NCC 2019 Volume Two Amendment 1
Search the National Construction Code editions
This Part applies to—
a Class 1 building; and
a Class 10a building; and
a Class 10b swimming pool associated with a Class 1 or 10a building.
A heated water supply system must be designed and installed in accordance with Part B2 of NCC Volume Three — Plumbing Code of Australia.
Thermal insulation for central heating water piping and heating and cooling ductwork must—
be protected against the effects of weather and sunlight; and
be able to withstand the temperatures within the piping or ductwork; and
use thermal insulation material in accordance with AS/NZS 4859.1.
The central heating water piping provisions apply to systems designed to heat the building via water, such as a hydronic heating system.
Central heating water piping that is not within a conditioned space must be thermally insulated to achieve the minimum material R-Value as follows:
Internal piping including—
flow and return piping that is—
within an unventilated wall space; or
within an internal floor between storeys; or
between ceiling insulation and a ceiling; and
heated water piping encased within a concrete floor slab (except that which is part of a floor heating system),
must, in all climate zones, have a minimum material R-Value of 0.4.
Piping located within a ventilated wall space, an enclosed building subfloor or a roof space, including—
flow and return piping; and
cold water supply piping within 500 mm of the connection to the central water heating system; and
relief valve piping within 500 mm of the connection to the central water heating system,
must have a minimum material R-Value of—
in climate zones 1, 2, 3 and 5 — 0.6; and
in climate zones 4, 6 and 7 — 0.9; and
in climate zone 8 — 1.3.
Piping located outside the building or in an unenclosed building subfloor or roof space, including—
flow and return piping; and
cold water supply piping within 500 mm of the connection to the central water heating system; and
relief valve piping within 500 mm of the connection to the central water heating system,
must have a minimum material R-Value of—
in climate zones 1, 2, 3 and 5 — 0.6; and
in climate zones 4, 6 and 7 — 1.3; and
in climate zone 8 — 1.3.
Insulation |
|
9 mm of closed cell polymer |
0.4 |
13 mm of closed cell polymer |
0.6 |
19 mm of closed cell polymer |
0.9 |
25 mm of closed cell polymer |
1.3 |
25 mm of glasswool |
1.3 |
Heating and cooling ductwork and fittings must—
achieve the material R-Value in 3.12.5.3(d); and
be sealed against air loss—
by closing all openings in the surface, joints and seams of ductwork with adhesives, mastics, sealants or gaskets in accordance with AS 4254.1 and AS 4254.2 for a Class C seal; or
for flexible ductwork, with a draw band in conjunction with a sealant or adhesive tape.
Duct insulation must—
abut adjoining duct insulation to form a continuous barrier; and
be installed so that it maintains its position and thickness, other than at flanges and supports; and
where located outside the building, under a suspended floor, in an attached Class 10a building or in a roof space—
be protected by an outer sleeve of protective sheeting to prevent the insulation becoming damp; and
have the outer protective sleeve sealed with adhesive tape not less than 48 mm wide creating an airtight and waterproof seal.
The requirements of (a) do not apply to heating and cooling ductwork and fittings located within the insulated building envelope including a service riser within the conditioned space, internal floors between storeys and the like.
Ductwork within a fully insulated building may still benefit from insulation particularly when the system is only operating for short periods.
In some climate zones condensation may create problems with uninsulated ductwork, in which case insulation should still be considered.
The material R-Value required by (a)(i) must be determined in accordance with the following:
In a heating-only system or cooling-only system including an evaporative cooling system—
ductwork must have a minimum material R-Value of—
in climate zones 1 to 7 — 1.0; and
in climate zone 8 — 1.5; and
fittings must have a minimum material R-Value of 0.4.
In a combined heating and refrigerated cooling system—
ductwork must have a minimum material R-Value of—
in climate zones 1, 3, 4, 6 and 7 — 1.5; and
in climate zones 2 and 5 — 1.0; and
in climate zone 8 — 1.5; and
fittings must have a minimum material R-Value of 0.4.
For the purposes of (d)(ii)(A), the minimum material R-Value required for ductwork may be reduced by 0.5 for combined heating and refrigerated cooling systems in climate zones 1, 3, 4, 6 and 7 if the ducts are—
under a suspended floor with an enclosed perimeter; or
in a roof space that has an insulation of greater than or equal to R0.5 directly beneath the roofing.
Insulating material and thickness | R-Value |
---|---|
45 mm glasswool (11 kg/m3) | 1.0 |
70 mm polyester (6.4 kg/m3) | 1.0 |
63 mm glasswool (11 kg/m3) | 1.5 |
90 mm polyester (8.9 kg/m3) | 1.5 |
85 mm glasswool (11 kg/m2) | 2.0 |
Insulating material and thickness | R-Value |
---|---|
38 mm glasswool (22 kg/m3) | 1.0 |
50 mm polyester (20 kg/m3) | 1.1 |
50 mm glasswool (22 kg/m3) | 1.5 |
75 mm polyester (20 kg/m3) | 1.7 |
Insulating material and thickness | R-Value |
---|---|
38 mm glasswool (32 kg/m3) | 1.0 |
50 mm polyester (32 kg/m3) | 1.3 |
50 mm glasswool (32 kg/m3) | 1.5 |
An electric resistance space heating system that serves more than one room must have—
separate isolating switches for each room; and
a separate temperature controller and time switch for each group of rooms with common heating needs; and
power loads of not more than 110 W/m2 for living areas, and 150 W/m2 for bathrooms.
The lamp power density or illumination power density of artificial lighting, excluding heaters that emit light, must not exceed the allowance of—
5 W/m2 in a Class 1 building; and
4 W/m2 on a verandah, balcony or the like attached to a Class 1 building; and
3 W/m2 in a Class 10a building associated with a Class 1 building.
The illumination power density allowance in (a) may be increased by dividing it by the relevant illumination power density adjustment factor for a control device in (f) as applicable.
When designing the lamp power density or illumination power density, the power of the proposed installation must be used rather than nominal allowances for exposed batten holders or luminaires.
When illumination power density and one or more control devices are used, the adjustment factor is only applied to the space(s) served by the control device. The adjusted allowance for this space is then combined with the allowances for the remaining spaces using an area weighted average, which subsequently increases the allowance provided in (a)(i), (ii) or (iii).
When no control device is used, the adjustment factor is equal to 1.
The second step in achieving compliance is to assess the overall lamp power density or overall illumination power density of the building.
Control device adjustment factors in (b) are only applied to the illumination power density, not the overall illumination power density.
If halogen lamps are installed, they must be separately switched from fluorescent lamps.
Artificial lighting around the perimeter of a building must—
be controlled by a daylight sensor; or
have an average light source efficacy of not less than 40 Lumens/W.
The artificial lighting around the perimeter of a building does not need to comply to a maximum power density as neither the lighting required or the area of the space can be easily defined. Instead, external lights are required to be controlled by daylight sensors or to be efficient.
In (d), separate switching is required for halogen lamps to facilitate less frequent usage. This is because they are significantly less energy efficient than fluorescent lamps.
The following illumination power density adjustment factors apply to control devices for artificial lighting:
Lighting timer for corridor lighting: 0.7.
Motion detector —
0.9, where —
at least 75% of the area of a space is controlled by one or more motion detectors; or
an area of less than 200 m2 is switched as a block by one or more motion detectors; and
0.7, where up to 6 lights are switched as a block by one or more detectors; and
0.55, where up to 2 lights are switched as a block by one or more detectors.
Manual dimming system where not less than 75% of the area of a space is controlled by manually operated dimmers: 0.85.
Programmable dimming system where not less than 75% of the area of a space is controlled by manually operated dimmers: 0.85.
Dynamic dimming system, with automatic compensation for lumen depreciation, the design lumen depreciation factor is not less than —
0.9 for fluorescent lights; or
0.8 for high pressure discharge lights.
Fixed dimming where at least 75% of the area is controlled by fixed dimmers that reduce the overall lighting level and the power consumption of the lighting — equal to the % of full power to which the dimmer is set divided by 0.95.
Daylight sensor and dynamic lighting control device, with dimmed or stepped switching of lights adjacent to windows:
Lights within the space adjacent to windows other than roof lightsfor a distance from the window equal to the depth of the floor at window head height: 0.5.
Lights within the space adjacent to roof lights: 0.6.
For the purposes of (f)(iii), manual dimming is where lights are controlled by a knob, slider or other mechanism or where there are pre-selected scenes that are manually selected.
For the purposes of (f)(iv), programmed dimming is where pre-selected scenes or levels are automatically selected by the time of day, photoelectric cell or occupancy sensor.
For the purposes of (f)(v), dynamic dimming is where the lighting level is varied automatically by a photoelectric cell to either proportionately compensate for the availability of daylight or the lumen depreciation of the lamps.
For the purposes of (f)(vi), fixed dimming is where lights are controlled to a level and that level cannot be adjusted by the user.
For the purposes of (f)(vii)(A) and (B), the illumination power density adjustment factor is only applied to lights controlled by that item — this adjustment factor does not apply to tungsten halogen or other incandescent sources.
A water heater in a heated water supply system must be designed and installed in accordance with Part B2 of NCC Volume Three — Plumbing Code of Australia.
Heating for a swimming pool must be by—
a solar heater not boosted by electric resistance heating; or
a heater using reclaimed energy; or
a gas heater; or
a heat pump; or
Where some or all of the heating required by (a) is by a gas heater or a heat pump, the swimming pool must have—
a cover unless located in a conditioned space; and
a time switch to control the operation of the heater.
A time switch must be provided to control the operation of a circulation pump for a swimming pool.
For the purposes of 3.12.5.7, a swimming pool does not include a spa pool.
Some jurisdictions may have requirements for a pool cover under the Smart Approved WaterMark Scheme.
Heating for a spa pool that shares a water recirculation system with a swimming pool must be by—
a solar heater; or
a heater using reclaimed energy; or
a gas heater; or
a heat pump; or
A time switch must be provided to control the operation of a circulation pump for a spa pool having a capacity of 680 L or more.