Filter
10.8
Part 10.8 Condensation managementPart 10.8 Condensation management
10.8.1
External wall construction
2019: 3.8.7.2
10.8.1
External wall construction
2019: 3.8.7.2
- comply with AS 4200.1; and
- be installed in accordance with AS 4200.2; and
- be located on the exterior side of the primary insulation layer of wall assemblies that form the external envelope of a building.
- in climate zones 4 and 5, 0.143 µg/N.s; and
- in climate zones 6, 7 and 8, 1.14 µg/N.s.
Explanatory information
10.8.1(2) requires some wall materials on the external side of the primary insulation layer to have a minimum level of vapour permeance. Vapour permeance is measured in µg/N.s (micrograms per newton-second).
Class 3 and Class 4 vapour control membranes (as defined by clause 5.3.4 of AS 4200.1) meet the vapour permeance requirements of 10.8.1(2)(a), while Class 4 vapour control membranes meet the vapour permeance requirements of 10.8.1(2)(b).
Open-cell insulation, such as mineral wool or fibreglass, typically has a high vapour permeance, while closed-cell insulation such as polystyrene typically has a low vapour permeance. Many foil-faced insulation products have a low vapour permeance.
10.8.2
Exhaust systems
2019: 3.8.7.3
10.8.2
Exhaust systems
2019: 3.8.7.3
- 25 L/s for a bathroom or sanitary compartment; and
- 40 L/s for a kitchen or laundry.
- be interlocked with the room’s light switch; and
- include a run-on timer so that the exhaust system continues to operate for 10 minutes after the light switch is turned off.
- via openings to an adjacent room with a free area of 14,000 mm2; or
- in accordance with AS 1668.2.
Explanatory information
A range hood installed in a kitchen must comply with 10.8.2(2).
10.8.2(3) requires venting clothes dryers to be provided with exhaust ducting directly from the clothes dryer to outdoor air. This requirement only applies to venting clothes dryers and not other types of clothes dryers, such as condensing clothes dryers.
10.8.2(5) and 10.8.2(6) requires some rooms that have exhaust systems and are not naturally ventilated (e.g. rooms without openable windows) to be provided with make-up air. The make-up air openings required by 10.8.2(5)(a) are based on the minimum flow rates of 10.8.2(1). An opening with a free area of 14,000 mm2 can by achieved by a 20 mm undercut to a 700 mm wide door. If the exhaust flowrates exceed the minimum flowrates of 10.8.2(1), additional make-up air openings may be required for the correct operation of the exhaust system.
10.8.3
Ventilation of roof spaces
2019: 3.8.7.4
10.8.3
Ventilation of roof spaces
2019: 3.8.7.4
- is located—
- immediately above the primary insulation layer; or
- immediately above sarking with a vapour permeance of not less than 1.14 μg/N.s, which is immediately above the primary insulation layer; or
- immediately above ceiling insulation that meets the requirements of 13.2.3(3) and 13.2.3(4); and
- has a height of not less than 20 mm; and
- is either—
- ventilated to outdoor air through evenly distributed openings in accordance with Table 10.8.3; or
- located immediately underneath the roof tiles of an unsarked tiled roof.
- concrete roof; or
- roof that is made of structural insulated panels; or
- roof that is subject to Bushfire Attack Level FZ requirements in accordance with AS 3959.
Roof pitch | Ventilation openings |
---|---|
< 10° | 25,000 mm2/m provided at each of two opposing ends |
≥ 10° and < 15° | 25,000 mm2/m provided at the eaves and 5,000 mm2/m at high level |
≥ 15° and < 75° | 7,000 mm2/m provided at the eaves and 5,000 mm2/m at high level, plus an additional 18,000 mm2/m at the eaves if the roof has a cathedral ceiling |
Table Notes
- Ventilation openings are specified as a minimum free open area per metre length of the longest horizontal dimension of the roof.
- For the purposes of this Table, high level openings are openings provided at the ridge or not more than 900 mm below the ridge or highest point of the roof space, measured vertically.
Explanatory information
Explanatory Figure 10.8.3 is an example of a roof space with low level ventilation.