(1) The test is conducted on a specimen of prototype wall construction and on a specimen of one or other of the constructions specified in NT S28C3.
(2) The testing of construction specified in NT S28C3 need not be repeated for subsequent comparisons provided complete records of the results, the test equipment and the technique of testing are kept so that identical equipment can be employed and an identical technique can be adopted in the testing of specimens of prototype wall construction.
NCC Title
Construction to be tested
NCC State
NT
NCC Variation Type
Replacement
NCC SPTC Current
Construction to be tested
NCC ID
_0f0b7895-5514-4139-b484-b6fdce1dfc0f
Building Classes
1a,1b,4,5,6,7a,7b,8,9a,9b,10a,10b,10c
(1) The test is conducted on a specimen of prototype wall construction and on a specimen of one or other of the constructions specified in S28C4 to S28C7.
(2) The testing of a construction specified in S28C4 to S28C7 need not be repeated for subsequent comparisons provided complete records of the results, the test equipment and the technique of testing are kept so that identical equipment can be employed and an identical technique can be adopted in the testing of specimens of prototype wall construction.
(1) The wall constructions to be compared must be tested in accordance with AS 1191.
(2) A horizontal steel platform 510 mm x 460 mm x 10 mm thick must be placed with one long edge in continuous and direct contact with the wall to be tested on the side of the wall on which the impact sound is to be generated.
(3) A tapping machine complying with ISO 140/6 — 1998 (E) must be mounted centrally on the steel platform.
(4) The sound transmission through the wall must be determined in accordance with AS 1191 except that the tapping machine as mounted on the steel platform must be used as the source of sound.
(5) The impact sound pressure levels measured in the receiving room must be converted into normalised levels using a reference equivalent absorption area of 10m2.
NCC Title
Method
NCC State
NT
NCC Variation Type
Replacement
NCC SPTC Current
Method
NCC ID
_9d2140b9-e150-439c-bd9b-6f8a97ef0495
Building Classes
1a,1b,4,5,6,7a,7b,8,9a,9b,10a,10b,10c
(1) The wall constructions to be compared must be tested in accordance with AS 1191.
(2) A horizontal steel platform 510 mm x 460 mm x 10 mm thick must be placed with one long edge in continuous and direct contact with the wall to be tested on the side of the wall on which the impact sound is to be generated.
(3) A tapping machine complying with ISO 140/6 — 1998 (E) must be mounted centrally on the steel platform.
(4) The sound transmission through the wall must be determined in accordance with AS 1191 except that the tapping machine as mounted on the steel platform must be used as the source of sound.
(5) The impact sound pressure levels measured in the receiving room must be converted into normalised levels using a reference equivalent absorption area of 10 m2.