Specification 28 Sound insulation for building elementsThis Specification lists the weighted sound reduction index RW for some common forms of construction.
This Specification lists the weighted sound reduction index RW for some common forms of construction.
Specification 28 gives information on the weighted sound reduction index (Rw), weighted sound reduction index with spectrum adaptation term (Rw + Ctr) and weighted normalised impact sound pressure level with spectrum adaptation term (Ln,w) for some common forms of building construction. It also list examples of discontinuous construction.
Further information can be obtained through literature produced by building product manufacturers.
The forms of construction listed in NT S28C3 are considered to have the RW stated in that clause if installed as follows:
Wall systems listed in S28C4 to S28C7 having a minimum 20 mm cavity between 2 separate leaves are deemed to be discontinuous construction if—
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C4a.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, when constructed as shown in Figure S28C4b.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C4c.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C4d.
has an with an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed in accordance with Figure S28C5d.
has an with an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed in accordance with Figure S28C5e.
has an Rw of not less than 45, if constructed as shown in Figure S28C5i.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C6a.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C6b.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C6c.
has an Rw of not less than 50, if constructed as shown in Figure S28C6d.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C7a.
has an Rw of not less than 50, if constructed as shown in Figure S28C7b.
has an Rw of not less than 45, if constructed as shown in Figure S28C7c.
has an Rw of not less than 45, if constructed as shown in Figure S28C7d.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C7e.
has an Rw + Ctr of not less than 50 and an Rw of not less than 50, if constructed as shown in Figure S28C7f.
has an Rw of not less than 50, if constructed as shown in Figure S28C7g.
has an Rw of not less than 45, if constructed as shown in Figure S28C7i.
has an Rw + Ctr of not less than 50, an Ln,w of not more than 62 and an Rw of not less than 50, if constructed as shown in Figure S28C8a.
has an Rw + Ctr of not less than 50, an Ln,w of not more than 62 and an Rw of not less than 50, if constructed as shown in Figure S28C9.
has an Rw + Ctr of not less than 50, an Ln,w of not more than 62 and an Rw of not less than 50, if constructed as shown in Figure S28C10a.
has an Rw + C of not less than 45 and an Rw of not less than 45, if constructed as shown in Figure S28C10b.