NCC 2019 Volume One Amendment 1
Search the National Construction Code editions
This Specification describes the requirements for mechanical smoke exhaust systems.
To state that Specification E2.2b outlines the requirements for mechanical smoke exhaust systems.
Specification E2.2b contains the requirements for mechanical smoke exhaust systems.
Smoke exhaust fans must have a sufficient capacity to contain the smoke layer—
within a smoke reservoir formed in accordance with Clause 4 and not less than 2 m above the highest floor level; and
above the top of any openings interconnecting different smoke reservoirs.
To specify the capacity and exhaust rates required of mechanical smoke exhaust systems.
Clause 2(a) defines the height to be maintained to the underside of the smoke layer. This height is used to determine the smoke exhaust capacity for various design fires under steady state conditions.
Clause 2(b) requires exhaust rates be determined using Figure 2 of Specification E2.2b. It specifies the exhaust rate required relative to the height to the underside of the smoke layer for various fire sizes.
The following needs to be known to use Figure 2 of Specification E2.2b:
The smoke exhaust rate in Figure 2 of Specification E2.2b is based on the rate at which air is drawn (i.e. “entrained”) into a plume of smoke which is generally symmetrical around a vertical axis where that plume is rising into the hot layer formed by the smoke reservoir.
The height to the underside of the smoke layer is measured from the highest floor level to the underside of the smoke reservoir. The smoke reservoir’s depth is determined by the depth of the smoke baffles/curtains required by Clause 4. See Figure Spec E2.2b.
Each smoke exhaust fan, complete with its drive, flexible connections, control gear and wiring must—
be constructed and installed so that it is capable of continuous operation (exhausting the required volumetric flow rate at the installed system resistance) at a temperature of 200° C for a period of not less than 1 hour; and
in a building not fitted with a sprinkler system, be capable of continuous operation at a temperature of 300° C for a period of not less than 30 minutes; and
be rated to handle the required volumetric flow rate at ambient temperature to be capable of exhausting cool smoke during the early stages of a fire and to allow routine testing; and
have any high temperature overload devices installed, automatically overridden during the smoke exhaust operation.
Classification |
Fire load (MW) for unsprinklered buildings |
Fire load (MW) for sprinklered buildings |
Class 2, 3 or 5 |
5 |
1.5 |
Class 6 |
10 |
5 |
Class 7 or 8 |
15 |
5 |
Class 9 — Generally |
5 |
1.5 |
Class 9b buildings covered by Part H1 (see Note), or exhibition halls. |
10 |
5 |
If the smoke reservoir above the stage is smoke separated from the audience area, the fire load specified applies to the stage area only and the fire load for the audience area is as per Class 9 generally.
To specify the operational requirements for smoke exhaust fans.
Clause 3 describes the operational requirements for smoke exhaust fans to ensure their design performance is maintained for an appropriate time, when operating in high temperature conditions. Fans must also be rated for ambient temperature operation to facilitate routine maintenance. These provisions also apply to dual purpose fans, that is those used for normal air-handling operations as well as for smoke exhaust.
A fire compartment must be divided at ceiling level into smoke reservoirs formed by smoke baffles/curtains of non-combustible and non-shatterable construction.
The horizontal area of a smoke reservoir must not exceed 2000 m2 and in enclosed walkways and malls of a Class 6 building must not exceed 60 m in length.
Smoke reservoirs must be of sufficient depth to contain the smoke layer and must not be less than 500 mm below an imperforate ceiling or roof.
Within a multi-storey fire compartment, a non-combustible bulkhead or smoke baffle/curtain must be provided around the underside of each opening into a building void to minimise the spread of smoke to other storeys.
The depth of the bulkhead or smoke baffle must be not less than the depth of the smoke reservoir provided under (c) plus an additional 400 mm.
To specify the requirements for smoke reservoirs, to enable the containment of smoke in the upper levels of compartments.
Clause 4(a) requires the division of fire compartments into smoke reservoirs.
Smoke reservoirs are necessary to contain the hot layer in the upper levels of compartments, thus preventing the lateral spread of smoke resulting in excessive cooling and downward mixing of the smoke with the relatively clear layer below which:
To maximise the effectiveness of smoke reservoirs, the horizontal area formed by a reservoir is limited by Clause 4(b) to 2 000 m2.
The maximum length of a smoke reservoir in a shopping mall is limited by Clause 4(b) to 60 metres, due to the distance people would be expected to travel below a smoke layer while evacuating to a safe place, having regard to the potential for smoke, from a fire in a mall or adjacent specialty shop, to flow into more than one reservoir.
Clause 4(c) specifies that the smoke reservoir must be of “sufficient” depth to contain the smoke layer.
Clause 4(d) deals with the location and depth of a bulkhead or smoke baffle/curtain. Any bulkhead and smoke baffle/curtain must be non-combustible. Clause 4(d) applies only to multi-storey fire compartments.
Smoke needs to be contained within the floor reservoir, and so the integrity of the containment must be maintained at the edges of voids in buildings, such as atriums, by the provision of non-combustible bulkheads or baffles.
Smoke exhaust fans and vents must be located—
such that each smoke reservoir is served by one or more fans with the maximum exhaust rate at any one point limited to avoid extracting air from below the smoke layer; and
to prevent the formation of stagnant regions resulting in excessive cooling and downward mixing of smoke; and
at natural collection points for the hot smoky gases within each smoke reservoir having due regard to the ceiling geometry and its effect on the migratory path of the smoke; and
away from the intersection of walkways or malls; and
to ensure that any voids containing escalators and/or stairs commonly used by the public are not used as a smoke exhaust path; and
to discharge directly to outdoor with a velocity of not less than 5 m/s, at a suitable point not less than 6 m from any air intake point or exit.
To make sure that exhaust fans and vents do not draw clean air up through the smoke layer.
For a given depth of smoke layer, there is a maximum rate at which smoke can be extracted from a single inlet before air is drawn from below the smoke layer. This is sometimes referred to as “plug-holing”.
Where the smoke layer is relatively shallow, more than one extraction point may be needed to minimise “plug-holing”. It may also be necessary to distribute the extraction points to prevent the formation of stagnant regions leading to excessive cooling and downward mixing of smoke with the relatively clear air below.
It is not suitable for a smoke exhaust fan and vent to discharge adjacent to an occupiable outdoor area.
Specific criteria are not given as the design is dependent on actual building layout.
Low level make-up air must be provided either automatically or via permanent ventilation openings to replace the air exhausted so as to minimise—
any disturbance of the smoke layer due to turbulence created by the incoming air; and
the risk of smoke migration to areas remote from the fire due to the effect of make-up air on the air balance of the total system.
The velocity of make-up air through doorways must not exceed 2.5 m/s.
Within a multi-storey fire compartment, make-up air must be provided across each vertical opening from a building void to the fire-affected storey at an average velocity of 1 m/s so as to minimise the spread of smoke from the fire-affected storey to other storeys.
To provide air to replace that being exhausted by the smoke exhaust system.
It is necessary to introduce “make-up air” to replace the air being exhausted by the smoke exhaust system, to:
Make-up air introduced below the smoke layer must be at relatively low velocities, to minimise any disturbance to the smoke layer. Make-up air introduced at higher velocities may cause:
Clause 6(c) deals with the provision of make-up air across any vertical opening from the building void to the fire-affected storey. This aims to minimise the risk of smoke spreading from the fire-affected storey to other storeys.
Specific criteria are not given in Clause 6 as the design is dependent on actual building layout.
Each smoke exhaust fan must be activated sequentially by smoke detectors complying with Specification E2.2a and arranged in zones to match the smoke reservoir served by the fan(s).
Subject to (c) and (d), an air handling system (other than individual room units less than 1000 L/s and miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system must be automatically shut down on the activation of the smoke exhaust system.
In a single storey fire compartment, air handling systems in all non fire-affected zones may operate on 100% outdoor air to provide make-up air to the fire-affected zone.
Within a multi-storey fire compartment, air handling systems in all non fire-affected zones and storeys must operate at 100% outdoor air to provide make-up air to the fire-affected storey via building voids connecting storeys.
Manual override control and indication together with operating instructions for use by emergency personnel must be provided adjacent to the fire indicator panel in accordance with the requirements of clauses 4.11 and 4.13 of AS 1668.1.
Manual control for the smoke exhaust system must also be provided at a location normally used by the stage manager in a theatre.
Power supply wiring to exhaust fans together with detection, control, and indication circuits (and where necessary to automatic make-up air supply arrangements) must comply with AS 1668.1.
To specify the control requirements for smoke exhaust systems and automatic make-up air arrangements.
To make sure that the smoke exhaust fan (or fans) operate in the designed manner, Clause 7(a) requires that the fans are activated sequentially by smoke detectors, and arranged in zones to match the smoke reservoir served by the fan (or fans).
Clause 7(b) requires air handling systems (which generally supply air to upper storeys in high rise buildings) to shut down on the activation of the smoke exhaust system where the air handling system:
This requirement minimises any disturbance to the hot smoke layer and limits smoke being distributed to other non-fire-affected areas of the building by way of the system.
Clause 7(b) is subject to Clauses 7(c) and (d).
A number of additional concessions to Clause 7(b) are allowed, including:
To allow manual control of the smoke exhaust system by the fire brigade, Clause 7(e) requires an override control to be located adjacent to the fire indicator panel.
In a theatre, an additional manual control must be provided in accordance with Clause 7(f) to allow the stage manager to control the smoke exhaust system during a performance. This is considered necessary because of any special effects which may cause a false alarm.
To reduce the risk of the smoke exhaust system failing during a fire, Clause 7(g) requires the electric cabling to the system’s essential components to be protected from fire in accordance with AS 1668.1.
A smoke detection system must be installed in accordance with Specification E2.2a to activate the smoke exhaust system.
To clarify the location of the requirements for the installation of a smoke detection system.
The smoke detection requirements for smoke exhaust systems are addressed in Clause 5 of Specification E2.2b. Such smoke detection systems designed to operate smoke-and-heat vents must also activate an occupant warning system.