Emergency access doors in a single enclosed lift shaft
2019: Spec E3.1: 6
(1) Where a lift is installed in a single enclosed lift shaft having a distance between normal landing entrances greater than 12.2 m, emergency access doors must be provided and constructed as follows:
The clear opening size of emergency doors must be not less than 600 mm wide x 980 mm high.
Hinged doors must not open towards the interior of the lift shaft.
Doors must be marked on the landing side with the letters not less than 35 mm high:
DANGER LIFTWELL ACCESS
KEEP FURNITURE AND FIXTURES CLEAR
Doors from the landing side must only be openable by a tool.
Each emergency door must be provided with a positive breaking electrical contact, wired into the control circuit to prevent movement of the lift until the emergency door is both closed and locked.
(2) Emergency egress from the lift car must be provided in single enclosed lift shafts where—
ropes are installed; and
the vertical distance between the lift car sill and the landing door head is less than 600 mm; and
the counterweight is resting on its fully compressed buffer.
(3) Emergency egress required by (2) must be in the form of an interlocked door with clear opening dimensions not less than 600 mm x 600 mm, accessible from the lift car entrance or the lift car roof (where the door is located in the wall of the lift shaft).