Filter
9.5
Part 9.5 Smoke alarms and evacuation lightingPart 9.5 Smoke alarms and evacuation lighting
9.5.1
Smoke alarm requirements
2019: 3.7.5.2
9.5.1
Smoke alarm requirements
2019: 3.7.5.2
- be located in—
- Class 1a buildings excluding any non-associated Class 10a private garages, subject to (2), in accordance with 9.5.2 and 9.5.4; and
- Class 1b buildings in accordance with 9.5.3 and 9.5.4; and
- comply with AS 3786, except that in a Class 10a private garage where the use of the area is likely to result in smoke alarms causing spurious signals, any other alarm deemed suitable in accordance with AS 1670.1 may be installed provided that smoke alarms complying AS 3786 are installed elsewhere in the Class 1 building; and
- be powered from the consumer mains source where a consumer mains source is supplied to the building; and
- be interconnected where there is more than one alarm.
- be installed in a Class 10a private garage that is located beneath a garage top dwelling and not associated with that dwelling; and
- be located on or near the ceiling; and
- comply with AS 1603.3; and
- be powered from the consumer mains source supplying the garage top dwelling where a consumer mains source is supplied to the building; and
- be interconnected to the garage top dwelling smoke alarms required by 9.5.2.
- a heat alarm is installed in the non-associated Class 10a private garage; and
- the heat alarm is interconnected to the garage top dwelling smoke alarms.
Explanatory information
A smoke alarm can give spurious alarms if the atmosphere contains particles which obscure vision, such as could occur in a Class 10a private garage part of a building. NSW 9.5.1(1)(b) therefore allows the use of a more suitable alarm, such as a heat alarm, in these locations.
NSW 9.5.1(1)(d) requires alarms to be interconnected where there is more than one alarm. This only applies within a single dwelling. Therefore alarms in a Class 1a dwelling need not be interconnected with alarms in another dwelling.
Where a Class 10a private garage is located beneath a garage top dwelling and is not associated with that dwelling, NSW 9.5.1(2)(a) requires a heat alarm to be provided in the non-associated Class 10a private garage. NSW 9.5.1(2)(b) to (e) contains requirements for installing heat alarms. NSW 9.5.1(3) contains requirements for the provision of durable notices.
Smoke and heat alarm requirements
Smoke alarms must—
- be located in—
- comply with AS 3786, except that in a Class 10a private garage where the use of the area is likely to result in smoke alarms causing spurious signals, any other alarm deemed suitable in accordance with AS 1670.1 may be installed provided that smoke alarms complying with AS 3786 are installed elsewhere in the Class 1 building; and
- be powered from the consumer mains source where a consumer mains source is supplied to the building; and
- be interconnected where there is more than one alarm.
Explanatory information
A smoke alarm can give spurious alarms if the atmosphere contains particles which obscure vision, such as could occur in a Class 10a private garage part of a building. 9.5.1(b) therefore allows the use of a more suitable alarm, such as a heat alarm, in these locations.
9.5.1(d) requires alarms to be interconnected where there is more than one alarm. This only applies within a single dwelling. Therefore, alarms in a Class 1a dwelling need not be interconnected with alarms in another dwelling or a private garage which does not belong to the Class 1a dwelling.
9.5.2
Location – Class 1a buildings
2019: 3.7.5.3
9.5.2
Location – Class 1a buildings
2019: 3.7.5.3
In a Class 1a building, smoke alarms must be located in—
- any storey containing bedrooms, every corridor or hallway associated with a bedroom, or if there is no corridor or hallway, in an area between the bedrooms and the remainder of the building; and
- each other storey not containing bedrooms.
Notes
Figure 9.5.2a and 9.5.2b illustrates requirements of this provision.
9.5.3
Location – Class 1b buildings
2019: 3.7.5.4
9.5.3
Location – Class 1b buildings
2019: 3.7.5.4
In a Class 1b building, smoke alarms must be located in—
- every bedroom; and
- every corridor or hallway associated with a bedroom, or if there is no corridor or hallway, in an area between the bedrooms and the remainder of the building; and
- each other storey.
Notes
Figure 9.5.3 illustrates requirements of this provision.
9.5.4
Installation of smoke alarms
2019: 3.7.5.5
9.5.4
Installation of smoke alarms
2019: 3.7.5.5
Smoke alarms required by 9.5.2 and 9.5.3 must be installed on or near the ceiling, in accordance with the following:
- Where a smoke alarm is located on the ceiling it must be—
- a minimum of 300 mm away from the corner junction of the wall and ceiling; and
- between 500 mm and 1500 mm away from the high point and apexes of the ceiling, if the room has a sloping ceiling.
- Where (a) is not possible, the smoke alarm may be installed on the wall, and located a minimum of 300 mm and a maximum of 500 mm off the ceiling at the junction with the wall.
Explanatory information
Smoke alarms need to be located on (or near) the ceiling for optimum detection of smoke in a fire situation with special care taken to avoid dead air spaces. A dead air space is an area in which trapped hot air will prevent smoke from reaching the alarm. This space generally occurs at the apex of cathedral ceilings, the corner junction of walls and ceilings and between exposed joists etc. (see Explanatory Figure 9.5.4).
Smoke alarms may be located on the wall in accordance with 9.5.4(b). Explanatory Figure 9.5.4 provides location criteria and the dimensional relationship to building elements and the associated dead air spaces.
9.5.5
Lighting to assist evacuation – Class 1b buildings
2019: 3.7.5.6
9.5.5
Lighting to assist evacuation – Class 1b buildings
2019: 3.7.5.6
In a Class 1b building, a system of lighting must be installed to assist evacuation of occupants in the event of a fire, and—
Explanatory information
The lighting required by 9.5.5 may consist of artificial lighting which may already be installed in a corridor, hallway or area, provided that the lighting is activated by the smoke alarm. However consideration should be given to ensure that the lighting is not controlled by a dimmer or timer controlled switch which may dim the level of light to an ineffective level, or switch the light off before occupants have time to evacuate.