TAS Part I10 Mortuaries
Introduction to this Part
This Part contains additional requirements for mortuaries.
Deemed-to-Satisfy Provisions
NCC Blurbs
(1) This Part applies to any premises used for the storage or preparation for burial, cremation or disposal by other means, of bodies of deceased persons.
(2) Mortuaries must be constructed in a manner that will ensure the health of staff and the general public.
NCC SPTC Current
Application of Part
NCC ID
_f32e8c90-a8d2-4d92-9865-1db4214d2aff
NCC Blurbs
(1) A mortuary may be integral with the remainder of a building but must be separated physically from all public areas of that building.
(2) Each mortuary at which bodies are prepared for burial, cremation or other disposal must be provided with a body preparation room—
- capable of being isolated from the remainder of the premises; and
- having a floor area not less than 10m2.
(3) A vehicle reception area or garage must be provided adjacent to and with direct access to the storage room or body preparation room to ensure that the transfer of uncoffined bodies is screened from public view.
(4) Access to toilet and shower facilities from any other part of the mortuary premises must be only by way of an air lock.
NCC SPTC Current
Layout of mortuary
NCC ID
_6170e742-bea2-49ca-b756-3138e1d15ceb
NCC Blurbs
(1) The floor must be—
- of impervious material with a smooth, unbroken surface; and
- uniformly graded to a floor drain.
(2) All walls and partitions must be of concrete or masonry with a smooth, unbroken finish for ease of cleaning.
(3) All joints between the floor, walls, partitions, ceiling, ventilation grilles, fittings, pipework, windows and light fittings must be sealed with impervious material for ease of cleaning.
(4) All joints between the floor and walls or partitions must be coved for ease of cleaning.
(5) The body preparation room must be provided with at least one washbasin, fitting with elbow or foot-operated taps, and an adequate supply of hot and cold water.
(6) The body preparation room must be provided with refrigerated storage facilities—
- With sufficient capacity for the storage of at least two adult bodies; and
- Capable of maintaining an internal temperature between 1°C and 5°C.
NCC Title
Construction of body preparation room
NCC SPTC Current
Construction of body preparation room
NCC ID
_0b630272-a5c2-4868-b118-928025db94f6
NCC Blurbs
Each mortuary with a body preparation room must be connected to—
- a permanent water supply with a physical discontinuity, provided by a registered break tank or reduced pressure zone device, between the water supply and all equipment, appliances, fittings and areas in the mortuary; and
- a water carriage sewerage system.
NCC Title
Water supply and sewerage
NCC SPTC Current
Water supply and sewerage
NCC ID
_b7d3f7ff-9479-48b4-b308-f1513a97d313