Part 3.3.6 Isolated masonry piers
Appropriate Performance Requirements
Where an alternative isolated masonry pier system is proposed as a Performance Solution to that described in Part 3.3.6, that proposal must comply with—
Performance RequirementP2.1.1 is satisfied for an isolated masonry pier system if it is designed and constructed in accordance with one of the following, as appropriate:
AS 3700, except—
'(for piers—isolated or engaged)' is removed from Clause 8.5.1(d); and
where Clause 8.5.1 requires design as for unreinforced masonry in accordance with Section 7, the member must also be designed as unreinforced masonry in accordance with Tables 10.3 and 4.1(a)(i)(C) of AS 3700.
AS 4773.1 and AS 4773.2.
Compliance with this acceptable construction practice satisfies Performance Requirement P2.1.1 for an isolated masonry pier system provided—
the building is located in an area with a design wind speed of not more than N3; and
isolated piers are constructed on footings that comply with Part 3.2; and
masonry units comply with 3.3.5.3(c) and have a minimum compressive strength of—
6.2 MPa for solid or cored units; or
15 MPa for hollow units; and
the roof structure and any walls provide the required lateral bracing for the top of the isolated pier when determined in accordance with AS 3700, except—
'(for piers—isolated or engaged)' is removed from Clause 8.5.1(d); and
where Clause 8.5.1 requires design as for unreinforced masonry in accordance with Section 7, the member must also be designed as unreinforced masonry in accordance with Tables 10.3 and 4.1(a)(i)(C) of AS 3700; and
the building site soil classification is either A, S or M; and
the building is not constructed in an alpine area; and
the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.
Isolated piers supporting carports, verandahs, porches and similar roof structures, or vehicle access door openings, which form part of the main roof, or are attached to a wall of a Class 1 building must—
be not less than 290 x 290 mm in section; and
be not more than 2.7 m high (see Figure 3.3.6.1); and
be spaced at not more than 3 m centres (see Figure 3.3.6.1); and
provide a bearing length of not less than 150 mm for any supported members; and
comply with the relevant provisions of this Part.
Isolated piers supporting tiled roofs must have—
a built-in 32 x 0.8 mm galvanised steel strap fixed to the roof structure that extends the full height of the pier; and
Isolated piers supporting sheet roofs must have—
a built-in 32 x 0.8 mm galvanised steel strap fixed to the roof structure extending the full height of the pier which is looped and fixed around a 4.6 grade 16 mm diameter galvanised steel rod cast into the footing when poured; or
a 4.6 grade M16 galvanised steel rod cast into the footing, threaded at the top and extending the full height of the pier to connect to the roof structure.
Piers for freestanding carports must—
be not less than 290 x 290 mm with the central core filled with 20 MPa concrete, or an exposure class mortar (see Table 3.3.5.2) complying with 3.3.5.4; and
have the core reinforced with one Y16 steel reinforcing rod cast into the footing and extending the full height of the pier to connect to the roof structure.
Subfloor isolated piers must be a minimum of 190 x 190 mm in section and comply with Figure 3.3.6.2 for height requirements.