NCC 2019 Volume One Amendment 1
Search the National Construction Code editions
Specification JVa Additional requirements
In addition to the modelling requirements for JV1, JV2 and JV3, a building must comply with—
for general thermal construction, J1.2; and
for deactivation, control and insulation of air-conditioning and mechanical ventilation systems—
J5.2(a)(i); and
J5.2(a)(ii)(A); and
J5.2(a)(iv); and
J5.2(a)(vi); and
J5.2(b); and
J5.2(c); and
J5.3(b); and
J5.3(d); and
J5.5; and
J5.6; and
J5.8; and
for testing package air-conditioning equipment not less than 65 kWr, AS/NZS 3823.1.2 at test condition T1; and
for testing a refrigeration chiller, AHRI 551/591; and
for interior artificial lighting and power control, J6.3; and
for interior decorative and display lighting, J6.4; and
for artificial lighting around the exterior of a building, J6.5; and
for boiling water and chilled water storage units, J6.6; and
for deactivation of swimming pool heating and pumping, J7.3(b)(ii) and J7.3(c); and
for deactivation of spa pool heating and pumping, J7.4(b)(ii) and J7.4(c); and
for facilities for energy monitoring, Part J8; and
for deactivation of fixed outdoor space heating appliances, clause J5.9(c).
To prescribe those Deemed-to-Satisfy Provisions and referenced documents that need to be complied with in addition to the modelling requirements of JV1, JV2 and JV3.
This clause lists requirements from the Deemed-to-Satisfy Provisions and referenced documents which must be complied with in addition to the necessary modelling. This is to overcome limitations in the modelling process by ensuring buildings designed under JV1, JV2 and JV3 cover the same range of energy efficiency attributes as the Deemed-to-Satisfy Provisions. For example, the standard of installing insulation is covered in subclause 2(a) of Specification JVa because it is not specifically addressed through modelling alone.
Where not included in the building energy simulation to satisfy JV1(a), compliance must be achieved with—
for a tenant supplementary heating and cooling system, J5.7; and
for heating, cooling and ventilation equipment not covered by the NABERS Energy for Offices base building rating, Part J5; and
for artificial lighting not covered by the NABERS Energy for Offices base building rating, Part J6.
To prescribe those Deemed-to-Satisfy Provisions that need to be complied with in addition to the modelling requirements of JV1.
Where not included in the building energy simulation to satisfy JV2(a), compliance must be achieved with—
for heating, cooling and ventilation equipment outside the scope of the Green Star model, Part J5; and
for artificial lighting outside the scope of the Green Star model, Part J6.
To prescribe those Deemed-to-Satisfy Provisions that need to be complied with in addition to the modelling requirements of JV2.