NSW Part J(A)5 Facilities for energy monitoring

NSW Part J(A)5 Facilities for energy monitoring

NSW J(A)5.0 Deemed-to-Satisfy Provisions

(a)

Where a Deemed-to-Satisfy Solution is proposed, Performance Requirement NSW J(A)P3 is satisfied by complying with NSW J(A)5.1 and NSW J(A)5.3.

(b)

Where a Performance Solution is proposed, the relevant Performance Requirement must be determined in accordance with A2.2(3) and A2.4(3) as applicable.

NSW J(A)5.1 Application of Part

The Deemed-to-Satisfy Provisions of this Part apply to a Class 2 building except within a sole-occupancy unit.

NSW J(A)5.2 * * * * *

NSW J(A)5.3 Compliance with BCA provisions

Class 2 buildings must comply with the national BCA provisions of J8.3.