NCC 2019 Volume Two Amendment 1
Search the National Construction Code editions
Objective
O2.4.1 Wet areas
The Objective is to safeguard the occupants from illness or injury and protect the building from damage caused by the accumulation of internal moisture arising from the use of wet areas in a building.
O2.4.2 Room heights
The Objective is to safeguard the occupants from injury or loss of amenity caused by inadequate height of a room or space.
O2.4.3 Facilities
The Objective is to—
O2.4.4 Light
The Objective is to safeguard occupants from injury, illness or loss of amenity due to—
O2.4.5 Ventilation
The Objective is to safeguard occupants from illness or loss of amenity due to lack of air freshness.
O2.4.6 Sound insulation
The Objective is to safeguard occupants from illness or loss of amenity as a result of undue sound being transmitted between adjoining dwellings.
Functional Statements
F2.4.1 Wet areas
A building is to be constructed to avoid the likelihood of—
caused by dampness or water overflow from bathrooms, laundries and the like.
F2.4.2 Room heights
A building is to be constructed to provide height in a room or space suitable for the intended use.
F2.4.3 Facilities
A building is to be provided with suitable—
Application:
F2.4.3 only applies to a Class 1 building.
F2.4.4 Light
F2.4.5 Ventilation
A space used by occupants within a building is to be provided with adequate ventilation consistent with its function or use.
F2.4.6 Sound insulation
A building element which separates dwellings is to be constructed to prevent undue sound transmission between those dwellings.
To protect the structure of the building and to maintain the amenity of the occupants, water must be prevented from penetrating—
behind fittings and linings; or
into concealed spaces,
of sanitary facilities, bathrooms, laundries and the like.
A room or space must be of a height that does not unduly interfere with its intended function.
Suitable sanitary facilities for personal hygiene must be provided in a convenient location within or associated with a building, appropriate to its function or use.
* * * * *
This clause has been deliberately left blank.
Laundering facilities or space for laundering facilities and the means for sanitary disposal of waste water must be provided in a convenient location within or associated with a building, appropriate to its function or use.
A food preparation facility must be provided which includes—
a means for food rinsing, utensil washing and the sanitary disposal of associated waste water; and
a means for cooking food; and
a space for food preparation.
A sanitary compartment must be constructed with sufficient space or other means to enable an unconscious occupant to be removed from the compartment.
P2.4.3 only applies to a Class 1 building.
For the purposes of P2.4.3(c), waste water includes water that is soiled as a result of clothes washing, mopping floors and other domestic cleaning processes.
A habitable room must be provided with windows, where appropriate to the function or use of that part of the building, so that natural light, when available, provides an average daylight factor of not less than 2%.
Artificial lighting must be installed to provide an illuminance of not less than 20 lux appropriate to the function or use of the building to enable safe movement by occupants.
P2.4.4(b) only applies—
P2.4.4(a) nominates a minimum average daylight factor for rooms provided with natural light. Note that Verification Method V2.4.4 provides a method by which the average daylight factor may be calculated.
To comply with P2.4.4(b), the level of artificial light must enable safe movement by occupants, appropriate to the use of the building. For example, in a movie room a lower level of lighting may be appropriate while a movie is being screened, however at the beginning and end of the movie when occupants are entering and exiting the movie room the minimum lighting level of 20 lux may be appropriate.
A space within a building used by occupants must be provided with means of ventilation with outdoor air which will maintain adequate air quality.
A mechanical air-handling system installed in a building must control—
the circulation of objectionable odours; and
the accumulation of harmful contamination by micro-organisms, pathogens and toxins.
Contaminated air must be disposed of in a manner which does not unduly create a nuisance or hazard to people in the building or other property.
Walls separating dwellings must provide insulation against the transmission of airborne sound sufficient to prevent illness or loss of amenity to the occupants.
Walls separating a bathroom, sanitary compartment, laundry or kitchen in a dwelling from a habitable room (other than a kitchen) in an adjoining dwelling, must provide insulation against impact generated sound sufficient to prevent illness or loss of amenity to the occupants.
The required sound insulation of walls must not be compromised by the incorporation or penetration of a pipe or other service element.
State and Territory Variations
In Northern Territory P2.4.6 is replaced with the following:
P2.4.6 Sound insulation
Risks associated with water vapour and condensation must be managed to minimise their impact on the health of occupants.
P2.4.7 only applies to a Class 1 building.
Compliance with P2.4.2 is verified where the height of a room or space provides an appropriate activity support level that does not unduly interfere with its intended function.
For a room or space in (a), the activity support level must consider the dimensions of—
doors, ramps, barriers, stairs and windows; and
fixed fittings and domestic services; and
fixed and moveable equipment or furniture; and
occupant circulation spaces.
The intent of P2.4.2 is the height of a room or space is sufficient for the intended use of the room or space. ‘Intended use’ recognises that the height required in a room or space is directly related to the room or space's intended function.
V2.4.2 is a means to verify that the height of a room or space is suitable for the intended use, and therefore meets the requirement of P2.4.2.
In relation to the intended function of a room or space, the activities that are likely to be undertaken by occupants in the room of space, as well the features of the activities, are relevant considerations when determining a suitable height.
For example, if the intended use of a room is a gymnasium, then gymnastic activities are likely to be undertaken in the room. These activities often involve jumps and flips which require significant space in order to be undertaken safely.
In terms of the occupants, their features and needs are also relevant when determining a suitable height. For example, occupant features and needs would differ between rooms or spaces intended as a child’s play area, and rooms or spaces intended for adult’s indoor cricket.
The method requires the consideration of occupant characteristics and activity characteristics through the defined terms ‘activity traits’, ‘occupant traits’ and ‘activity support level’. Refer to Schedule 3 for more information on these terms.
When determining the activity support level, the method requires consideration of the relevant dimensions of items likely to be located in the room or space, as well as occupant circulation spaces.
Some of these considerations are—
For example, the location and dimensions of a wash-basin is a relevant consideration in determining the activity support level of a bathroom. This is because an occupant will typically need to access the wash-basin whilst standing, which will influence the necessary height of the space.
Another example is the consideration of moveable equipment such as a refrigerator in a kitchen. If the intended use of a space is a kitchen, then it would be unrealistic to determine a sufficient height for the room without considering the height of a typical refrigerator that would be located in the room.
Compliance with P2.4.4(a) is verified for the provision of natural light in all habitable rooms when the average daylight factor for each window is determined in accordance with the following formula:
W = the net area of the light transmitting area of the window (m2); and
A = the total area of the internal wall, floor and ceiling surfaces (m2); and
T = the diffuse light transmittance of the window; and
θ = visible sky angle in degrees, measured in a vertical plane normal to and from the centre of the window; and
R = the area-weighted average reflectance of area A.
For a Class 1 building, compliance with P2.4.5(a) and P2.4.5(b)(i) is verified when it is determined that the building under typical conditions in use is provided with sufficient ventilation with outdoor air such that contaminant levels do not exceed the limits specified in Table V2.4.5.
Pollutant |
Averaging Time |
Maximum Air Quality Value |
---|---|---|
Carbon dioxide, CO2 |
8 hours |
850 ppm Note 1 |
Carbon monoxide, CO |
15 minutes |
90 ppm |
Carbon monoxide, CO |
30 minutes |
50 ppm |
Carbon monoxide, CO |
1 hour |
25 ppm |
Carbon monoxide, CO |
8 hours |
10 ppm |
Formaldehyde, CH2O |
30 minutes |
0.1 mg/m3 |
Nitrogen dioxide, NO2 |
1 year |
40 μg/m3 (0.0197 ppm) Note 2 |
Nitrogen dioxide, NO2 |
1 hour |
200 μg/m3 (0.0987 ppm) Note 2 |
Ozone, O3 |
8 hour, daily maximum |
100 μg/m3 (0.0473 ppm) |
Particulate matter, PM2.5 |
1 year |
10 μg/m3 |
Particulate matter, PM2.5 |
24 hour (99th percentile) |
25 μg/m3 |
Particulate matter, PM10 |
1 year |
20 μg/m3 |
Particulate matter, PM10 |
24 hour (99th percentile) |
50 μg/m3 |
Total volatile organic compounds |
1 hour |
500 μg/m3 |
Notes to Table V2.4.5 :
Compliance with P2.4.6(a) and (c) to insulate against transmission of airborne sound through walls separating dwellings is verified when it is measured in-situ that the wall has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 when determined under AS/NZS ISO 717.1.
State and Territory Variations
V2.4.6 does not apply in Northern Territory.
Compliance with P2.4.7 is verified when modelling that assesses the effects of—
indoor and outdoor temperature and humidity conditions; and
heating and cooling set points; and
rain absorption; and
wind pressure; and
solar radiation; and
material hygrothermal properties,
determines that moisture will not accumulate—
interior to the primary water control layer within a building envelope; or
on the interior surface of the water control layer.