A farm shed need not comply with the provisions of Parts C2, C3 and C4, except for C2D12, if it is separated from any other building or allotment boundary by a distance of not less than 6 m.
A fixed platform, stairway, ladder and any going and riser, landing, handrail or barrier may comply with AS 1657 in lieu of D3D14, D3D15, D3D17 to D3D21 and D3D22 where it serves a farm building or a farm shed.
The threshold of a doorway that serves an area not required to be accessible by D4D2 in a farm building need not comply with D3D16 where the door sill is not more than 700 mm above the finished surface of the ground, floor or the like, to which the doorway opens.
provided with a fire hydrant system installed in accordance with AS 2419.1, except reference to ‘4 hours’ water supply in clause 4.2 is replaced with ‘2 hours’; or
located on the same allotment as an access point to a water supply which—
has a minimum total capacity of 144,000 litres; and
is situated so as to enable emergency services vehicles access to within 4 m; and
is located within 60 m of the building and not more than 90 m from any part of the building.
(3) For the purposes of (2)(b), water supply for a farm building must consist of one or any number of the following:
A water storage tank.
A dam.
A reservoir.
A river.
A lake.
A bore.
A sea.
(4) If the whole or part of the water supply referred to in (2)(b) is contained in a water storage tank, it must be—
located not less than 10 m from the building; and
fitted with at least one small bore suction connection and one large bore suction connection where—
each suction connection is located in a position so as to enable emergency service vehicles access to within 4 m; and
the suction connections are located not less than 10 m from the building; and
‘small bore suction connection’ and ‘large bore suction connection’ have the meanings contained in AS 2419.1.
(1) A farm building not provided with a fire hose reel system in accordance with E1D3 must be provided with—
one portable fire extinguisher rated at not less than 5ABE in each room containing flammable materials or electrical equipment; and
one portable fire extinguisher rated at not less than 4A60BE adjacent to every requiredexit door; and
location signs complying with clauses 3.3 to 3.9 of AS 2444 above each required portable fire extinguisher.
(2) A farm shed must be provided with not less than one portable fire extinguisher for every 500 m2 of floor area or part thereof, distributed as evenly as practicable throughout the building.
(3) A portable fire extinguisher required by (2) must be—
of ABE type; and
not less than 4.5 kg in size; and
installed in accordance with Section 3 of AS 2444.
(1) An emergency lighting system need not be installed in a farm building—
with no artificial lighting as permitted by I3D18; or
with artificial lighting where, if that lighting fails due to an emergency, automatic power supply to the building is provided by a fuel-driven generator.
(2) An emergency lighting system need not be installed in a farm shed.
In a farm building or a farm shed, if an exit is not readily apparent to persons occupying or visiting the building, exit signs complying with I3D15 must be installed in appropriate positions in corridors, hallways, lobbies and the like, indicating the direction to a requiredexit.
the use of illuminated exit signs may adversely impact the behaviour or welfare of animals being kept in the building; and
non-illuminated exit signs are installed in accordance with the requirements of Appendix D of AS/NZS 2293.1 as for an externally illuminated exit sign, and clauses 5.6 and 5.8 of AS/NZS 2293.1.
non-illuminated exit signs are installed in accordance with the requirements of Appendix D of AS/NZS 2293.1 as for an externally illuminated exit sign, and clauses 5.6 and 5.8 of AS/NZS 2293.1; and
the maximum viewing distance in clause 5.6 of AS/NZS 2293.1 is not more than 24 m.
F5D2 does not apply to a farm shed which has ceiling heights not less than—
in a room, corridor, passageway or the like — 2.1 m; and
in a room or space with a sloping ceiling or projections — a height of not less than 2.1 m for at least two-thirds of the floor area of the room or space, and when calculating the floor area of the room or space, any part that has a ceiling height of less than 1.5 m is not included; and
in a stairway, ramp, landing or the like — 2.0 m measured vertically above the nosing line of stairway treads or the floor surface of the ramp, landing or the like.