NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Search the National Construction Code editions
C4
Part C4 Protection of openingsPart C4 Protection of openings
This Part contains Deemed-to-Satisfy Provisions for Part C1. It covers the protection of openings such as windows, doors, services and construction joints to reduce the risk of fire spread within or between buildings.
Deemed-to-Satisfy Provisions
C4D1
Deemed-to-Satisfy Provisions
2019: C3.0
C4D2
Application of Part
2019: C3.1
C4D3
Protection of openings in external walls
2019: C3.2
C4D4
Separation of external walls and associated openings in different fire compartments
2019: C3.3
The distance between parts of external walls and any openings within them in different fire compartments separated by a fire wall must not be less than that set out in Table C4D4, unless—
Angle between walls | Minimum distance (m) |
---|---|
0° (walls opposite) | 6 |
more than 0° to 45° | 5 |
more than 45° to 90° | 4 |
more than 90° to 135° | 3 |
more than 135° to less than 180° | 2 |
180° or more | Nil |
C4D5
Acceptable methods of protection
2019: C3.4
C4D6
Doorways in fire walls
2019: C3.5
C4D7
Sliding fire doors
2019: C3.6
C4D8
Protection of doorways in horizontal exits
2019: C3.7
C4D9
Openings in fire-isolated exits
2019: C3.8
C4D10
Service penetrations in fire-isolated exits
2019: C3.9
Fire-isolated exits must not be penetrated by any services other than—
C4D11
Openings in fire-isolated lift shafts
2019: C3.10
C4D12
Bounding construction: Class 2 and 3 buildings and Class 4 parts
2019: C3.11
C4D13
Openings in floors and ceilings for services
2019: C3.12
the service must be installed in accordance with (2).
C4D14
Openings in shafts
2019: C3.13
In a building of Type A construction, an opening in a wall providing access to a ventilating, pipe, garbage or other service shaft must be protected by—
C4D15
Openings for service installations
2019: C3.15
C4D16
Construction joints
2019: C3.16
C4D17
Columns protected with lightweight construction to achieve an FRL
2019: C3.17
A column protected by lightweight construction to achieve an FRL which passes through a building element that is required to have an FRL or a resistance to the incipient spread of fire, must be installed using a method and materials identical with a prototype assembly of the construction which has achieved the required FRL or resistance to the incipient spread of fire.
Where external stairs, ramps or ladders are used as an exit in a bulk grain storage facility, any window or door opening within 6 m of the stairway or ladder—
Protection of openings – bulk grain storage facilities