Substitute application of Performance Requirement FP2.2 as follows:
FP2.2 only applies to—
Performance RequirementsFP2.1 to FP2.6 are satisfied by complying with F2.1 to F2.9 and Vic F2.101.
User Group | Closet Pans | Urinals | Washbasins | |||
---|---|---|---|---|---|---|
Design Occupancy |
Number |
Design Occupancy |
Number |
Design Occupancy |
Number | |
Class 9b — early childhood centre | ||||||
Children | 1 — 30 | 2 | 1 — 30 | 2 | ||
> 30 | Add 1 per 15 | > 30 | Add 1 per 15 |
Note to Vic Table F2.3: Facilities for use by children must be—
In an early childhood centre, other than a restricted children’s service, closet pans situated in a group for use by children must be separated from one another by means of a partition, which, except for the doorway, is opaque for a height of not less than 900 mm but not more than 1200 mm above the floor.
If an assembly building, place of public entertainment (as defined in the Building Act 1993) or an open spectator stand accommodates more than 5000 spectators at an arena, sportsground, showground, racecourse, cricket ground, football ground, coursing ground, motor racing arena, or the like, a suitable room or rooms must be provided in accordance with Table F2.101 for use by para-medical attendants for first aid purposes.
Spectator capacity |
Number of first aid rooms |
5001–10 000 spectators |
1 first aid room |
10 001–15 000 spectators |
2 first aid rooms |
15 001–30 000 spectators |
3 first aid rooms |
each extra 15 000 spectators or part thereof |
1 first aid room |
Conditions: First aid rooms required by (a) must—
be distributed as uniformly as possible throughout the assembly building or open spectator stand; and
be convenient to a public road; and
be readily accessible from within and outside the arena or ground; and
have a floor area of not less than 24 m2; and
be provided with a suitable wash basin or sink.
A habitable room or space must have sufficient size to enable the room or space to fulfil its intended use.
Compliance with FP3.1 is verified in relation to the height of a habitable room or space where the height of a habitable room or space provides an appropriate activity support level that does not unduly interfere with its intended function.
Performance RequirementVic FP3.1 is satisfied by complying with F3.1 and Vic F3.101 to Vic F3.103.
A children’s room in a children’s service must have a floor area allowing a clear space of at least 3.25 m2 for each child using that room.
When calculating the clear space required by (a) any passageway or thoroughfare less than 3 metres wide, kitchen, toilet or shower area, storage area (including cupboards), areas through which doors may swing, cot rooms (including areas where fixed cots will be used or stored) or any other ancillary area must not be included.
A habitable room in a Class 3 building (other than a residential aged care building)—
must have a floor area of at least 7.5 m2; or
may have a floor area less than 7.5 m2 provided the room has light and ventilation not less than that required for a room having a floor area of 7.5 m2.
In a residential aged care building—
each bedroom must have a floor area of not less than 12 m2 per occupant; and
all other common habitable rooms (other than kitchens) must have a floor area of not less than 7.5 m2 with—
in a Class 3 hostel or supported residential services building or Class 9c building an aggregate floor area of not less than 3.5 m2 per occupant; or
in a Class 9a nursing home an aggregate floor area of not less than 2.5 m2 per occupant.
Class 9b buildings — to all general purpose classrooms in primary or secondary schools and all playrooms or the like for the use of children in an early childhood centre other than a restricted children’s service.
In a Class 2, 3 or 9 building or Class 4 part of a building a required window that faces a boundary of an adjoining allotment or a wall of the same building or another building on the allotment must not be less than a horizontal distance from that boundary or wall that is the greater of—
generally — 1 m; and
in a patient care area or other room used for sleeping purposes in a Class 9a or Class 9c building — 3 m; and
50% of the square root of the exterior height of the wall in which the window is located, measured in metres from its sill.
(deleted).
In a Class 9b early childhood centre, other than a d, the sills of 50% of windows in children's rooms must be located not more than 500 mm above the floor level.