Part 6.3 Structural steel membersPart 6.3 Structural steel members
6.3.1
Application
New for 2022
6.3.1
Application
New for 2022
6.3.2
Structural steel members
2019: 3.4.4.2
6.3.2
Structural steel members
2019: 3.4.4.2
- Bearers supporting a timber floor or non-loadbearing stud wall — in accordance with 6.3.3.
- Strutting beams supporting roof and ceiling loads — in accordance with 6.3.4.
- Lintels supporting roof, ceiling, frame and timber floor — in accordance with 6.3.5.
- Columns — in accordance with 6.3.6.
6.3.3
Bearers
New for 2022
6.3.3
Bearers
New for 2022
Structural steel bearers must comply with the following:
- Effective bearer spacing must be determined in accordance with—
- for single span joists — Table H1D6a and Figure H1D6d; and
- for continuous span joists — Table H1D6b and Figure H1D6e.
- Maximum acceptable bearer spans must be determined in accordance with—
- for single spans — Tables 6.3.3a and 6.3.3c; and
- for continuous spans — Tables 6.3.3b and 6.3.3d.
- All loads along the bearer must be evenly distributed.
- The difference in distance between supports for continuous span bearers must not be more than 10% of the span.
- Fixing of joists and columns to structural steel bearers must comply with 6.3.7.
- Bearers must be supported by structural steel columns that comply with 6.3.6 and are fixed in accordance with 6.3.7.
Steel section | Effective load width (m) | ||||
---|---|---|---|---|---|
1.8 | 2.4 | 3.0 | 3.6 | 4.2 | |
125 TFB | 4.2 | 4.0 | 3.9 | 3.8 | 3.6 |
180 UB 16.1 | 5.6 | 5.4 | 5.3 | 5.1 | 4.7 |
200 UB 18.2 | 6.4 | 6.2 | 6.0 | 5.8 | 5.4 |
250 UB 25.7 | 8.3 | 8.0 | 7.8 | 7.6 | 7.1 |
250 x 150 x 9 RHS | 9.3 | 9.0 | 8.8 | 8.6 | 8.4 |
250 x 150 x 5 RHS | 8.0 | 7.8 | 7.6 | 7.1 | 6.6 |
310 UB 32.0 | 10.0 | 9.7 | 9.4 | 9.2 | 8.6 |
125 x 75 x 2 RHS | 2.9 | 2.6 | 2.3 | 2.2 | 2.0 |
125 x 75 x 3 RHS | 3.5 | 3.3 | 3.2 | 2.9 | 2.7 |
150 x 50 x 2 RHS | 3.3 | 2.9 | 2.6 | 2.4 | 2.3 |
150 x 50 x 3 RHS | 3.7 | 3.6 | 3.4 | 3.1 | 2.9 |
100 TFB | 2.9 | 2,8 | 2.7 | 2.5 | 2.4 |
150 PFC | 5.2 | 5.0 | 4.9 | 4.7 | 4.6 |
180 PFC | 6.1 | 5.9 | 5.8 | 5.6 | 5.4 |
200 PFC | 6.8 | 6.6 | 6.4 | 6.2 | 5.9 |
250 PFC | 8.9 | 8.6 | 8.4 | 8.2 | 8.0 |
300 PFC | 10.4 | 10.1 | 9.8 | 9.5 | 9.3 |
Table Notes
- Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.
- Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.
- Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.
Steel section | Effective load width (m) | ||||
---|---|---|---|---|---|
1.8 | 2.4 | 3.0 | 3.6 | 4.2 | |
125 TFB | 5.2 | 4.6 | 4.2 | 3.9 | 3.6 |
180 UB 16.1 | 6.8 | 6.0 | 5.5 | 5.1 | 4.7 |
200 UB 18.2 | 7.7 | 6.9 | 6.2 | 5.8 | 5.4 |
250 UB 25.7 | 10.2 | 9.1 | 8.3 | 7.6 | 7.1 |
250 x 150 x 9 RHS | 12.4 | 11.5 | 10.5 | 9.8 | 9.1 |
250 x 150 x 5 RHS | 9.5 | 8.4 | 7.7 | 7.1 | 6.6 |
310 UB 32.0 | 12.3 | 11.0 | 10.0 | 9.2 | 8.6 |
125 x 75 x 2 RHS | 2.9 | 2.6 | 2.3 | 2.2 | 2.0 |
125 x 75 x 3 RHS | 4.0 | 3.5 | 3.2 | 2.9 | 2.7 |
150 x 50 x 2 RHS | 3.3 | 2.9 | 2.6 | 2.4 | 2.3 |
150 x 50 x 3 RHS | 4.2 | 3.7 | 3.4 | 3.1 | 2.9 |
100 TFB | 3.4 | 3.0 | 2.7 | 2.5 | 2.4 |
150 PFC | 6.5 | 5.8 | 5.3 | 4.9 | 4.6 |
180 PFC | 7.8 | 6.9 | 6.3 | 5.8 | 5.4 |
200 PFC | 8.5 | 7.6 | 6.9 | 6.4 | 5.9 |
250 PFC | 11.6 | 10.4 | 9.5 | 8.7 | 8.2 |
300 PFC | 13.4 | 12.0 | 10.9 | 10.1 | 9.4 |
Table Notes
- Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.
- Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.
- Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.
Steel section | Effective load width (m) | ||||
---|---|---|---|---|---|
1.8 | 2.4 | 3.0 | 3.6 | 4.2 | |
125 TFB | 3.9 | 3.7 | 3.5 | 3.4 | 3.3 |
180 UB 16.1 | 5.2 | 5.0 | 4.8 | 4.6 | 4.4 |
200 UB 18.2 | 5.9 | 5.6 | 5.4 | 5.2 | 5.0 |
250 UB 25.7 | 7.7 | 7.3 | 7.1 | 6.8 | 6.6 |
250 x 150 x 9 RHS | 8.7 | 8.3 | 8.0 | 7.7 | 7.5 |
250 x 150 x 5 RHS | 7.5 | 7.1 | 6.9 | 6.6 | 6.1 |
310 UB 32.0 | 9.3 | 8.9 | 8.5 | 8.2 | 8.0 |
125 x 75 x 2 RHS | 2.7 | 2.4 | 2.2 | 2.0 | 1.9 |
125 x 75 x 3 RHS | 3.2 | 3.0 | 2.9 | 2.7 | 2.5 |
150 x 50 x 2 RHS | 3.0 | 2.7 | 2.4 | 2.2 | 2.1 |
150 x 50 x 3 RHS | 3.4 | 3.3 | 3.1 | 2.9 | 2.7 |
100 TFB | 2.7 | 2.6 | 2.5 | 2.3 | 2.2 |
150 PFC | 4.8 | 4.6 | 4.4 | 4.2 | 4.1 |
180 PFC | 5.7 | 5.4 | 5.2 | 5.0 | 4.9 |
200 PFC | 6.3 | 6.0 | 5.8 | 5.6 | 5.4 |
250 PFC | 8.3 | 7.9 | 7.6 | 7.3 | 7.1 |
300 PFC | 9.7 | 9.2 | 8.9 | 8.6 | 8.3 |
Table Notes
- Load accounted for includes 0.98 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.
- Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.
- Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.
Steel section | Effective load width (m) | ||||
---|---|---|---|---|---|
1.8 | 2.4 | 3.0 | 3.6 | 4.2 | |
125 TFB | 4.8 | 4.3 | 3.9 | 3.6 | 3.3 |
180 UB 16.1 | 6.3 | 5.6 | 5.1 | 4.7 | 4.4 |
200 UB 18.2 | 7.2 | 6.4 | 5.8 | 5.3 | 5.0 |
250 UB 25.7 | 9.5 | 8.5 | 7.7 | 7.1 | 6.6 |
250 x 150 x 9 RHS | 11.6 | 10.8 | 9.8 | 9.1 | 8.5 |
250 x 150 x 5 RHS | 8.8 | 7.8 | 7.1 | 6.6 | 6.1 |
310 UB 32.0 | 11.5 | 10.2 | 9.3 | 8.5 | 8.0 |
125 x 75 x 2 RHS | 2.7 | 2.4 | 2.2 | 2.0 | 1.9 |
125 x 75 x 3 RHS | 3.7 | 3.3 | 3.0 | 2.7 | 2.5 |
150 x 50 x 2 RHS | 3.1 | 2.7 | 2.4 | 2.2 | 2.1 |
150 x 50 x 3 RHS | 3.9 | 3.4 | 3.1 | 2.9 | 2.7 |
100 TFB | 3.2 | 2.8 | 2.5 | 2.3 | 2.2 |
150 PFC | 6.1 | 5.4 | 4.9 | 4.5 | 4.2 |
180 PFC | 7.2 | 6.4 | 5.8 | 5.4 | 5.0 |
200 PFC | 8.0 | 7.1 | 6.4 | 5.9 | 5.5 |
250 PFC | 10.9 | 9.7 | 8.8 | 8.1 | 7.6 |
300 PFC | 12.5 | 11.2 | 10.1 | 9.4 | 8.7 |
Table Notes
- Load accounted for includes 0.98 kPa permanent floor, 0.92 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed.
- Load combinations included are 1.35G and 1.25G+1.5Q for ULS and G + 0.7Q for SLS with a maximum deflection of span/300.
- Bearers are assumed to have intermediate lateral restraints at joist locations and are considered fully laterally restrained.
6.3.4
Strutting beams
New for 2022
6.3.4
Strutting beams
New for 2022
Structural steel strutting beams must comply with the following:
- Acceptable strutting beam spacing must be determined in accordance with—
- for single span rafters — Table H1D6a and Figure H1D6a; and
- for continuous span rafters — Table H1D6b and Figure H1D6b.
- Maximum acceptable strutting beam spans must be determined in accordance with—
- Any point load applied must be located within the middle third of the strutting beam.
- Strutting beams must be tied down in accordance with H1D6(3) where supporting metal roofs.
- Fixing and any cutting of strutting beams must comply with 6.3.7.
- Strutting beams must be supported by structural steel columns that comply with 6.3.6 and be fixed in accordance with 6.3.7.
Section | Ceiling load width (m) | ||
---|---|---|---|
1.8 | 3.6 | 6.0 | |
125 TFB | 3.5 | 3.3 | 3.2 |
150 UB 14.0 | 3.6 | 3.4 | 3.3 |
200 UB 18.2 | 4.5 | 4.3 | 4.1 |
250 UB 31.4 | 6.8 | 6.5 | 6.2 |
310 UB 46.2 | 8.9 | 8.5 | 8.1 |
100 TFB | 2.0 | 2.0 | 1.9 |
150 PFC | 4.7 | 4.5 | 4.3 |
200 PFC | 5.5 | 5.3 | 5.0 |
250 PFC | 7.5 | 7.1 | 6.8 |
300 PFC | 7.8 | 7.5 | 7.1 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
Section | Ceiling load width (m) | ||
---|---|---|---|
1.8 | 3.6 | 6.0 | |
125 TFB | 2.6 | 2.6 | 2.5 |
150 UB 14.0 | 2.8 | 2.7 | 2.7 |
200 UB 18.2 | 3.6 | 3.5 | 3.4 |
250 UB 31.4 | 5.5 | 5.4 | 5.2 |
310 UB 46.2 | 7.3 | 7.1 | 6.9 |
100 TFB | 1.4 | 1.4 | 1.4 |
150 PFC | 3.7 | 3.6 | 3.5 |
200 PFC | 4.4 | 4.3 | 4.1 |
250 PFC | 6.0 | 5.8 | 5.7 |
300 PFC | 6.3 | 6.2 | 6.0 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
Section | Ceiling load width (m) | ||
---|---|---|---|
1.8 | 3.6 | 6.0 | |
125 TFB | 2.2 | 2.2 | 2.2 |
150 UB 14.0 | 2.4 | 2.3 | 2.3 |
200 UB 18.2 | 3.1 | 3.0 | 3.0 |
250 UB 31.4 | 4.8 | 4.7 | 4.6 |
310 UB 46.2 | 6.4 | 6.3 | 6.1 |
100 TFC | 1.1 | 1.1 | 1.1 |
150 PFC | 3.1 | 3.1 | 3.0 |
200 PFC | 3.7 | 3.7 | 3.6 |
250 PFC | 5.2 | 5.1 | 5.0 |
300 PFC | 5.5 | 5.4 | 5.3 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
Section | Ceiling load area (m2) | ||
---|---|---|---|
0 | 6 | 12 | |
125 TFB | 3.9 | 3.5 | 3.2 |
150 UB 14.0 | 4.0 | 3.7 | 3.4 |
200 UB 18.2 | 5.4 | 4.9 | 4.6 |
250 UB 31.4 | 8.9 | 8.2 | 7.7 |
310 UB 46.2 | 12.0 | 11.3 | 10.7 |
100 TFB | 2.0 | 1.8 | 1.6 |
150 PFC | 5.9 | 5.3 | 4.9 |
200 PFC | 7.1 | 6.5 | 6.0 |
250 PFC | 10.1 | 9.3 | 8.7 |
300 PFC | 10.5 | 9.8 | 9.2 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G and 1.25G + 1.5Q, 1.25G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G+WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.
Section | Ceiling load area (m2) | ||
---|---|---|---|
0 | 6 | 12 | |
125 TFB | 2.7 | 2.6 | 2.4 |
150 UB 14.0 | 2.9 | 2.8 | 2.6 |
200 UB 18.2 | 4.0 | 3.8 | 3.6 |
250 UB 31.4 | 6.8 | 6.5 | 6.2 |
310 UB 46.2 | 9.6 | 9.2 | 8.8 |
100 TFB | 1.4 | 1.3 | 1.2 |
150 PFC | 4.2 | 4.0 | 3.8 |
200 PFC | 5.2 | 4.9 | 4.7 |
250 PFC | 7.7 | 7.3 | 7.0 |
300 PFC | 8.2 | 7.8 | 7.5 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G and 1.25G + 1.5Q, 1.25G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G+WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.
Section | Ceiling load area (m2) | ||
---|---|---|---|
0 | 6 | 12 | |
125 TFB | 2.2 | 2.1 | 2.0 |
150 UB 14.0 | 2.4 | 2.3 | 2.2 |
200 UB 18.2 | 3.3 | 3.2 | 3.0 |
250 UB 31.4 | 5.7 | 5.5 | 5.3 |
310 UB 46.2 | 8.2 | 7.9 | 7.7 |
100 TFB | 1.1 | 1.0 | 1.0 |
150 PFC | 3.4 | 3.2 | 3.1 |
200 PFC | 4.2 | 4.1 | 3.9 |
250 PFC | 6.4 | 6.2 | 6.0 |
300 PFC | 6.9 | 6.6 | 6.4 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G and 1.25G + 1.5Q, 1.25G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G+WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.
Section | Ceiling load width (m) | ||
---|---|---|---|
1.8 | 3.6 | 6.0 | |
125 TFB | 2.7 | 2.6 | 2.6 |
150 UB 14.0 | 2.8 | 2.8 | 2.7 |
200 UB 18.2 | 3.6 | 3.5 | 3.4 |
250 UB 31.4 | 5.5 | 5.4 | 5.2 |
310 UB 46.2 | 7.2 | 7.1 | 6.9 |
100 TFB | 1.6 | 1.5 | 1.5 |
150 PFC | 3.7 | 3.7 | 3.6 |
200 PFC | 4.4 | 4.3 | 4.2 |
250 PFC | 6.0 | 5.8 | 5.7 |
300 PFC | 6.3 | 6.1 | 6.0 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.84 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
Section | Ceiling load width (m) | ||
---|---|---|---|
1.8 | 3.6 | 6.0 | |
125 TFB | 2.0 | 2.0 | 2.0 |
150 UB 14.0 | 2.2 | 2.1 | 2.1 |
200 UB 18.2 | 2.8 | 2.8 | 2.7 |
250 UB 31.4 | 4.4 | 4.3 | 4.3 |
310 UB 46.2 | 5.8 | 5.7 | 5.6 |
100 TFB | 1.1 | 1.1 | 1.1 |
150 PFC | 2.8 | 2.8 | 2.8 |
200 PFC | 3.4 | 3.3 | 3.3 |
250 PFC | 4.7 | 4.6 | 4.6 |
300 PFC | 5.0 | 4.9 | 4.8 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.84 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
Section | Ceiling load width (m) | ||
---|---|---|---|
1.8 | 3.6 | 6.0 | |
125 TFB | 1.7 | 1.7 | 1.7 |
150 UB 14.0 | 1.8 | 1.8 | 1.8 |
200 UB 18.2 | 2.4 | 2.4 | 2.4 |
250 UB 31.4 | 3.8 | 3.8 | 3.7 |
310 UB 46.2 | 5.0 | 5.0 | 4.9 |
100 TFB | 0.9 | 0.9 | 0.9 |
150 PFC | 2.4 | 2.4 | 2.3 |
200 PFC | 2.9 | 2.8 | 2.8 |
250 PFC | 4.0 | 4.0 | 3.9 |
300 PFC | 4.3 | 4.2 | 4.2 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.84 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
Section | Ceiling load area (m2) | ||
---|---|---|---|
0 | 6 | 12 | |
125 TFB | 3.4 | 3.1 | 2.9 |
150 UB 14.0 | 3.5 | 3.3 | 3.0 |
200 UB 18.2 | 4.7 | 4.4 | 4.1 |
250 UB 31.4 | 7.9 | 7.4 | 7.0 |
310 UB 46.2 | 10.9 | 10.4 | 9.9 |
100 TFB | 1.7 | 1.6 | 1.4 |
150 PFC | 5.1 | 4.6 | 3.6 |
200 PFC | 6.2 | 5.7 | 5.4 |
250 PFC | 9.0 | 8.4 | 8.0 |
300 PFC | 9.5 | 8.9 | 8.5 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.
Section | Ceiling load area (m2) | ||
---|---|---|---|
0 | 6 | 12 | |
125 TFB | 2.3 | 2.2 | 2.1 |
150 UB 14.0 | 2.5 | 2.4 | 2.3 |
200 UB 18.2 | 3.4 | 3.3 | 3.2 |
250 UB 31.4 | 5.9 | 5.7 | 5.5 |
310 UB 46.2 | 8.5 | 8.2 | 7.9 |
100 TFB | 1.2 | 1.1 | 1.0 |
150 PFC | 3.6 | 3.4 | 3.3 |
200 PFC | 4.4 | 4.2 | 4.1 |
250 PFC | 6.7 | 6.4 | 6.2 |
300 PFC | 7.2 | 6.9 | 6.7 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.
Section | Ceiling load area (m2) | ||
---|---|---|---|
0 | 6 | 12 | |
125 TFB | 1.8 | 1.8 | 1.7 |
150 UB 14.0 | 2.0 | 1.9 | 1.9 |
200 UB 18.2 | 2.8 | 2.7 | 2.7 |
250 UB 31.4 | 5.0 | 4.8 | 4.7 |
310 UB 46.2 | 7.1 | 7.0 | 6.8 |
100 TFB | 0.9 | 0.9 | 0.8 |
150 PFC | 2.8 | 2.7 | 2.7 |
200 PFC | 3.6 | 3.5 | 3.4 |
250 PFC | 5.5 | 5.4 | 5.2 |
300 PFC | 5.9 | 5.8 | 5.6 |
Table Notes
- Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.
6.3.5
Lintels
New for 2022
6.3.5
Lintels
New for 2022
Structural steel lintels must comply with the following:
- Spans for lintels supporting roofs, frames and timber floors must be determined in accordance with—
- for metal sheet roofs, Table 6.3.5a, 6.3.5b or 6.3.5c; and
- for tiled roofs, Table 6.3.5d, 6.3.5e or 6.3.5f.
- Effective load widths for structural steel lintels must be determined in accordance with Figure 6.3.5 (a) or (b).
- All loads along the structural steel lintel must be evenly distributed.
- The top flange of the structural steel lintel must be laterally restrained at the loading points.
- Fixing of structural steel lintels must comply with 6.3.7.
- Structural steel lintels used in masonry must also comply with H1D5.
- Lintel beams must be supported by structural steel columns that comply with 6.3.6.
Section | Floor load width (m) | ||
---|---|---|---|
0 | 1.8 | 3.6 | |
150 UB 14.0 | 4.4 | 3.0 | 2.5 |
200 UB 25.4 | 6.8 | 4.7 | 4.0 |
250 UB 31.4 | 7.7 | 5.3 | 4.6 |
100 TFB | 2.8 | 1.8 | 1.5 |
150 PFC | 5.7 | 3.8 | 3.2 |
200 PFC | 6.5 | 4.3 | 3.7 |
250 PFC | 8.4 | 5.7 | 4.9 |
75 x 75 x 5 EA | 2.0 | 1.0 | – |
90 x 90 x 6 EA | 3.0 | 1.5 | 1.0 |
100 x 100 x 6 EA | 3.0 | 1.8 | 1.0 |
125 x 75 x 6 UA | 3.0 | 1.8 | 1.3 |
150 x 100 x 10 UA | 4.0 | 3.0 | 2.5 |
Table Notes
- Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G and 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A floor load of “0” must be used for lintels not supporting floor loads.
Section | Floor load width (m) | ||
---|---|---|---|
0 | 1.8 | 3.6 | |
150 UB 14.0 | 3.1 | 2.7 | 2.4 |
200 UB 25.4 | 4.9 | 4.3 | 3.8 |
250 UB 31.4 | 5.6 | 4.9 | 4.3 |
100 TFB | 1.9 | 1.7 | 1.5 |
150 PFC | 4.0 | 3.4 | 3.0 |
200 PFC | 4.5 | 3.9 | 3.4 |
250 PFC | 6.0 | 5.2 | 4.6 |
75 x 75 x 5 EA | 1.0 | – | – |
90 x 90 x 6 EA | 1.8 | 1.3 | – |
100 x 100 x 6 EA | 1.8 | 1.3 | – |
125 x 75 x 6 UA | 1.8 | 1.3 | 1.0 |
150 x 100 x 10 UA | 3.0 | 2.5 | 2.0 |
Table Notes
- Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G and 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A floor load of “0” must be used for lintels not supporting floor loads.
Section | Floor load width (m) | ||
---|---|---|---|
0 | 1.8 | 3.6 | |
150 UB 14.0 | 2.6 | 2.4 | 2.2 |
200 UB 25.4 | 4.1 | 3.8 | 3.6 |
250 UB 31.4 | 4.7 | 4.4 | 4.1 |
100 TFB | 1.6 | 1.5 | 1.4 |
150 PFC | 3.3 | 3.0 | 2.8 |
200 PFC | 3.8 | 3.5 | 3.3 |
250 PFC | 5.1 | 4.6 | 4.3 |
75 x 75 x 5 EA | – | – | – |
90 x 90 x 6 EA | 1.0 | – | – |
100 x 100 x 6 EA | 1.0 | – | – |
125 x 75 x 6 UA | 1.3 | 1.0 | 1.0 |
150 x 100 x 10 UA | 2.5 | 2.0 | 2.0 |
Table Notes
- Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G and 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A floor load of “0” must be used for lintels not supporting floor loads.
Section | Floor load width (m) | ||
---|---|---|---|
0 | 1.8 | 3.6 | |
150 UB 14.0 | 4.0 | 2.8 | 2.3 |
200 UB 25.4 | 6.2 | 4.4 | 3.7 |
250 UB 31.4 | 7.1 | 5.0 | 4.3 |
100 TFB | 2.5 | 1.7 | 1.4 |
150 PFC | 5.2 | 3.5 | 2.9 |
200 PFC | 5.9 | 4.0 | 3.4 |
250 PFC | 7.7 | 5.4 | 4.5 |
75 x 75 x 5 EA | 2.0 | – | – |
90 x 90 x 6 EA | 2.5 | 1.3 | – |
100 x 100 x 6 EA | 3.0 | 1.3 | – |
125 x 75 x 6 UA | 2.5 | 1.5 | 1.0 |
150 x 100 x 10 UA | 4.0 | 2.5 | 2.0 |
Table Notes
- Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS G + 0.7Q, G + WS.
- 0.9G + WSS for SLS with a maximum deflection of span/300.
- Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A floor load of “0” must be used for lintels not supporting floor loads.
Section | Floor load width (m) | ||
---|---|---|---|
0 | 1.8 | 3.6 | |
150 UB 14.0 | 2.8 | 2.5 | 2.2 |
200 UB 25.4 | 4.4 | 3.9 | 3.5 |
250 UB 31.4 | 5.1 | 4.5 | 4.0 |
100 TFB | 1.7 | 1.5 | 1.3 |
150 PFC | 3.6 | 3.1 | 2.7 |
200 PFC | 4.1 | 3.6 | 3.1 |
250 PFC | 5.4 | 4.7 | 4.2 |
75 x 75 x 5 EA | – | – | – |
90 x 90 x 6 EA | 1.3 | 1.0 | – |
100 x 100 x 6 EA | 1.5 | 1.0 | – |
125 x 75 x 6 UA | 1.5 | 1.0 | – |
150 x 100 x 10 UA | 2.5 | 2.0 | 1.8 |
Table Notes
- Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A floor load of “0” must be used for lintels not supporting floor loads.
Section | Floor load width (m) | ||
---|---|---|---|
0 | 1.8 | 3.6 | |
150 UB 14.0 | 2.4 | 2.2 | 2.0 |
200 UB 25.4 | 3.8 | 3.4 | 3.2 |
250 UB 31.4 | 4.3 | 4.0 | 3.7 |
100 TFB | 1.5 | 1.3 | 1.2 |
150 PFC | 3.0 | 2.7 | 2.5 |
200 PFC | 3.4 | 3.1 | 2.9 |
250 PFC | 4.6 | 4.2 | 3.9 |
75 x 75 x 5 EA | – | – | – |
90 x 90 x 6 EA | – | – | – |
100 x 100 x 6 EA | – | – | – |
125 x 75 x 6 UA | 1.0 | – | – |
150 x 100 x 10 UA | 2.0 | 1.8 | 1.5 |
Table Notes
- Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.
- Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS G + 0.7Q, G + WS.
- 0.9G + WS for SLS with a maximum deflection of span/300.
- Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.
- A floor load of “0” must be used for lintels not supporting floor loads.
6.3.6
Columns
2019: 3.4.4.3
6.3.6
Columns
2019: 3.4.4.3
Structural steel columns must comply with the following:
- Columns must support the maximum area provided for in—
- Tables 6.3.6a, 6.3.6b and 6.3.6c for columns supporting tiled floor and tiled roof load; and
- Tables 6.3.6d, 6.3.6e and 6.3.6f for columns supporting timber floor and metal roof load.
- The floor area to be supported is to be determined in accordance with Table 6.3.6g and Figure 6.3.6a.
- The flooring system supported by structural steel columns must be fully braced to the footing level either by—
- subject to (d), adequately fixing the full height of the column to bracing walls of similar height in the two orthogonal directions of the building; or
- a bracing system designed in accordance with AS 1684.2, AS 1684.3, AS/NZS 4600, NASH standard or AS 3700 as appropriate to the materials being used.
- For the purposes of (c)(i), the bracing walls must be capable of resisting racking forces in each direction not less than a proportion of the building’s racking force equal to the proportion of floor area that the column is supporting compared to the total floor area of the building.
- Acceptable load eccentricity must not exceed 50% of the cross-sectional width plus 100 mm (see Figure 6.3.6b).
- Have a minimum nominal yield strength of 250 MPa.
Column section | Effective height (mm) | Floor load area (m2) | ||
---|---|---|---|---|
4 | 10 | 16 | ||
CHS 250 | 2400 | 60.3 x 4.5 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS |
CHS 250 | 2700 | 60.3 x 4.5 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS |
CHS 250 | 3000 | 60.3 x 4.5 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS |
CHS 250 | 3300 | 60.3 x 5.4 CHS | 88.9 x 5 CHS | 114.3 x 5.4 CHS |
CHS 250 | 3600 | 60.3 x 5.4 CHS | 88.9 x 5 CHS | 114.3 x 5.4 CHS |
CHS 350 | 2400 | 60.3 x 2.9 CHS | 88.9 x 3.2 CHS | 114.3 x 3.2 CHS |
CHS 350 | 2700 | 60.3 x 2.9 CHS | 88.9 x 3.2 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3000 | 60.3 x 2.9 CHS | 88.9 x 3.2 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3300 | 76.1 x 2.3 CHS | 88.9 x 3.2 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3600 | 76.1 x 2.3 CHS | 101.6 x 2.6 CHS | 114.3 x 3.2 CHS |
SHS 350 | 2400 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 350 | 2700 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3000 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3300 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3600 | 65 x 65 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 450 | 2400 | 50 x 50 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 2700 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3000 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3300 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3600 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
Table Notes
- Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor.
- Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
- Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
- A maximum load eccentricity of 100 mm has been accounted for in the columns.
- A roof load area of “0” must be used for columns not supporting roof loads.
- The length of wall load allowed for is equal to the square root of the floor area.
Column section | Effective height (mm) | Floor load area (m2) | ||
---|---|---|---|---|
4 | 10 | 16 | ||
CHS 250 | 2400 | 76.1 x 4.5 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
CHS 250 | 2700 | 76.1 x 4.5 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
CHS 250 | 3000 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 139.7 x 5 CHS |
CHS 250 | 3300 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 139.7 x 5 CHS |
CHS 250 | 3600 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 139.7 x 5 CHS |
CHS 350 | 2400 | 76.1 x 3.2 CHS | 101.6 x 3.2 CHS | 139.7 x 3 CHS |
CHS 350 | 2700 | 76.1 x 3.2 CHS | 101.6 x 3.2 CHS | 139.7 x 3 CHS |
CHS 350 | 3000 | 76.1 x 3.2 CHS | 114.3 x 3.2 CHS | 139.7 x 3 CHS |
CHS 350 | 3300 | 88.9 x 2.6 CHS | 114.3 x 3.2 CHS | 139.7 x 3 CHS |
CHS 350 | 3600 | 88.9 x 2.6 CHS | 114.3 x 3.2 CHS | 139.7 x 3 CHS |
SHS 350 | 2400 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 350 | 2700 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3000 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3300 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3600 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 450 | 2400 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 2700 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3000 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 450 | 3300 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 450 | 3600 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
Table Notes
- Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
- Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
- Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
- A maximum load eccentricity of 100 mm has been accounted for in the columns.
- A roof load area of “0” must be used for columns not supporting roof loads.
- The length of wall load allowed for is equal to the square root of the floor area.
Column section | Effective height (mm) | Floor load area (m2) | ||
---|---|---|---|---|
4 | 10 | 16 | ||
CHS 250 | 2400 | 88.9 x 5 CHS | 114.3 x 5.4 CHS | 139.7 x 5 CHS |
CHS 250 | 2700 | 88.9 x 5 CHS | 114.3 x 5.4 CHS | 139.7 x 5 CHS |
CHS 250 | 3000 | 88.9 x 5 CHS | 114.3 x 5.4 CHS | 139.7 x 5 CHS |
CHS 250 | 3300 | 88.9 x 5.9 CHS | 114.3 x 5.4 CHS | 139.7 x 5 CHS |
CHS 250 | 3600 | 88.9 x 5.9 CHS | 114.3 x 5.4 CHS | 139.7 x 5 CHS |
CHS 350 | 2400 | 101.6 x 2.6 CHS | 114.3 x 3.6 CHS | 139.7 x 3.5 CHS |
CHS 350 | 2700 | 101.6 x 2.6 CHS | 114.3 x 3.6 CHS | 139.7 x 3.5 CHS |
CHS 350 | 3000 | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS | 139.7 x 3.5 CHS |
CHS 350 | 3300 | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS | 139.7 x 3.5 CHS |
CHS 350 | 3600 | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS | 139.7 x 3.5 CHS |
SHS 350 | 2400 | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS | 100 x 100 x 4 SHS |
SHS 350 | 2700 | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3000 | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS | 100 x 100 x 5 SHS |
SHS 350 | 3300 | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS | 100 x 100 x 5 SHS |
SHS 350 | 3600 | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS | 100 x 100 x 5 SHS |
SHS 450 | 2400 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 450 | 2700 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 450 | 3000 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 450 | 3300 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 450 | 3600 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
Table Notes
- Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
- Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
- Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
- A maximum load eccentricity of 100 mm has been accounted for in the columns.
- A roof load area of “0” must be used for columns not supporting roof loads.
- The length of wall load allowed for is equal to the square root of the floor area.
Column section | Effective height (mm) | Floor load area (m2) | ||
---|---|---|---|---|
4 | 10 | 16 | ||
CHS 250 | 2400 | 60.3 x 3.6 CHS | 76.1 x 5.9 CHS | 101.6 x 5 CHS |
CHS 250 | 2700 | 60.3 x 3.6 CHS | 76.1 x 5.9 CHS | 101.6 x 5 CHS |
CHS 250 | 3000 | 60.3 x 4.5 CHS | 76.1 x 5.9 CHS | 101.6 x 5 CHS |
CHS 250 | 3300 | 60.3 x 4.5 CHS | 76.1 x 5.9 CHS | 101.6 x 5 CHS |
CHS 250 | 3600 | 60.3 x 4.5 CHS | 88.9 x 5 CHS | 101.6 x 5 CHS |
CHS 350 | 2400 | 60.3 x 2.3 CHS | 88.9 x 2.6 CHS | 101.6 x 3.2 CHS |
CHS 350 | 2700 | 60.3 x 2.9 CHS | 88.9 x 2.6 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3000 | 60.3 x 2.9 CHS | 88.9 x 3.2 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3300 | 60.3 x 2.9 CHS | 88.9 x 3.2 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3600 | 60.3 x 2.9 CHS | 88.9 x 3.2 CHS | 114.3 x 3.2 CHS |
SHS 350 | 2400 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 350 | 2700 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 350 | 3000 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 350 | 3300 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 350 | 3600 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 2400 | 50 x 50 x 2 SHS | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS |
SHS 450 | 2700 | 50 x 50 x 2 SHS | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS |
SHS 450 | 3000 | 50 x 50 x 2 SHS | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS |
SHS 450 | 3300 | 50 x 50 x 2.5 SHS | 89 x 89 x 3.5 SHS | 89 x 89 x 3.5 SHS |
SHS 450 | 3600 | 50 x 50 x 2.5 SHS | 89 x 89 x 3.5 SHS | 89 x 89 x 3.5 SHS |
Table Notes
- Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
- Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
- Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
- A maximum load eccentricity of 100 mm has been accounted for in the columns.
- A roof load area of “0” must be used for columns not supporting roof loads.
- The length of wall load allowed for is equal to the square root of the floor area.
Column section | Effective height (mm) | Floor load area (m2) | ||
---|---|---|---|---|
4 | 10 | 16 | ||
CHS 250 | 2400 | 60.3 x 5.4 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS |
CHS 250 | 2700 | 76.1 x 3.6 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS |
CHS 250 | 3000 | 76.1 x 3.6 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS |
CHS 250 | 3300 | 76.1 x 3.6 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS |
CHS 250 | 3600 | 76.1 x 4.5 CHS | 88.9 x 5.9 CHS | 114.3 x 5.4 CHS |
CHS 350 | 2400 | 76.1 x 2.3 CHS | 88.9 x 3.2 CHS | 114.3 x 3.2 CHS |
CHS 350 | 2700 | 76.1 x 2.3 CHS | 101.6 x 2.6 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3000 | 76.1 x 3.2 CHS | 101.6 x 2.6 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3300 | 76.1 x 3.2 CHS | 101.6 x 3.2 CHS | 114.3 x 3.2 CHS |
CHS 350 | 3600 | 76.1 x 3.2 CHS | 101.6 x 3.2 CHS | 114.3 x 3.2 CHS |
SHS 350 | 2400 | 65 x 65 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 350 | 2700 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3000 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3300 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3600 | 75 x 75 x 2.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 450 | 2400 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 2700 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3000 | 65 x 65 x 2 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3300 | 65 x 65 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3600 | 65 x 65 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
Table Notes
- Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
- Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
- Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
- A maximum load eccentricity of 100 mm has been accounted for in the columns.
- A roof load area of “0” must be used for columns not supporting roof loads.
- The length of wall load allowed for is equal to the square root of the floor area.
Column section | Effective height (mm) | Floor load area (m2) | ||
---|---|---|---|---|
4 | 10 | 16 | ||
CHS 250 | 2400 | 76.1 x 4.5 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
CHS 250 | 2700 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
CHS 250 | 3000 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
CHS 250 | 3300 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
CHS 250 | 3600 | 76.1 x 5.9 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS |
CHS 350 | 2400 | 76.1 x 3.2 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
CHS 350 | 2700 | 76.1 x 3.2 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
CHS 350 | 3000 | 88.9 x 2.6 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
CHS 350 | 3300 | 88.9 x 2.6 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
CHS 350 | 3600 | 88.9 x 2.6 CHS | 101.6 x 3.2 CHS | 114.3 x 3.6 CHS |
SHS 350 | 2400 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 350 | 2700 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3000 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3300 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 350 | 3600 | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS | 100 x 100 x 4 SHS |
SHS 450 | 2400 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 2700 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3000 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3300 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
SHS 450 | 3600 | 75 x 75 x 2.5 SHS | 89 x 89 x 3.5 SHS | 100 x 100 x 3 SHS |
Table Notes
- Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
- Load combinations included are 1.35G and 1.2G + 1.5Q for ULS.
- Columns are assumed to be simply-supported at both ends with an effective length factor of 1.
- A maximum load eccentricity of 100 mm has been accounted for in the columns.
- A roof load area of “0” must be used for columns not supporting roof loads.
- The length of wall load allowed for is equal to the square root of the floor area.
Column descriptor (as shown in Figure 6.3.6a) | Total area supported |
---|---|
C1 | 0.4L1 x 0.4LA |
C2 | 0.7(L1 + L2) x 0.4LA |
C3 | 0.4L1 x 0.7(LA + LB) |
C4 | 0.7(L1 + L2) x 0.7(LA + LB) |
C5 | 0.4L1 + 0.4LC |
C6 | 0.7(L1 + L2) x 0.4LC |
Table Notes
The total area supported equations marginally overestimate the total area to account for a difference between L1 and L2 by up to 30%.
Explanatory information: Cantilever columns
A cantilever column is not assisted by any lateral bracing element such as a column bracing set, timber or masonry wall.
Explanatory information: Calculating column size
The following is an example of the steps required to calculate a suitable column to support typical floor loads in a residential building. It is proposed the column will—
- have an actual height of 1800 mm; and
- support a timber floor only; and
- be square in section; and
- be cast in to the footings; and
- be fully braced by column bracing sets.
Step 1 – Determining effective column height
The column height (H) is determined by multiplying the actual height by the relevant height factor (F1) in Tables 6.3.6d, 6.3.6e or 6.3.6f. In this case, the relevant value for F1 is 1.00 as the column is cast in to the footing and is fully braced.
Therefore:
- H = actual height x F1
- H = 1800 mm x F1
- H = 1800 mm (1.8 m)
Step 2 – Determine floor area to be supported
The column position selected is C4 as shown in Figure 6.3.6a and the dimensions of L1 and L2 are 2700 mm (2.7 m), LA is 1900 mm (1.9 m) and LB is 2100 mm (2.1 m).
The area supported by the column is determined by the formulae set out in Table 6.3.6g.
Therefore:
- Total area supported (A) is 0.625(L1 + L2) x 0.625(LA + LB)
- A = 0.625(2.7 m + 2.7 m) x 0.625 x (1.9 m + 2.1 m)
- A = (0.625 x 5.4 m) x (0.625 x 4.0 m)
- A = 3.38 m x 2.5 m
- A = 8.5 m2
Step 3 – Select column size from Tables 6.3.6d, 6.3.6e or 6.3.6f
The column with an effective height of 1800 mm supporting a floor area of 8.5 m2 is selected from the 10 m2 column in Table 6.3.6d (“0” roof load area) giving a SHS 350 75 x 75 x 3 size.
It should be noted there is a choice of CHS 250 88.9 x 4 or CHS 350 101.6 x 2.6 should a different section be desired.
6.3.7
Fixings and bearing for structural steel members
New for 2022
6.3.7
Fixings and bearing for structural steel members
New for 2022
- For single spans, the bearing distance must be not less than the width of the member.
- For continuous spans, internal bearing must be not less than two times the width of the member.
- be supported and fixed in accordance with Figure 6.3.7b; and
- where ends are cut to suit roof pitch, be cut in accordance with Figure 6.3.7c.
Explanatory information
The ends of bearers and lintels must be sufficiently supported to ensure structural loads are transferred to the footing system. The amount of horizontal bearing (measured in millimetres) required on the vertical supports will depend on the type of span of the bearer or lintel. For single spans, the amount of horizontal bearing is to be equal to or greater than the width of the bearer or lintel. For continuous spans it is to be twice the width of the bearer or lintel.
For bearing distance, see 6.3.7(4)(a) and (b).
Explanatory Figure 6.3.7 depicts an example of a 200 PFC bearer or lintel supporting floor or roof loads over a single span.
6.3.8
Penetrations through structural steel members
New for 2022
6.3.8
Penetrations through structural steel members
New for 2022
Penetrations through structural steel members must be within the allowable zones in Figure 6.3.8.
Explanatory information
Cutting and penetrations in structural steel should be avoided where possible. Figure 6.3.8 provides permissible zones for penetrations through structural steel. However, it is recommended that a suitable qualified professional be consulted where penetrations or cuts are required to be made on site.
6.3.9
Corrosion protection
2019: 3.4.4.4
6.3.9
Corrosion protection
2019: 3.4.4.4
Structural steel members that are not built in to a masonry wall must—
- be protected against corrosion in accordance with Tables 6.3.9a, 6.3.9b and 6.3.9c; and
- where a paint finish is applied to the surface, be free from rust; and
- where zinc coatings are applied to the surface, be provided with a barrier coat to prevent domestic enamels from peeling; and
- when cut or welded on-site, have those areas and any other areas of damage to protective coatings comply with (a).
Environment | Location | Minimum protective coating | ||
---|---|---|---|---|
Option 1 (hot dip galvanising) | Option 2 (duplex system). See Table 6.3.9c | Option 3 (paint). See Table 6.3.9b | ||
Low (mild steel corrosion rate 1.3 to 25 μm/year | Typically remote inland areas or more than 1 km from sheltered bays | HDG75 | – | ACL2, ACC2, IZS1, PUR2A |
Medium (mild steel corrosion rate 25 to 50 μm/year) | Typically more than 1 km from breaking surf or aggressive industrial areas or more than 50 m from sheltered bays | HDG225 | – | ACL3, ACC4, ACC5, IZS1, PUR3, PUR4 |
High (mild steel corrosion rate 50 to 80 μm/year) | Typically more than 200 m from breaking surf or aggressive industrial areas or within 50 m from sheltered bays | HDG450 | HDG150 (5 years) 4D (10-15 years) or HDG300 (10 years) 2D (5-10 years) | ACC6, IZS3, PUR5 |
Very High (mild steel corrosion rate 80 to 200 μm/year) | Typically extends from 100 m inland from breaking surf to 200 m inland from breaking surf, or within 200 m of aggressive industrial areas and within 100 m of breaking surf. | HDG900 | HDG300 (5 years) 5D (10-15 years) or HDG600 (10 years) 4D (5-10 years) | ACC6 (C5-M only), PUR5 |
Table Notes
Hot dip galvanising and duplex systems must be in accordance with AS 2312.2. Paint systems must be in accordance with AS 2312.1.
AS 2312.1 system | Surface preparation | 1st coat | 2nd coat | 3rd coat | Total DFT | |||
---|---|---|---|---|---|---|---|---|
Type of paint | DFT | Type of paint | DFT | Type of paint | DFT | |||
ACC2 | Sa 2.5 | Epoxy primer | 75 | Acrylic (2 pack) | 50 | – | – | 125 |
ACC4 | Sa 2.5 | Epoxy primer | 75 | High build epoxy | 125 | Acrylic (2 pack) | 50 | 250 |
ACC5 | Sa 2.5 | Zinc rich primer | 75 | High build epoxy | 125 | Acrylic (2 pack) | 50 | 250 |
ACC6 | Sa 2.5 | Zinc rich primer | 75 | High build epoxy | 200 | Acrylic (2 pack) | 50 | 325 |
ACL2 | Sa 2.5 | Zinc rich primer | 75 | Acrylic latex | 40 | Acrylic latex | 40 | 155 |
ACL3 | Sa 2.5 | Zinc rich primer | 75 | High build epoxy | 125 | Acrylic latex | 40 | 240 |
IZS1 | Sa 2.5 | Inorganic zinc silicate | 75 | – | – | – | – | 75 |
IZS3 | Sa 2.5 | Inorganic zinc silicate | 125 | – | – | – | – | 125 |
PUR2A | Sa 2.5 | Zinc rich primer | 75 | High build polyurethane | 75 | – | – | 150 |
PUR3 | Sa 2.5 | Epoxy primer | 75 | High build epoxy | 125 | Polyurethane gloss | 50 | 250 |
PUR4 | Sa 2.5 | Zinc rich primer | 75 | High build epoxy | 125 | Polyurethane gloss | 50 | 250 |
PUR5 | Sa 2.5 | Zinc rich primer | 75 | High build epoxy | 200 | Polyurethane gloss | 50 | 325 |
Table Notes
DFT refers to dry film thickness, measured in μm.
AS 2312.2 duplex system | Surface preparation | 1st coat | 2nd coat | 3rd coat | Total DFT | |||
---|---|---|---|---|---|---|---|---|
Type of paint | DFT | Type of paint | DFT | Type of paint | DFT | |||
2D | Degrease, wash and dry, sweep blast clean | Epoxy primer (2 pack) inhibitive | 75 | Polyurethane or acrylic gloss (2 pack) | 100 | – | – | 175 |
4D | Degrease, wash and dry, sweep blast clean | High-build epoxy (2 pack) | 250 | Polyurethane or acrylic gloss (2 pack) | 100 | – | – | 350 |
5D | Degrease, wash and dry, sweep blast clean | Epoxy primer (2 pack) inhibitive | 75 | High-build epoxy (2 pack) | 225 | Polyurethane or acrylic gloss (2 pack) | 100 | 400 |
Table Notes
DFT refers to dry film thickness, measured in μm.
Notes
Clause 3.4.4.4 and Table 3.4.4.7 from NCC Volume Two 2019 (Amendment 1) may be used in place of 6.3.9 and Tables 6.3.9a, 6.3.9b and 6.3.9c until 1 May 2024.