A fire control centre must be so located in a building that egress from any part of its floor, to a road or open space, does not involve changes in level which in aggregate exceed 300 mm.
Equipment not permitted within a fire control centre
2019: Spec E1.8: 4
An internal combustion engine, pumps, sprinkler control valves, pipes and pipe fittings must not be located in a fire control centre, but may be located in rooms accessed through the fire control centre.
(1) The ambient sound level within the fire control centre measured when all fire safety equipment is operating in the manner in which it operates in an emergency must not exceed 65 dB(A).
(2) The measurement must be taken for a sufficient time to characterise the effects of all sound sources.
(3) Where there is not a great variation in noise level, a measurement time of 60 seconds may be used.
A fire control centre in a building more than 50 m in effective height must be in a separate room where—
the enclosing construction is of concrete, masonry or the like, sufficiently impact resistant to withstand the impact of any likely falling debris, and with an FRL of not less than 120/120/120; and
any material used as a finish, surface, lining or the like within the room complies with the requirements of Specification 7; and
services, pipes, ducts and the like that are not directly required for the proper functioning of the fire control room do not pass through it; and
openings in the walls, floors or ceiling which separate the room from the interior of the building are confined to doorways, ventilation and other openings for services necessary for the proper functioning of the facility.
(1) Required doors to a fire control room must open into the room, be lockable and located so that persons using escape routes from the building will not obstruct or hinder access to the room.
(2) The fire control room must be accessible via two paths of travel—
one from the front entrance of the building; and
one direct from a public place or fire-isolated passageway which leads to a public place and has a door with an FRL of not less than –/120/30.
a Fire Indicator Panel and necessary control switches and visual status indication for all required fire pumps, smoke control fans and other required fire safety equipment installed in the building; and
a telephone directly connected to an external telephone exchange; and
a blackboard or whiteboard not less than 1200 mm wide x 1000 mm high; and
a pin-up board not less than 1200 mm wide x 1000 mm high; and
a raked plan layout table of a size suitable for laying out the plans provided under (f); and
colour-coded, durable, tactical fire plans.
(2) In addition, a fire control room may contain—
master emergency control panels, lift annunciator panels, remote switching controls for gas or electrical supplies and emergency generator backup; and
building security, surveillance and management systems if they are completely segregated from all other systems.
(3) A fire control room must—
have a floor area of not less than 10 m2 and the length of any internal side must be not less than 2.5 m; and
if only the minimum prescribed equipment is installed — have a net floor area of not less than 8 m2 with a clear space of not less than 1.5 m2 in front of the Fire Indicator Panel; and
if additional equipment is installed — have an additional area of not less than 2 m2 net floor area for each additional facility and a clear space of not less than 1.5 m2 in front of each additional control or indicator panel; and
be constructed such that the area required for any path of travel through the room to other areas is provided in addition to the requirements (b) and (c).
Ventilation and power supply for a fire control room
2019: Spec E1.8: 10
(1) A fire control room must be ventilated by—
natural ventilation from a window or doorway in an external wall of the building which opens directly into the fire control room from a road or open space; or
a pressurisation system that only serves the fire control room, and—
is installed in accordance with AS 1668.1 as though the room is a fire-isolated stairway; and
is activated automatically by operation of the fire alarm, or sprinkler system complying with Specification 17, installed in the building and manually by an over-riding control in the room; and
provides a flow of fresh air through the room of not less than 30 air changes per hour when the system is operating and any door to the room is open; and
has fans, motors and ductwork that form part of the system but not contained within the fire control room protected by enclosing construction with an FRL of not less than 120/120/120; and
has any electrical supply to the fire control room or equipment necessary for its operation connected to the supply side of the main disconnection switch for the building.
(2) No openable devices, other than necessary doorways, pressure controlled relief louvres and windows that are openable by a key, must be constructed in the fire control room.
Emergency lighting in accordance with the Deemed-to-Satisfy Provisions of Part E4 must be provided in a fire control room, except that an illumination level of not less than 400 lux must be maintained at the surface of the plan table.