Filter
9.2
Part 9.2 Fire separation of external wallsPart 9.2 Fire separation of external walls
9.2.1
External walls of Class 1 buildings
2019: 3.7.2.2
9.2.1
External walls of Class 1 buildings
2019: 3.7.2.2
An external wall of a Class 1 building, and any openings in that wall, must comply with 9.2.3 if the wall is less than—
- 900 mm from an allotment boundary other than the boundary adjoining a road alignment or other public space; or
- 1.8 m from another building on the same allotment other than an appurtenant Class 10 building associated with the Class 1 building or a detached part of the same Class 1 building; or
- 3 m from a brush fence.
External walls of Class 1 buildings
An external wall of a Class 1 building, and any openings in that wall, must comply with 9.2.3 if the wall is less than—
- 900 mm from an allotment boundary other than the boundary adjoining a road alignment or other public space; or
- 1.8 m from another building on the same allotment other than a Class 10 building associated with the Class 1 building or a detached part of the same Class 1 building.
9.2.2
Measurement of distances
2019: 3.7.2.3
9.2.2
Measurement of distances
2019: 3.7.2.3
SA 9.2.2 Measurement of distances2019: 3.7.2.3
9.2.3
Construction of external walls
2019: 3.7.2.4
9.2.3
Construction of external walls
2019: 3.7.2.4
- commence at the footings or ground slab, except where the external wall commences above a separating wall complying with 9.3.1 (see Figure 9.2.2e); and
- extend to—
- the underside of a non-combustible roof covering, except that a wall may terminate not more than 200 mm from the underside of a non-combustible roof covering, where the area between the external wall and underside of the roof covering is sealed with a non-combustible fascia, gutter or flashing; or
- the underside of a non-combustible eaves lining (See Figures 9.2.3a and b); and
- be constructed in accordance with (2).
- have an FRL of not less than 60/60/60 when tested from the outside; or
- be of masonry-veneer construction in which the external masonry veneer is not less than 90 mm thick; or
- be of masonry construction not less than 90 mm thick.
- non-openable fire windows or other construction with an FRL of not less than –/60/–; or
- self-closing solid core doors not less than 35 mm thick.
- in a bathroom, laundry or toilet, the opening has an area of not more than 1.2 m2; or
- in a room other than one referred to in (a), the opening has an area of not more than 0.54 m2 and—
- the window is steel-framed, there are no opening sashes and it is glazed in wired glass; or
- the opening is enclosed with translucent hollow glass blocks.
Explanatory information
- A Performance Solution must be used where an external wall required to be fire-resisting does not commence in accordance with 9.2.3(1)(a).
- The intent of the typical construction details shown in Figures 9.2.3a and b are to ensure that combustible materials (external or internal) are not directly exposed to fire at the junction of the wall and non-combustible roof, eaves lining, guttering and the like. Other forms of construction may also be acceptable provided that they achieve this intent.
- See Figure 9.2.2a and clause 10.7.3 for internal separating wall construction under one common roof.
9.2.4
Class 10a buildings
2019: 3.7.2.5
9.2.4
Class 10a buildings
2019: 3.7.2.5
- 9.2.5 where a Class 10a building is located between or adjacent to a Class 1 building and a boundary alignment that is not a boundary with a road alignment or other public space; or
- 9.2.6 where a Class 10a building is located between or adjacent to a Class 1 building it is associated with and another building on the same allotment; or
- 9.2.7 where two or more Class 10a buildings on the same allotment are located between and are associated with different Class 1 buildings.
SA 9.2.4 Class 10a buildings2019: 3.7.2.5
SA 9.2.4 Class 10a buildings2019: 3.7.2.5
Explanatory information
9.2.4(1)(a) ensures that when a Class 10 building is located between an allotment boundary and a Class 1 building or another building on the same allotment, either directly or indirectly, that the Class 1 building be protected by a wall with an FRL.
The intention is to prevent the spread of fire from an allotment boundary (fire source feature) to a Class 1 building via a Class 10a building. Where a Class 10a building is not sited directly and wholly between the allotment boundary and the Class 1 building (see 9.2.5), the potential of fire spreading from the allotment boundary to the Class 1 still exists. Therefore, fire separation would be required.
9.2.4 does not apply to a boundary that adjoins a road or public space such as parklands, lakes, rivers and the like where the construction of buildings is unlikely.
9.2.5
Protection of Class 1 buildings — Class 10a between Class 1 and the allotment boundary
2019: Figure 3.7.2.4
9.2.5
Protection of Class 1 buildings — Class 10a between Class 1 and the allotment boundary
2019: Figure 3.7.2.4
The following methods are acceptable for the protection of a Class 1 building where a Class 10a building is located between or adjacent to a Class 1 building and a boundary alignment that is not a boundary with a road alignment or other public space:
- The Class 10a building is not less than 900 mm from the allotment boundary, other than the boundary adjoining a road alignment or other public space, as shown in Figure 9.2.5a.
- An external wall of the Class 10a building which is less than 900 mm from an allotment boundary, other than the boundary adjoining a road alignment or other public space, complies with 9.2.3 as shown in Figure 9.2.5b.
- An external wall of the Class 10a building, which is less than 900 mm from the Class 1 building, complies with 9.2.3 as shown in Figure 9.2.5c.
- The Class 1 building is not less than 900 mm from the Class 10a building, as shown in Figure 9.2.5d.
- An external wall of the Class 1 building, which is less than 900 mm from the Class 10a building, complies with 9.2.3, as shown in Figure 9.2.5e.
- An external wall of the Class 10a building which is less than 900 mm from an allotment boundary other than the boundary adjoining a road alignment or other public space, complies with 9.2.3, as shown in Figure 9.2.5f.
- An external wall of the Class 10a building, which is less than 900 mm from the external wall of the Class 1 building, complies with 9.2.3, as shown in Figure 9.2.5g.
- An external wall of the Class 1 building, which is less than 900 mm from a Class 10a building that is situated less than 900 mm from an allotment boundary, complies with 9.2.3, as shown in Figure 9.2.5h.
- The external wall of the Class 1 and Class 10a building which are less than 900 mm from an allotment boundary, other than the boundary adjoining a road alignment or other public space, complies with 9.2.3 as shown in Figure 9.2.5i.
9.2.6
Protection of Class 1 buildings—Class 10a between Class 1 and other buildings on allotment
2019: Figure 3.7.2.5
9.2.6
Protection of Class 1 buildings—Class 10a between Class 1 and other buildings on allotment
2019: Figure 3.7.2.5
The following methods are acceptable for the protection of a Class 1 building where a Class 10a building is located between or adjacent to a Class 1 building it is associated with and another building on the same allotment:
- The Class 10a building is not less than 1.8 m from the other building, as shown in Figure 9.2.6a.
- An external wall of the Class 10a building, which is less than 1.8 m from the other building, complies with 9.2.3, as shown in Figure 9.2.6b.
- An external wall of the Class 10a building, which is less than 1.8 m from the Class 1 building, complies with 9.2.3, as shown in Figure 9.2.6c.
- The Class 1 building is not less than 1.8 m from the Class 10a building, as shown in Figure 9.2.6d.
- An external wall of the Class 1 building, which is less than 1.8 m from the Class 10a building, complies with 9.2.3, as shown in Figure 9.2.6e.
- An external wall of the Class 10a building, which is less than 1.8 m from the external wall of the other building, complies with 9.2.3, as shown in Figure 9.2.6f.
- An external wall of the Class 10a building, which is less than 1.8 m from the external wall of the Class 1 building, complies with 9.2.3, as shown in Figure 9.2.6g.
- An external wall of the Class 1 and 10a building, which is less than 1.8 m from the external wall of the other building, complies with 9.2.3, as shown in Figure 9.2.6h.
9.2.7
Protection of Class 1 buildings—separation of Class 10a buildings on an allotment
2019: Figure 3.7.2.6
9.2.7
Protection of Class 1 buildings—separation of Class 10a buildings on an allotment
2019: Figure 3.7.2.6
The following methods are acceptable for the protection of a Class 1 building where two or more Class 10a buildings on the same allotment are located between and are associated with different Class 1 buildings:
- Each Class 10a building must be separated from each other by a distance of not less than 1.8 m, as shown in Figure 9.2.7a.
- Each Class 10a building must be separated from each other by external walls complying with 9.2.3, as shown in Figure 9.2.7b.
- Each Class 10a building must be separated from each Class 1 building by a distance of not less than 900 mm, as shown in Figure 9.2.7c.
- Each Class 10a building must be separated from each Class 1 building by external walls complying with 9.2.3, as shown in Figure 9.2.7d.
- Each Class 10a building must be separated by a wall complying with 9.3.1, as shown in Figure 9.2.7e.
- Each Class 10a building must be separated from each other by external walls complying with 9.2.3, as shown in Figure 9.2.7f.
- Each Class 10a building must be separated from each Class 1 building by external walls complying with 9.2.3, as shown in Figure 9.2.7g.
- Each Class 10a building must be separated by a wall complying with 9.3.1, as shown in Figure 9.2.7h.
9.2.8
Open carports
2019: 3.7.2.6
9.2.8
Open carports
2019: 3.7.2.6
A Class 10a carport is exempt from complying with 9.2.4(1) if—
- it has—
- two or more sides open and not less than one third of its perimeter open and, for the purpose of this clause, a side is considered to be open if the roof covering adjacent to that side is not less than 500 mm from another building or allotment boundary; or
- any part of the external wall of the Class 1 building located less than 2 m from the allotment boundary or less than 4 m from another Class 1 building on the same allotment is fire-resisting to the underside of a non-combustible roof covering or to the underside of a non-combustible ceiling lining (see SA Figure 9.2.8a, SA Figure 9.2.8b and SA Figure 9.2.8c); and
- it has polycarbonate or non-combustible roof covering and any ceiling lining and wall cladding, including gables, is also non-combustible (see Figure 9.2.8a); and
- it does not provide direct vertical support to any part of the Class 1 building; and
- in the case where it has a common roof structure with the Class 1 building and the carport or verandah does not have a ceiling (see Figure 9.2.8b), the opening between the top of the wall of the Class 1 building and the underside of the roof covering is infilled with—
- non-combustible material; or
- construction with non-combustible material on the carport or verandah side; and
- in the case where two carports or verandahs have a common roof structure with two different Class 1 buildings and the carports or verandahs have a ceiling, the roof space or ceiling space between the top of the ceiling and the underside of the roof covering is infilled as follows—
- vertically between the two Class 1 buildings and between the two appurtenant carports of verandahs in accordance with (d) (see SA Figure 9.2.8d); or
- vertically between the two Class 1 buildings and between the two appurtenant carports or verandahs in accordance with (d), except that the construction must be clad with non-combustible materials on both sides and must not be crossed by timber or other combustible building elements except for roof battens with dimensions of 75 × 50 mm or less, roof sarking-type material or a timber gutter board not less than 20 mm thick.
Open carports
A Class 10a carport is exempt from complying with 9.2.4(1) if—
- it has two or more sides open and not less than one third of its perimeter open; and
- for the purposes of (a), a side is considered to be open if the roof covering adjacent to that side is not less than 500 mm from another building or allotment boundary; and
- it has a polycarbonate or non-combustible roof covering; and
- any ceiling lining and wall cladding, including gables, is non-combustible (see Figure 9.2.8a); and
- it does not provide direct vertical support to any part of the Class 1 building; and
- in the case where it has a common roof structure with the Class 1 building and the carport does not have a ceiling (See Figure 9.2.8b), the opening between the top of the wall of the Class 1 building and the underside of the roof covering is infilled with—
- a non-combustible material; or
- construction clad with non-combustible material on the carport side.
Explanatory information
A side of a carport enclosed by a vehicle access door is not considered to be an open side.
9.2.9
Allowable encroachments
2019: 3.7.2.7
9.2.9
Allowable encroachments
2019: 3.7.2.7
- the external wall of the building and the allotment boundary other than a boundary adjoining a road or other public space; or
- the external walls of two buildings on the same allotment; or
- the external wall of the building and a brush fence.
- non-combustible fascias, gutters and downpipes; and
- light fittings, electricity or gas meters, aerials or antennas; and
- pergolas, sun blinds or water tanks; and
- unroofed terraces, landings, steps and ramps, not more than 1 m in height.
- combustible fascias, gutters and downpipes (see Figures 9.2.9a, 9.2.9b and 9.2.9c); and
- eaves with non-combustible roof cladding and non-combustible lining; and
- flues, chimneys, pipes, domestic fuel tanks, cooling or heating appliances or other services.
Allowable encroachments
- between the external wall of the building and the allotment boundary other than a boundary adjoining a road or other public space; or
- between the external walls of two buildings on the same allotment; or
- between the external wall of the building and the vertical projection of the external wall of another building on the same allotment; or
- that extends beyond the vertical projection of another building on the same allotment other than a building it is associated with.
- non-combustible fascias, gutters and downpipes; and
- light fittings, electricity or gas meters, aerials or antennas; and
- pergolas, sun blinds or water tanks (see Figure 9.2.9a); and
- unroofed terraces, landings, steps and ramps, not more than 1 m in height.
- combustible fascias, gutters and downpipes (see Figure 9.2.9a, Figure 9.2.9b and Figure 9.2.9c); and
- eaves with non-combustible roof cladding and non-combustible lining; and
- flues, chimneys, pipes, domestic fuel tanks, cooling or heating appliances or other services.
Explanatory information
A deck is not considered an unroofed terrace and is therefore not permitted as an allowable encroachment under 9.2.9 whether combustible or not.
The term ‘pergola’ is a reference to an unroofed structure.
Explanatory Figure 9.2.9 depicts encroachment of a building on the same allotment, but which is not associated with the building onto which it encroaches.
9.2.10
Roof lights
2019: 3.7.2.8
9.2.10
Roof lights
2019: 3.7.2.8
Combustible roof lights, skylights or the like installed in a roof or part of a roof required to have a non-combustible covering must—
- have an aggregate area not more than 20% of the roof or part of the roof; and
- be not less than—
- 900 mm from the allotment boundary other than the boundary adjoining a road alignment or other public space; and
- 1.8 m from any roof light or the like in another building on the allotment other than an associated building or a detached part of the same building (see Figure 9.2.10).