NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

J4

Part J4 Building fabric

Part J4 Building fabric

Introduction to this Part

This Part contains Deemed-to-Satisfy Provisions for compliance with Part J1. It sets out provisions for the building envelope including roofs, ceilings, roof lights, walls, glazing and floors.

Notes

From 1 May 2023 to 30 September 2023 Section J of NCC 2019 Volume One Amendment 1 may apply instead of Section J of NCC 2022 Volume One. From 1 October 2023 Section J of NCC 2022 Volume One applies.

Notes: New South Wales Section J Energy Efficiency

  1. For a Class 2 building or a Class 4 part of a building, where a relevant development consent or an application for a complying development certificate requires compliance with a BASIX Single Dwelling or Multi Dwelling Certificate issued under Version 3.0 or earlier, NSW Section J of NCC 2019 Volume One Amendment 1 applies.
  2. For a Class 2 building or a Class 4 part of a building, where a relevant development consent or an application for a complying development certificate requires compliance with a BASIX Single Dwelling or Multi Dwelling Certificate issued under Version 4.0 or later, Section J of NCC 2022 Volume One applies.
  3. For a Class 2 building or a Class 4 part of a building, where a relevant development consent or an application for a complying development certificate requires compliance with a BASIX Alterations and Additions Certificate, NSW Section J of NCC 2019 Volume One Amendment 1 applies.
  4. For a Class 3 building or Class 5 to 9 building:
    1. From 1 May 2023 to 30 September 2023 NSW Section J of NCC 2019 Volume One Amendment 1 may apply instead of Section J of NCC 2022 Volume One.
    2. From 1 October 2023 Section J of NCC 2022 Volume One applies.

Notes: Tasmania Section J Energy Efficiency

In Tasmania, for a Class 2 building and Class 4 part of a building, Section J is replaced with Section J of BCA 2019 Amendment 1.

Deemed-to-Satisfy Provisions

(1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements J1P1 to J1P4 are satisfied by complying with—

  1. J2D2; and
  2. J3D2 to J3D15; and
  3. J4D2 to J4D7; and
  4. J5D2 to J5D8; and
  5. J6D2 to J6D13; and
  6. J7D2 to J7D9; and
  7. J8D2 to J8D4; and
  8. J9D2 to J9D5.

NSW J4D1 Deemed-to-Satisfy Provisions2019: J1.0

Delete subclause J4D1(1) and insert J4D1(1) as follows:

(1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements NSW J1P1 to NSW J1P7 are satisfied by complying with—

  1. NSW J2D2; and
  1. NSW J3D2 to J3D10; and
  2. NSW J4D2 to J4D7; and
  3. NSW J5D2 to J5D8; and
  4. NSW J6D2 to J6D13; and
  5. NSW J7D2 to J7D9; and
  6. J8D2 to NSW J8D4; and
  7. J9D2 to J9D5.

(2) Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2G2(3) and A2G4(3) as applicable.

NCC Blurbs

(1) The Deemed-to-Satisfy Provisions of this Part apply to building elements forming the envelope of a Class 3 and Class 5 to 9 building.

(2) NSW J4D3, applies to building elements forming the envelope of a sole-occupancy unit in a Class 2 building and a Class 4 part of a building.

(3) (2) only applies to thermal insulation in a sole-occupancy unit in a Class 2 building and a Class 4 part of a building where a development consent specifies that the insulation is to be provided as part of the development.

NCC Title

Application of Part

NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Application of Part

The Deemed-to-Satisfy Provisions of this Part apply to building elements forming the envelope of a Class 2 to 9 building other than J4D3(5), J4D4, J4D5, J4D6 and J4D7 which do not apply to a Class 2 sole-occupancy unit or a Class 4 part of a building.

NCC Blurbs

(1) Where required, insulation must comply with AS/NZS 4859.1 and be installed so that it—

  1. abuts or overlaps adjoining insulation other than at supporting members such as studs, noggings, joists, furring channels and the like where the insulation must be against the member; and
  2. forms a continuous barrier with ceilings, walls, bulkheads, floors or the like that inherently contribute to the thermal barrier; and
  3. does not affect the safe or effective operation of a service or fitting.

(2) Where required, reflective insulation must be installed with—

  1. the necessary airspace to achieve the required R-Value between a reflective side of the reflective insulation and a building lining or cladding; and
  2. the reflective insulation closely fitted against any penetration, door or window opening; and
  3. the reflective insulation adequately supported by framing members; and
  4. each adjoining sheet of roll membrane being—
    1. overlapped not less than 50 mm; or
    2. taped together.

(3) Where required, bulk insulation must be installed so that—

  1. it maintains its position and thickness, other than where it is compressed between cladding and supporting members, water pipes, electrical cabling or the like; and
  2. in a ceiling, where there is no bulk insulation or reflective insulation in the wall beneath, it overlaps the wall by not less than 50 mm.

(4) Roof, ceiling, wall and floor materials, and associated surfaces are deemed to have the thermal properties listed in Specification 36.

(5) The required Total R-Value and Total System U-Value, including allowance for thermal bridging, must be—

  1. calculated in accordance with AS/NZS 4859.2 for a roof or floor; or
  2. determined in accordance with Specification 37 for wall-glazing construction; or
  3. determined in accordance with Specification 39 or Section 3.5 of CIBSE Guide A for soil or sub-floor spaces.

Notes

Where required is deemed to refer to “Where a development consent specifies that insulation is to be provided as part of the development.”.

NCC Title

Thermal construction—general

NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Thermal construction—general

(1) Where required, insulation must comply with AS/NZS 4859.1 and be installed so that it—

  1. abuts or overlaps adjoining insulation other than at supporting members such as studs, noggings, joists, furring channels and the like where the insulation must be against the member; and
  2. forms a continuous barrier with ceilings, walls, bulkheads, floors or the like that inherently contribute to the thermal barrier; and
  3. does not affect the safe or effective operation of a service or fitting.

(2) Where required, reflective insulation must be installed with—

  1. the necessary airspace to achieve the required R-Value between a reflective side of the reflective insulation and a building lining or cladding; and
  2. the reflective insulation closely fitted against any penetration, door or window opening; and
  3. the reflective insulation adequately supported by framing members; and
  4. each adjoining sheet of roll membrane being—
    1. overlapped not less than 50 mm; or
    2. taped together.

(3) Where required, bulk insulation must be installed so that—

  1. it maintains its position and thickness, other than where it is compressed between cladding and supporting members, water pipes, electrical cabling or the like; and
  2. in a ceiling, where there is no bulk insulation or reflective insulation in the wall beneath, it overlaps the wall by not less than 50 mm.

(4) Roof, ceiling, wall and floor materials, and associated surfaces are deemed to have the thermal properties listed in Specification 36.

(5) The required Total R-Value and Total System U-Value, including allowance for thermal bridging, must be—

  1. calculated in accordance with AS/NZS 4859.2 for a roof or floor; or
  2. determined in accordance with Specification 37 for wall-glazing construction; or
  3. determined in accordance with Specification 39 or Section 3.5 of CIBSE Guide A for soil or sub-floor spaces.

(1) A roof or ceiling must achieve a Total R-Value greater than or equal to—

  1. in climate zones 1, 2, 3, 4 and 5, R3.7 for a downward direction of heat flow; and
  2. in climate zone 6, R3.2 for a downward direction of heat flow; and
  3. in climate zone 7, R3.7 for an upward direction of heat flow; and
  4. in climate zone 8, R4.8 for an upward direction of heat flow.

(2) In climate zones 1, 2, 3, 4, 5, 6 and 7, the solar absorptance of the upper surface of a roof must be not more than 0.45.

Roof lights must have—

  1. a total area of not more than 5% of the floor area of the room or space served; and
  2. transparent and translucent elements, including any imperforate ceiling diffuser, with a combined performance of—
    1. for Total system SHGC, in accordance with Table J4D5; and
    2. for Total system U-Value, not more than U3.9.
Table J4D5 Roof lights – Total system SHGC
Roof light shaft index Note 1 Total area of roof lights up to 3.5% of the floor area of the room or space Total area of roof lights more than 3.5% and up to 5% of the floor area of the room or space
<1.0 ≤ 0.45 ≤ 0.29
≥ 1.0 to < 2.5 ≤ 0.51 ≤ 0.33
≥ 2.5 ≤ 0.76 ≤ 0.49
Table Notes
  1. The roof light shaft index is determined by measuring the distance from the centre of the shaft at the roof to the centre of the shaft at the ceiling level and dividing it by the average internal dimension of the shaft opening at the ceiling level (or the diameter for a circular shaft) in the same units of measurement.
  2. The area of a roof light is the area of the roof opening that allows light to enter the building.
  3. The total area of roof lights is the combined area for all roof lights serving the room or space.
NCC Blurbs

(1) The Total System U-Value of wall-glazing construction, including wall-glazing construction which wholly or partly forms the envelope internally, must not be greater than—

  1. for a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, U2.0; and
  2. for a Class 3 or 9c building or a Class 9a ward area
    1. in climate zones 1, 3, 4, 6 or 7, U1.1; or
    2. in climate zones 2 or 5, U2.0; or
    3. in climate zone 8, U0.9.

(2) The Total System U-Value of display glazing must not be greater than U5.8.

(3) The Total System U-Value of wall-glazing construction must be calculated in accordance with Specification 37.

(4) Wall components of a wall-glazing construction must achieve a minimum Total R-Value of—

  1. where the wall is less than 80% of the area of the wall-glazing construction, R1.0; or
  2. where the wall is 80% or more of the area of the wall-glazing construction, the value specified in NSW Table J4D6a.

(5) The solar admittance of externally facing wall-glazing construction, excluding wall-glazing construction which is wholly internal, must not be greater than—

  1. for a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, the values specified in NSW Table J4D6b; and
  2. for a Class 3 or 9c building or a Class 9a ward area, the values specified in NSW Table J4D6c.

(6) The solar admittance of a wall-glazing construction must be calculated in accordance with Specification 37.

(7) The Total system SHGC of display glazing must not be greater than 0.81 divided by the applicable shading factor specified in S37C7.

Insert NSW table (NSW J4D6a) J4D6 as follows:
NSW Table NSW J4D6a: Minimum wall Total R-Value - Wall area 80% or more of wall-glazing construction area
Climate zone Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area Class 3 or 9c building or Class 9a ward area
1 2.4 3.3
2 1.4 1.4
3 1.4 3.3
4 1.4 2.8
5 1.4 1.4
6 1.4 2.8
7 1.4 2.8
8 1.4 3.8
Insert NSW table (J4D6b) J4D6 as follows:
NSW Table J4D6b: Maximum wall-glazing construction solar admittance - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Climate zone Eastern aspect solar admittance Northern aspect solar admittance Southern aspect solar admittance  Western aspect solar admittance
1 0.12 0.12 0.12 0.12
2 0.13 0.13 0.13 0.13
3 0.16 0.16 0.16 0.16
4 0.13 0.13 0.13 0.13
5 0.13 0.13 0.13 0.13
6 0.13 0.13 0.13 0.13
7 0.13 0.13 0.13 0.13
8 0.2 0.2 0.42 0.36
Table J4D6c Maximum wall-glazing construction solar admittance - Class 3 or 9c building or Class 9a ward area
Climate zone Eastern aspect solar admittance Northern aspect solar admittance Southern aspect solar admittance Western aspect solar admittance
1 0.07 0.07 0.10 0.07
2 0.10 0.10 0.10 0.10
3 0.07 0.07 0.07 0.07
4 0.07 0.07 0.07 0.07
5 0.10 0.10 0.10 0.10
6 0.07 0.07 0.07 0.07
7 0.07 0.07 0.08 0.07
8 0.08 0.08 0.08 0.08
NCC Title

Walls and glazing

NCC State
NSW
NCC Variation Type
Replacement
NCC SPTC Current
Walls and glazing

(1) The Total System U-Value of wall-glazing construction, including wall-glazing construction which wholly or partly forms the envelope internally, must not be greater than—

  1. for a Class 2 common area, a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, U2.0; and
  2. for a Class 3 or 9c building or a Class 9a ward area
    1. in climate zones 1, 3, 4, 6 or 7, U1.1; or
    2. in climate zones 2 or 5, U2.0; or
    3. in climate zone 8, U0.9.

(2) The Total System U-Value of display glazing must not be greater than U5.8.

(3) The Total System U-Value of wall-glazing construction must be calculated in accordance with Specification 37.

(4) Wall components of a wall-glazing construction must achieve a minimum Total R-Value of—

  1. where the wall is less than 80% of the area of the wall-glazing construction, R1.0; or
  2. where the wall is 80% or more of the area of the wall-glazing construction, the value specified in Table J4D6a.

(5) The solar admittance of externally facing wall-glazing construction, excluding wall-glazing construction which is wholly internal, must not be greater than—

  1. for a Class 2 common area, a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, the values specified in Table J4D6b; and
  2. for a Class 3 or 9c building or a Class 9a ward area, the values specified in Table J4D6c.

(6) The solar admittance of a wall-glazing construction must be calculated in accordance with Specification 37.

(7) The Total system SHGC of display glazing must not be greater than 0.81 divided by the applicable shading factor specified in S37C7.

Table J4D6a Minimum wall Total R-Value - Wall area 80% or more of wall-glazing construction area
Climate zone Class 2 common area, Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area Class 3 or 9c building or Class 9a ward area
1 2.4 3.3
2 1.4 1.4
3 1.4 3.3
4 1.4 2.8
5 1.4 1.4
6 1.4 2.8
7 1.4 2.8
8 1.4 3.8
Table J4D6b Maximum wall-glazing construction solar admittance - Class 2 common area, Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Climate zone Eastern aspect solar admittance Northern aspect solar admittance Southern aspect solar admittance  Western aspect solar admittance
1 0.12 0.12 0.12 0.12
2 0.13 0.13 0.13 0.13
3 0.16 0.16 0.16 0.16
4 0.13 0.13 0.13 0.13
5 0.13 0.13 0.13 0.13
6 0.13 0.13 0.13 0.13
7 0.13 0.13 0.13 0.13
8 0.2 0.2 0.42 0.36
Table J4D6c Maximum wall-glazing construction solar admittance - Class 3 or 9c building or Class 9a ward area
Climate zone Eastern aspect solar admittance Northern aspect solar admittance Southern aspect solar admittance Western aspect solar admittance
1 0.07 0.07 0.10 0.07
2 0.10 0.10 0.10 0.10
3 0.07 0.07 0.07 0.07
4 0.07 0.07 0.07 0.07
5 0.10 0.10 0.10 0.10
6 0.07 0.07 0.07 0.07
7 0.07 0.07 0.08 0.07
8 0.08 0.08 0.08 0.08

(1) A floor must achieve the Total R-Value specified in Table J4D7.

(2) For the purposes of (1), a slab-on-ground that does not have an in-slab heating or cooling system is considered to achieve a Total R-Value of R2.0, except—

  1. in climate zone 8; or
  2. a Class 3, Class 9a ward area or Class 9b building in climate zone 7 that has a floor area to floor perimeter ratio of less than or equal to 2.

(3) A floor must be insulated around the vertical edge of its perimeter with insulation having an R-Value greater than or equal to 1.0 when the floor—

  1. is a concrete slab-on-ground in climate zone 8; or
  2. has an in-slab or in-screed heating or cooling system, except where used solely in a bathroom, amenity area or the like.

(4) Insulation required by (3) for a concrete slab-on-ground must—

  1. be water resistant; and
  2. be continuous from the adjacent finished ground level—
    1. to a depth not less than 300 mm; or
    2. for the full depth of the vertical edge of the concrete slab-on-ground.
Table J4D7 Floors – Minimum Total R-Value
Location Climate zone 1— upwards heat flow Climate zones 2 and 3 — upwards and downwards heat flow Climate zones 4, 5, 6 and 7 — downwards heat flow Climate zone 8 — downwards heat flow
A floor without an in-slab heating or cooling system 2.0 2.0 2.0 3.5
A floor with an in-slab heating or cooling system 3.25 3.25 3.25 4.75
Table Notes

For the purpose of calculating the Total R-Value of a floor, the sub-floor and soil R-Value must be calculated in accordance with Specification 39 or Section 3.5 of CIBSE Guide A.