
NCC Volume One Class 2 to 9 buildings |
NCC Volume Two Class 1 and 10 buildings |
---|---|---|
Termite management for attachments to buildings and penetrations through a slab |
||
Penetrations for pipework through a vapour barrier |
||
Pipework in timber bearers and joists of solid timber or engineered wood products |
||
Fittings, fixtures and pipework installations in steel framed construction |
||
Penetrations through a fire-resisting wall or floor |
C3 Protection of openings | |
Fixtures or fittings in a wet area |
F1 Damp and weather proofing | |
Service pipework external to the building and penetrations through roof cladding in a bushfire prone area |
||
Pipework sound insulation |