NCC 2019 Volume Two Amendment 1
Search the National Construction Code editions
The provisions of 3.12.1.1 to 3.12.1.5 apply to—
a Class 1 building; and
a Class 10a building with a conditioned space.
The provisions of 3.12.1.6 apply to a Class 1 building with an attached Class 10a building.
Where required, insulation must comply with AS/NZS 4859.1 and be installed so that it—
abuts or overlaps adjoining insulation other than at supporting members such as columns, studs, noggings, joists, furring channels and the like where the insulation must butt against the member; and
forms a continuous barrier with ceilings, walls, bulkheads, floors or the like that inherently contribute to the thermal barrier; and
does not affect the safe or effective operation of a domestic service or fitting.
Care should be taken when installing insulation to ensure that it does not interfere with the safety or performance of domestic services and fittings such as heating flues, recessed light fittings, light transformers, gas appliances and general plumbing and electrical components. This includes providing appropriate clearance as detailed in relevant legislation and referenced standards such as for electrical, gas and fuel oil installations.
Where required, reflective insulation must be installed with—
the necessary airspace, to achieve the required R-Value between a reflective side of the reflective insulation and a building lining or cladding; and
Airspace adjoining reflective insulation
For reflective insulation and the adjoining airspace to achieve its tested R-Value, the airspace needs to be a certain width. This width varies depending on the particular type of reflective insulation and the R-Value to be achieved.
the reflective insulation closely fitted against any penetration, door or window opening; and
the reflective insulation adequately supported by framing members; and
each adjoining sheet of roll membrane being—
overlapped greater than or equal to 150 mm; or
taped together.
Adjoining sheets of roll membrane
Where reflective insulation also acts as a vapour barrier or sarking, both the minimum overlap and taping may be necessary.
Where required, bulk insulation must be installed so that—
it maintains its position and thickness, other than where it crosses roof battens, water pipes, electrical cabling or the like; and
Compression of bulk insulation
The R-Value of bulk insulation is reduced if it is compressed. The allocated space for bulk insulation must therefore allow the insulation to be installed so that it maintains its correct thickness when using the product’s stated R-Value, otherwise the R-Value needs to be reduced to account for any compression. This is particularly relevant to wall and cathedral ceiling framing whose members can only accommodate a limited thickness of insulation. In some instances, larger framing members or thinner insulation material, such as polystyrene boards, may be necessary to ensure that the insulation achieves its required R-Value.
in a ceiling, where there is no bulk insulation or reflective insulation in the external wall beneath,it overlaps the external wall by greater than or equal to 50 mm.
Subject to (b) and (e), a roof must—
achieve the Total R-Value specified in Tables 3.12.1.1a to 3.12.1.1g as appropriate, for the direction of heat flow; and
where a pitched roof has a flat ceiling, have greater than or equal to 50% of the added insulation laid on the ceiling.
In climate zones 1, 2, 3, 4 and 5 the Total R-Value specified in Tables 3.12.1.1a to 3.12.1.1g as appropriate, is reduced by 0.5 where—
the required insulation is laid on the ceiling; and
the roof space is ventilated by—
gable vents, ridge vents, eave vents, roof vents or the like that—
are evenly distributed to allow an unobstructed flow of air; and
are located to ensure, where practicable, there are no dead airspaces; and
have an aggregate fixed open area of greater than or equal to 1% of the ceiling area; or
having—
not less than 2 wind-driven roof ventilators having an aggregate opening area of greater than or equal to 0.14 m2; and
gable vents, ridge vents, eave vents, roof vents or the like that have an aggregate fixed open area of greater than or equal to 0.2% of the ceiling area.
Direction of heat flow | Upper surface solar absorptance value | Minimum Total R-Value |
---|---|---|
Down | ≤ 0.4 | 3.1 |
Down | > 0.4 but ≤ 0.6 | 4.1 |
Down | > 0.6 | 5.1 |
Direction of heat flow | Upper surface solar absorptance value | Minimum Total R-Value |
---|---|---|
Down | ≤ 0.4 | 4.1 |
Down | > 0.4 but ≤ 0.6 | 4.6 |
Down | > 0.6 | 5.1 |
Note to Table 3.12.1.1b: Altitude means the height above the Australian Height Datum at the location where the building is to be constructed.
Direction of heat flow | Upper surface solar absorptance value | Minimum Total R-Value |
---|---|---|
Down and Up | ≤ 0.4 | 4.1 |
Down and Up | > 0.4 but ≤ 0.6 | 4.6 |
Down and Up | > 0.6 | 5.1 |
Note to Table 3.12.1.1c: Altitude means the height above the Australian Height Datum at the location where the building is to be constructed.
Direction of heat flow | Upper surface solar absorptance value | Minimum Total R-Value |
---|---|---|
Down and Up | ≤ 0.4 | 4.1 |
Down and Up | > 0.4 but ≤ 0.6 | 4.6 |
Down and Up | > 0.6 | 5.1 |
Direction of heat flow | Upper surface solar absorptance value | Minimum Total R-Value |
---|---|---|
Up | ≤ 0.4 | 4.1 |
Up | > 0.4 but ≤ 0.6 | 4.6 |
Up | > 0.6 | 5.1 |
Direction of heat flow | Upper surface solar absorptance value | Minimum Total R-Value |
---|---|---|
Up | ≤ 0.4 | 4.6 |
Up | > 0.4 but ≤ 0.6 | 5.1 |
Up | > 0.6 | 5.1 |
Direction of heat flow | Upper surface solar absorptance value | Minimum Total R-Value |
---|---|---|
Up | ≤ 0.4 | 6.3 |
Up | > 0.4 but ≤ 0.6 | 6.3 |
Up | > 0.6 | 6.3 |
Colour | Value |
---|---|
Slate (dark grey) | 0.90 |
Red, green | 0.75 |
Yellow, buff | 0.60 |
Zinc aluminium — dull | 0.55 |
Galvanised steel — dull | 0.55 |
Light grey | 0.45 |
Off white | 0.35 |
Light cream | 0.30 |
A roof that—
is required to achieve a minimum Total R-Value; and
has metal sheet roofing directly fixed to metal purlins, metal rafters or metal battens; and
does not have a ceiling lining or has a ceiling lining fixed directly to those metal purlins, metal rafters or metal battens (see Figure 3.12.1.1(b)),
must have a thermal break, consisting of a material with an R-Value of greater than or equal to 0.2, installed between the metal sheet roofing and its supporting metal purlins, metal rafters, or metal battens.
A roof, or roof and associated ceiling,is deemed to have the Total R-Value in Figure 3.12.1.1.
Unventilated with a downwards direction of heat flow — Total R-Value of 0.48
Unventilated with an upwards direction of heat flow — Total R-Value of
0.36
Unventilated with a downwards direction of heat flow — Total R-Value of 0.44
Unventilated with an upwards direction of heat flow — Total R-Value of 0.38
Ventilated with a downwards direction of heat flow — Total R-Value of 0.74
Ventilated with an upwards direction of heat flow — Total R-Value of 0.23
Unventilated with a downwards direction of heat flow — Total R-Value of 0.56
Unventilated with an upwards direction of heat flow — Total R-Value of 0.41
Ventilated with a downwards direction of heat flow — Total R-Value of 0.72
Ventilated with an upwards direction of heat flow — Total R-Value of 0.21
Unventilated with a downwards direction of heat flow — Total R-Value of 0.54
Unventilated with an upwards direction of heat flow — Total R-Value of 0.39
Notes to Figure 3.12.1.1:
Figure 3.12.1.1
provides examples of various roof and ceiling construction. The R-Value of the
required
insulation is calculated by subtracting the inherent Total R-Value
of the roof and ceiling construction from the Total R-Value
in Tables 3.12.1.1a to 3.12.1.1g.
The inherent Total
R-Value of the typical roof and ceiling has been determined
by adding together the R-Values of the out door air film, roof
cladding, roof airspace, ceiling sheet lining and internal film.
Irrespective of the framing material used, the minimum added R-Value specified in Figures 3.12.1.1 and 3.12.1.3 and Table 3.12.1.4 is deemed to include the effect of thermal bridging created by framing members in situations other than described in explanatory note 4.
Because of the high thermal conductance of metal, a thermal break is to be provided where the ceiling lining of a house is fixed directly to the underside of the metal purlins or metal battens of a metal deck roof or where there is no ceiling lining. The purpose of the thermal break is to ensure that the thermal performance of this form of roof construction is comparable to that of a similar roof with timber purlins or timber battens.
A thermal break may be provided by materials such as timber, expanded polystyrene strips, plywood or compressed bulk insulation. The material used as a thermal break must separate the metal purlins or metal battens from the metal deck roofing and achieve the specified R-Value. Reflective insulation alone is not suitable for use as a thermal break because it requires an adjoining airspace to achieve the specified R-Value (see explanatory note 6).
For the purposes of 3.12.1.2(c),expanded
polystyrene strips of not less than 12 mm thickness,compressed bulk insulation, and timber of not
less than 20 mm thickness are considered to achieve an R-Value of not
less than 0.2.
The thermal performance of the roof may vary depending on the position of the insulation, the climatic conditions, the design of the house and the way in which it is operated. For example, insulation installed under the roof, rather than on the ceiling, of a conditioned house with a large roof space is less effective because of the additional volume of roof airspace that would need to be heated or cooled. Conversely, for an unconditioned house, the use of reflective insulation is more effective when placed directly under the roof.
There are a number of different insulation products that may be used to achieve the minimum added R-Value. However, care should be taken to ensure that the choice made is appropriate for the construction and climatic conditions as the location and relationship between options in Figures 3.12.1.1 and 3.12.1.3 and Table 3.12.1.4 may not be suitable in all circumstances for both practical and technical reasons. For instance, in some climate zones, insulation should be installed with due consideration of condensation and associated interaction with adjoining building materials. As an example, reflective insulation or sarking installed on the cold side of the building envelope should be vapour permeable. Note that Part 3.8.7 contains specific provisions for condensation.
Reflective insulation is considered to provide the following additional R-Values when used in conjunction with the Total R-Value of a pitched roof and flat ceiling construction described in Figure 3.12.1.1. To achieve these values, the reflective insulation must be laid directly under the roof cladding and have a minimum airspace of 15 mm between a reflective side of the reflective insulation and the adjoining lining or roof cladding (see 3.12.1.1(b)).
The actual R-Value added by reflective insulation and its adjoining airspace should be determined for each product in accordance with relevant standards, taking into consideration factors such as the number of adjacent airspaces, dimensions of the adjacent airspace, whether the space is ventilated and the presence of an anti-glare coating. When reflective insulation has an anti-glare coating on one side, the emittance value of that side will be greater than the value of the uncoated side.
Also, where another emittance value for reflective insulation is used (other than the value used in the table below), care should be taken to ensure that the number of airspaces allowed for is consistent with the form of construction and whether the airspace is reflective, partially reflective or non-reflective. Where bulk insulation fill is the airspace, the Total R-Value should be reduced to take account of the loss of airspace.
Emittance of added reflective insulation | Direction of heat flow Note 1 | R-Value added—unventilated roof space | R-Value added—ventilated roof space |
---|---|---|---|
0.2 outer / 0.05 inner | Down | 1.12 | 1.21 |
0.2 outer / 0.05 inner | Up | 0.75 | 0.59 |
0.9 outer / 0.05 inner | Down | 0.92 | 1.01 |
0.9 outer / 0.05 inner | Up | 0.55 | 0.40 |
R-Value added by reflective insulation—Flat skillion or pitched roof (≤10°) with horizontal
ceiling
Emittance of added reflective insulation | Direction of heat flow Note 1 | R-Value added |
---|---|---|
0.2 outer / 0.05 inner | Down | 1.28 |
0.2 outer / 0.05 inner | Up | 0.68 |
0.9 outer / 0.05 inner | Down | 1.06 |
0.9 outer / 0.05 inner | Up | 0.49 |
Emittance of added reflective insulation | Direction of heat flow Note 1 | R-Value added — pitch ≥ 15° to ≤ 25° | R-Value added — pitch > 25° to ≤ 35° | R-Value added — pitch > 35° to ≤ 45° |
---|---|---|---|---|
0.2 outer / 0.05 inner | Down | 0.96 | 0.86 | 0.66 |
0.2 outer / 0.05 inner | Up | 0.72 | 0.74 | 0.77 |
0.9 outer / 0.05 inner | Down | 0.74 | 0.64 | 0.44 |
0.9 outer / 0.05 inner | Up | 0.51 | 0.52 | 0.53 |
Notes:
Where, for operational or safety reasons associated with exhaust fans, flues or recessed downlights, the area of required ceiling insulation is reduced, the loss of insulation must be compensated for by increasing the R-Value of insulation in the remainder of the ceiling in accordance with Table 3.12.1.1h.
Where the minimum R-Value of ceiling insulation required to satisfy 3.12.1.2(a) is not stated in Table 3.12.1.1h, interpolation may be used to determine the adjusted minimum R-Value.
Percentage of ceiling area uninsulated | Minimum R-Value of ceiling insulation required to satisfy 3.12.1.2(a) | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1.0 | 1.5 | 2.0 | 2.5 | 3.0 | 3.5 | 4.0 | 4.5 | 5.0 | 5.5 | 6.0 | |
Minimum R-Value of ceiling insulation required to satisfy 3.12.1.2(a) | |||||||||||
0.5% to less than 1.0% | 1.0 | 1.6 | 2.2 | 2.8 | 3.4 | 4.0 | 4.7 | 5.4 | 6.2 | 6.9 | X |
1.0% to less than 1.5% | 1.1 | 1.7 | 2.3 | 2.9 | 3.6 | 4.4 | 5.2 | 6.1 | 7.0 | X | X |
1.5% to less than 2.0% | 1.1 | 1.7 | 2.4 | 3.1 | 3.9 | 4.8 | 5.8 | 6.8 | X | X | X |
2.0% to less than 2.5% | 1.1 | 1.8 | 2.5 | 3.3 | 4.2 | 5.3 | 6.5 | X | X | X | X |
2.5% to less than 3.0% | 1.2 | 1.9 | 2.6 | 3.6 | 4.6 | 5.9 | X | X | X | X | X |
3.0% to less than 4.0% | 1.2 | 2.0 | 3.0 | 4.2 | 5.7 | X | X | X | X | X | X |
4.0% to less than 5.0% | 1.3 | 2.2 | 3.4 | 5.0 | X | X | X | X | X | X | X |
5.0% or more | X | X | X | X | X | X | X | X | X | X | X |
Notes to Table 3.12.1.1h:
Roof lights (including any associated shaft and diffuser) serving a habitable room or an interconnecting space such as a corridor, hallway, stairway or the like must—
if the roof lights are not required for compliance with Part 3.8.4 or —
comply with Table 3.12.1.2; and
have an aggregate area of not more than 3% of the total floor area of the storey served; or
if the roof lights are required for compliance with Part 3.8.4 or Part 3.8.5—
have an area not more than 150% of the minimum area required by Part 3.8.5; and
have transparent and translucent elements, including any imperforate ceiling diffuser with—
a Total System SHGC of not more than 0.29; and
a Total system U-Valueof not more than 2.9.
For the purposes of Table 3.12.1.2, the following applies:
The roof light shaft index is determined by measuring the distance from the centre of the shaft at the roof to the centre of the shaft at the ceiling level and dividing it by the average internal dimension of the shaft opening at the ceiling level (or the diameter for a circular shaft) in the same units of measurement.
The roof light area index is the total area of roof lights serving the room or space as a percentage of the floor area of the room or space.
The total area of roof lights is the combined area for all roof lights serving the room or space.
The area of a roof light is the area of the roof opening that allows light to enter the building.
The thermal performance of an imperforate ceiling diffuser may be included in the Total system U-Valueof the roof light.
The total area of roof lights serving the room or space as a percentage of the floor area of the room or space must not be more than 5% unless allowed by (a)(ii),
Roof light shaft index | Roof light area index ≤ 2% | Roof light area index > 2% to ≤ 3% | Roof light area index > 3% to ≤ 4% | Roof light area index > 4% to ≤ 5% |
---|---|---|---|---|
<0.5 |
Total System
SHGC ≤0.83 Total system U-Value ≤8.5 |
Total System
SHGC ≤0.57 Total system U-Value ≤5.7 |
Total System
SHGC ≤0.43 Total system U-Value ≤4.3 |
Total System
SHGC ≤0.34 Total system U-Value ≤3.4 |
≥0.5 to <1.0 |
Total System
SHGC ≤0.83 Total system U-Value ≤8.5 |
Total System
SHGC ≤0.72 Total system U-Value ≤5.7 |
Total System
SHGC ≤0.54 Total system U-Value ≤4.3 |
Total System
SHGC ≤0.43 Total system U-Value ≤3.4 |
≥1.0 to <2.5 |
Total System
SHGC ≤0.83 Total system U-Value ≤8.5 |
Total System
SHGC ≤0.83 Total system U-Value ≤5.7 |
Total System
SHGC ≤0.69 Total system U-Value ≤4.3 |
Total System
SHGC ≤0.55 Total system U-Value ≤3.4 |
≥2.5 |
Total System
SHGC ≤0.83 Total system U-Value ≤8.5 |
Total System
SHGC ≤0.83 Total system U-Value ≤5.7 |
Total System
SHGC ≤0.83 Total system U-Value ≤4.3 |
Total System
SHGC ≤0.83 Total system U-Value ≤3.4 |
Translucent or transparent element description | Domed panel | Flat, framed panel |
---|---|---|
Single layer clear |
Total System SHGC: 0.80 Total system U-Value: 8.4 |
Total System SHGC: 0.79 Total system U-Value: 8.0 |
Single tinted |
Total System SHGC: 0.66 Total system U-Value: 8.4 |
Total System SHGC: 0.63 Total system U-Value: 7.9 |
Single layer translucent (“opal”) |
Total System SHGC: 0.57 Total system U-Value: 8.4 |
Total System SHGC: 0.56 Total system U-Value: 7.9 |
Double layer clear |
Total System SHGC: 0.71 Total system U-Value: 5.4 |
Total System SHGC: 0.70 Total system U-Value: 4.9 |
Worst case whole roof light element performance values with an imperforate ceiling
diffuser
Translucent or transparent element description | Domed panel | Flat, framed panel |
---|---|---|
Single layer clear |
Total System SHGC: 0.72 Total system U-Value: 4.3 |
Total System SHGC: 0.71 Total system U-Value: 4.2 |
Single tinted |
Total System SHGC: 0.59 Total system U-Value: 4.3 |
Total System SHGC: 0.57 Total system U-Value: 4.2 |
Single layer translucent (“opal”) |
Total System SHGC: 0.51 Total system U-Value: 4.3 |
Total System SHGC: 0.50 Total system U-Value: 4.2 |
Double layer clear |
Total System SHGC: 0.64 Total system U-Value: 3.4 |
Total System SHGC: 0.63 Total system U-Value: 3.2 |
Each part of an external wall must satisfy the requirements of —
(b) for all walls; or
(c) for walls with a surface density greater than or equal to 220 kg/m2, except for—
opaque non-glazed openings such as doors (including garage doors), vents, penetrations, shutters and the like; and
Surface density is the mass of one vertical square metre of wall.
Each part of an external wall must—
in climate zones 1, 2, 3, 4 and 5—
achieve a minimum Total R-Value of 2.8; or
—
achieve a minimum Total R-Value of 2.4; and
shade the external wall of the storey with a verandah, balcony, eaves, carport or the like, which projects at a minimum angle of 15 degrees in accordance with Figure 3.12.1.2; or
in climate zones 6 and 7, achieve a minimum Total R-Value of 2.8; or
in climate zones 8, achieve a minimum Total R-Value of 3.8.
Each part of an external wall with a wall surface density of greater than or equal to 220 kg/m2 must—
in climate zones 1, 2 and 3—
for a storey, other than one with a storey above, shade the wall with a verandah, balcony, eaves, carport or the like that projects at a minimum angle of 15 degrees in accordance with Figure 3.12.1.2; and
incorporate insulation with an R-Value of greater than or equal to 0.5; and
on the lowest storey containing habitable rooms, have either—
a concrete slab-on-ground floor; or
masonry internal walls; or
in climate zone 5 (option a)—
for a storey, other than one with a storey above, shade the wall with a verandah, balcony, eaves, carport or the like that projects at a minimum angle of 15 degrees in accordance with Figure 3.12.1.2; and
when the external walls are not shaded in accordance with (A)and there is another storey above,external glazing complies with 3.12.2.1 with the applicable value for CSHGC in Table 3.12.2.1e reduced by 15%;and
incorporate insulation with an R-Value of greater than or equal to 0.5; and
on the lowest storey containing habitable rooms, have either—
a concrete slab-on-ground floor; or
masonry internal walls; or
in climate zone 5 (option b)—
shade the wall with a verandah, balcony, eaves, carport or the like that projects at a minimum angle of 15 degrees in accordance with Figure 3.12.1.2; and
have external glazing that complies with 3.12.2.1 with the applicable value for CSHGC in Table 3.12.2.1e reduced by 15%; and
on the lowest storey containing habitable rooms, have either—
a concrete slab-on-ground floor; or
masonry internal walls; or
in climate zones 4 and 6 (option a)—
incorporate insulation with an R-Value of greater than or equal to 0.5; and
on the lowest storey containing habitable rooms, have either—
a concrete slab-on-ground floor; or
masonry internal walls; or
in climate zones 4 and 6 (option b), have external glazing that complies with 3.12.2.1 with the applicable value for CU in Tables 3.12.2.1d and 3.12.2.1f reduced by 20%; or
in climate zones 4 and 6 (option c)—
incorporate insulation with an R-Value of greater than or equal to 1.0; and
on the lowest storey containing habitable rooms, have either—
a concrete slab-on-ground floor; or
masonry internal walls; or
in climate zone 7 (option a)—
incorporate insulation with an R-Value of greater than or equal to 1.0; or
in climate zone 7 (option b)—
incorporate insulation with an R-Value of greater than or equal to 0.5; or
in climate zone 7 (option c), incorporate insulation with an R-Value of greater than or equal to 1.5; or
in climate zone 8, achieve a minimum Total R-Value of 3.8.
Guttering can be considered as providing shading if attached to a shading projection.
A wall in (b) that—
has lightweight external cladding such as weatherboards, fibre-cement or metal sheeting fixed to the metal frame; and
does not have a wall lining or has a wall lining that is fixed directly to the metal frame (see Figure 3.12.1.3(a) and (b)),
must have a thermal break, consisting of a material with an R-Value greater than or equal to 0.2, installed between the external cladding and the metal frame.
A thermal break may be provided by materials such as timber battens, plastic strips or polystyrene insulation sheeting.The material used as a thermal break must separate the metal frame from the cladding and achieve the specified R-Value.
For the purposes of 3.12.1.4(d)(ii), expanded polystyrene strips greater than or equal to 12 mm thickness and timber greater than or equal to 20 mm thickness are deemed to achieve an R-Value greater than or equal to 0.2.
The R-Value of the thermal break is not included when calculating the Total R-Value of the wall, if the thermal break is only applied to the metal frame, because this calculation is done for locations free of framing members.
A wall in constructed in accordance with Figure 3.12.1.3 is deemed to have the Total R-Value specified in that Figure
Explanatory information for R-Value added by reflective insulation
Wall construction | Reflective airspace details | R-Value added by reflective insulation |
---|---|---|
Concrete or masonry with internal plasterboard on battens |
One 20 mm reflective airspace located between reflective insulation (of not more than 0.05 emittance inwards) and plasterboard | 0.48 |
External wall cladding (70 mm timber frame with internal lining) | One 70 mm reflective airspace located between reflective insulation (of not more than 0.05 emittance inwards) and plasterboard | 0.43 |
Masonry veneer (70 mm timber frame with internal lining) |
|
0.95 |
Cavity masonry |
|
0.50 |
A suspended floor, other than an intermediate floor in a building with more than one storey—
must achieve the Total R-Value specified in Table 3.12.1.4; and
Table 3.12.1.4 Suspended floor – minimum Total R-Value
Climate zone | Direction of heat flow | Minimum Total R-Value |
---|---|---|
1 | Up | 1.5 |
2 | Up | 1.0 |
3 | Up | 1.5 |
4 | Down | 2.25 |
5 | Down | 1.0 |
6 | Down | 2.25 |
7 | Down | 2.75 |
8 | Down | 3.25 |
Note to Table 3.12.1.4: For an enclosed perimeter treatment, the under floor airspace and its enclosure may be included in the Total R-Value calculation.
with an in-slab or in-screed heating or cooling system, must be insulated—
around the vertical edge of its perimeter with insulation having an R-Value greater than or equal to 1.0; and
that is enclosed beneath, must have a barrier installed at or below floor level to prevent convection within the wall cavity, from the airspace under the floor.
A floor is deemed to have the Total R-Value specified in Tables 3.12.1.5a and 3.12.1.5b.
Notes to Tables 3.12.1.5a:
Table 3.12.1.5b Total R-Value for typical suspended concrete floor
Enclosure and height of floor and direction of heat flow | Cavity masonry | 190 mm concrete masonry | Single skin masonry | 9 mm fibre-cement sheet |
---|---|---|---|---|
Enclosed ≤0.6 m high with an upwards heat flow | Total R-Value: 0.93 | Total R-Value: 0.88 | Total R-Value: 0.83 | Total R-Value: 0.72 |
Enclosed ≤0.6 m high with a downwards heat flow | Total R-Value: 1.06 | Total R-Value: 1.01 | Total R-Value: 0.96 | Total R-Value: 0.85 |
Enclosed >0.6 m but to ≤1.2 m high with an upwards heat flow |
Total R-Value: 0.81 |
Total R-Value: 0.76 | Total R-Value: 0.71 | Total R-Value: 0.60 |
Enclosed >0.6 m but to ≤1.2 m high with a downwards heat flow | Total R-Value: 0.94 | Total R-Value: 0.89 | Total R-Value: 0.84 | Total R-Value: 0.72 |
Enclosed >1.2 m to ≤2.4 m high with an upwards heat flow | Total R-Value: 0.71 | Total R-Value: 0.67 | Total R-Value: 0.62 | Total R-Value: 0.52 |
Enclosed >1.2 m to ≤2.4 m high with a downwards heat flow | Total R-Value: 0.84 | Total R-Value: 0.79 | Total R-Value: 0.74 | Total R-Value: 0.64 |
Unenclosed with an upwards heat flow | Total R-Value: 0.34 | Total R-Value: 0.34 | Total R-Value: 0.34 | Total R-Value: 0.34 |
Unenclosed with a downwards heat flow | Total R-Value: 0.46 | Total R-Value: 0.46 | Total R-Value: 0.46 | Total R-Value: 0.46 |
Notes to Tables 3.12.1.5b:
Table 3.12.1.5a Total R-Value for typical suspended timber floor
Enclosure and height of floor and direction of heat flow | Cavity masonry | 190 mm concrete masonry | Single skin masonry | 9 mm fibre-cement sheet |
---|---|---|---|---|
Enclosed ≤0.6 m high with an upwards heat flow | Total R-Value: 1.00 | Total R-Value: 0.93 | Total R-Value: 0.88 | Total R-Value: 0.77 |
Enclosed ≤0.6 m high with a downwards heat flow | Total R-Value: 1.11 | Total R-Value: 1.06 | Total R-Value: 1.01 | Total R-Value: 0.90 |
Enclosed >0.6 m but to ≤1.2 m high with an upwards heat flow |
Total R-Value: 0.86 |
Total R-Value: 0.81 | Total R-Value: 0.76 | Total R-Value: 0.65 |
Enclosed >0.6 m but to ≤1.2 m high with a downwards heat flow | Total R-Value: 1.00 | Total R-Value: 0.94 | Total R-Value: 0.89 | Total R-Value: 0.77 |
Enclosed >1.2 m to ≤2.4 m high with an upwards heat flow | Total R-Value: 0.76 | Total R-Value: 0.72 | Total R-Value: 0.67 | Total R-Value: 0.57 |
Enclosed >1.2 m to ≤2.4 m high with a downwards heat flow | Total R-Value: 0.89 | Total R-Value: 0.84 | Total R-Value: 0.79 | Total R-Value: 0.69 |
Unenclosed with an upwards heat flow | Total R-Value: 0.39 | Total R-Value: 0.39 | Total R-Value: 0.39 | Total R-Value: 0.39 |
Unenclosed with a downwards heat flow | Total R-Value: 0.51 | Total R-Value: 0.51 | Total R-Value: 0.51 | Total R-Value: 0.51 |
A concrete slab-on-ground—
with an in-slab or in-screed heating or cooling system, must have insulation with an R-Value greater than or equal to 1.0, installed around the vertical edge of its perimeter; and
Insulation required by (c)(i) and (c)(ii)(A) must—
be water resistant; and
be continuous from the adjacent finished ground level—
to a depth of greater than or equal to 300 mm; or
for at least the full depth of the vertical edge of the concrete slab-on-ground (see Figure 3.12.1.4).
The requirements of (a)(ii), and (c)(i) do not apply to an in-screed heating or cooling system used solely in a bathroom, amenity area or the like.
3.12.1.5(e) provides an exemption for an in-screed heating or cooling system used solely in bathrooms, amenity areas and the like, as these are typically small areas.
Care should be taken to ensure that the type of termite management system selected is compatible with the slab edge insulation.
A Class 10a building attached to a Class 1 building must—
have an external fabric that achieves the required level of thermal performance for a Class 1 building; or
be separated from the Class 1 building with construction having the required level of thermal performance for the Class 1 building; or
in climate zone 5—
be enclosed with masonry walls other than where there are doors and glazing; and
be separated from the Class 1 building with a masonry wall that extends to the ceiling or roof; and
achieve a Total R-Value in the roof equivalent to that required by Tables 3.12.1.1a to 3.12.2.1h as appropriate for the Class 1 building; and
not have a garage door facing the east or west orientation other than if the Class 1 building glazing complies with 3.12.2.1 with the applicable value for CSHGC in Tables 3.12.2.1a to 3.12.2.1h as appropriate reduced by 15%.
The attachment of a Class 10a building, such as a garage, glasshouse, solarium, pool enclosure or the like should not compromise the thermal performance of the Class 1 building. In addition, the Class 10a building may be insulated and so assist the Class 1 building achieve the required thermal performance.
The following are examples of a Class 1 building with an attached Class 10a garage.
In (a), the thermal performance required for the Class 1 building may be achieved by including the walls and floor of the Class 1 building that adjoin the Class 10a garage.
In (b), the thermal performance required for the Class 1 building may be achieved by including the outside walls and floor of the Class 10a garage.
In (c),in climate zone 5, the thermal performance of the Class 1 building may be achieved by ensuring that the roof of the Class 10a building satisfies Tables 3.12.1.1a to 3.12.1.1g and the walls are of masonry construction.